ETS communication objects
Manual DALI gateway S64 KNX/S128 KNX
26
8.2
Objects for the time control module
For each of the up to 16 templates in the colour control module communication objects are
available for activation/deactivation. Please see chapter 13.3 Disabling/enabling. These need to
be enabled under time control in the DCA.
Obj
Object name
Function
Type
Flags
23
Template 1, Activate
Activate/stop
1 Bit
1.010
CW
This object activates template 1 in the colour control module. If the value is 1, the template is
active and will be executed according to schedule.
24ff
Template x, Activate
Activate/stop
1 Bit
1.010
CW
This object activates template x in the colour control module. If the value is 1, the template is
active and will be executed according to schedule.
8.3
Objects for energy saving
There are 16 energy-saving objects available which can be assigned to groups resp. ECGs in the
corresponding parameters. Therefore, it is possible to activate and deactivate the ECG power
with an additional switching actuator.
55
Energy Saving Object 1
On / Off
1 Bit
1.001
CRT
With the appropriate assignment in the parameters, this object is switched off when
associated groups or ECGs are switched off. This allows a separate power supply to be
switched off. If the associated groups or ECGs are controlled again with a value > 0%, this
object is switched on again before.
In this case, a minimum time delay is programmed so that the ECGs are ready for operation
again.
56ff
Energy Saving Object x
On / Off
1 Bit
1.001
CRT
With the appropriate assignment in the parameters, this object is switched off when
associated groups or ECGs are switched off. This allows a separate power supply to be
switched off. If the associated groups or ECGs are controlled again with a value > 0%, this
object is switched on again before.
In this case, a minimum time delay is programmed so that the ECGs are ready for operation
again.