7

Using the OBELISK top2 memory card

 

L

The OBELISK top2 memory card is not included in the 
scope of supply of the device, but can be ordered as an 
accessory (9070404). 

All functions can also be set on the PC using the OBELISK 

software and transferred to the device via the memory card.

¾

†

Insert memory card in the time switch

¾

†

Read in/out saved switching times and device setups in 

the time switch or start Obelisk program

¾

†

Remove memory card after copying etc.

 

!

Avoid mechanical overload and contamination during 
storage/transport

Copying OBELISK → Time switch
This copies the switch programme and optionally all time 

switch settings (e.g. form time etc.) from the memory card to 

the time switch.

Copying Time switch → OBELISK
Copies all switch programmes and settings from the 

time switch to the memory card.

Starting OBELISK program
Takes over the switching times that are programmed on the 

memory card.

As soon as the memory card is removed, the switching times 

of the time switch are re-activated.

u

u

u

OBELISK

COPY

OBELISK -> 

TIME

COPY TIME 

SWITCH -> 

OBELISK

RUN OBELISK

CHECK 

OBELISK

OVERWRITE 

OK

OVERWRITE 

OK

 

L

The current OBELISK top2 PC software is available at  
www.theben.de.

Resetting the time switch

¾

†

Press the 4 buttons simultaneously

 

▻ You can choose between RETAIN PROGRAMS and 

DELETE PROGRAMS

6.  Technical data

Operating voltage

12–24 V, 50–60 Hz, +10 % / –15 %, 

12–24 V DC, +10 % / –15 %

Standby

0.9 W (1714100) 

0.2 W (1724100)

Switching capacity max.

16 A (at 250 V AC, cos 

ϕ

 = 1)

Switching capacity

2 A (at 250 V AC, cos 

ϕ

 = 0.6)

Switching capacity min.

10 mA/230 V AC

100 mA/12 V AC/DC

Protection rating 

IP 20 in accordance with EN 60529

Protection class 

Protection class: II in accordance 

with EN 60730-1 subject to correct 

installation for supply with FELV and/

or mains switching

Protection class

III for supply with SELV and switching 

of SELV

Operating temperature 

–30 °C … +55 °C

Shortest switching time

1 min.

Power reserve 

10 years at +20 °C

Time accuracy (typical)

± 0.25 s/day (25 °C)

Rated impulse voltage 

4 kV

Pollution degree 

2

Contact

Changeover contact, µ contact

Max. switching cycles with 16 A 

resistive load 

50 000

Incandescent lamp load

1000 W

Halogen lamp load (230 V)

1000 W

Fluorescent lamps (LLB low-loss  

ballasts): 

uncompensated (230 V) 

series compensated (230 V) 

parallel compensated (230 V)

1000 VA

1000 VA

80 W (max. 12 µF) 

Fluorescent lamps (EB – Electronic 

Ballasts) (230 V)

120 W

Compact fluorescent lamps (EB) 

30 W

LED lamps (< 2 W)

6 W

LED lamps (2 W – 8 W)

20 W

LED lamps (> 8 W)

25 W

Corresponds to type 1 BSTU in 

accordance with IEC/EN 60730-2-7 

or IEC/EN 60730-1
Switching of any external conductor 

is permitted.
Approved for switching SELV and 

mains voltage

7.  Contact

Theben AG

Hohenbergstr. 32

72401 Haigerloch

GERMANY

Phone +49 7474 692-0

Fax +49 7474 692-150
Hotline

Phone +49 7474 692-369

hotline@theben.de

Addresses, telephone numbers etc. 

www.theben.de

Summary of Contents for 1714100

Page 1: ...oper use The astronomical time switch is used for instance for lighting equipment roads external staircases display windows entrances etc Only for use in closed dry rooms Do not use on safety devices...

Page 2: ...NU Activate display Open menu Cancel menu ESC leave menu OK Save selection Confirm selection Options are displayed 0 6 12 18 24 Time display Sunrise sunset display Date display Channel status C1 C2 ON...

Page 3: ...alue can be used to shift the calculated astro times by 120 min This means that the astro turn on and turn off times can be adapted to local conditions e g mountains high buildings etc or to personal...

Page 4: ...3 types of date areas Fixed date area e g starting time on 2015 04 02 at 04 00 p m end time on 2015 04 24 at 10 00 a m Yearly repeating date area e g Christmas starting time on 24 12 at 06 00 p m ever...

Page 5: ...HOLIDAY END Press MENU Select MANUAL and press OK to confirm Select CHANNEL confirm with OK Select PERM ON or PERM OFF and press OK to confirm Setting holiday function MANUAL MENU u CHANNEL C1 u PERM...

Page 6: ...ously for 2 seconds Cancelling manual permanent switching Press both buttons simultaneously Hour counter The operating hours of the channel relay are displayed and deleted in the OPTIONS menu If the n...

Page 7: ...ta Operating voltage 12 24 V 50 60 Hz 10 15 12 24 V DC 10 15 Standby 0 9 W 1714100 0 2 W 1724100 Switching capacity max 16 A at 250 V AC cos 1 Switching capacity 2 A at 250 V AC cos 0 6 Switching capa...

Reviews: