ETS parameters
Manual DALI gateway S64 KNX/S128 KNX
39
9
ETS parameters
The ETS parameters of the device are distributed across different parameter pages. To simplify
the overview, only the parameter pages of the device selected in the function tree are displayed.
2 channel device
: All parameter pages of the 1st channel are marked with the prefix D1-
and those of the 2nd channel with the prefix D2-. In the following description this prefix
will be omitted.
9.1
General
Three parameter pages are available under the heading “General“. The parameters are
described below.
9.1.1
Parameter page – behaviour
Parameter
Settings
Behaviour on KNX Failure
No Action
Switch to On-Value
Switch to Off-Value
Switch to Emergency-Value
Use this parameter to set the behaviour of the connected ECGs/lamps on KNX failure.
Behaviour on KNX Voltage Recovery
No Action
Switch to Last Value
Switch to On-Value
Switch to Off-Value
Use this parameter to set the behaviour of the connected ECGs/lamps on KNX voltage
recovery or bus reset.