12. If you
don’t see
a rise in received signal strength
You will be presented with the screen below
(AQ-air quality could be any number up to 40%)
Now look at the position of the reflector in relation to the beam head. You will need to angle
the beam toward the reflector by moving the head about its X or Y axis using the internal
motors
In the example below you will notice that the reflector is below the line of fire of the beam.
So in this case you would need to lower the angle of the beam (-Y) until you receive a AQ
(Air Quality)
reading above 40% sensitivity. (
40 steps of the motor = 1degree of movement)
Y +
X+
X -
Y -
Y -
To make adjustments
to the X and Y axis you
need to press
enter
.
This will then display
an
*
(adjustment
mode)
beside the
X
and
Y
co-ordinates
40 steps = 1 degree off movement
Adjustments can now be
made to the
X
and
Y
axis
by using the
left
(
x-
),
right
(
x+
),
up
(
y+
),
down
(
y-
) keys. Looking
at the reflector this will
move the beam across
the reflector like so
(40 steps = 1degree)
(you can hold the key down for
faster increments)
in the example above
moving the
y
axis
down
(
y-
) results in a
greater % air quality
now press
enter
to exit
*
(adjustment mode)
and view changing
x
and
y
values.
Re-press
enter
to display
*
(adjustment mode)
to stop movement or to make a further change
to values
beam head
reflector