ETS parameters
Manual DALI gateway S64 KNX/S128 KNX
49
Value-Set Behaviour
Set Value immediately
Dim to Value in 3 Seconds
Dim to Value in 6 Seconds
Dim to Value in 10 Seconds
Dim to Value in 20 Seconds
Dim to Value in 30 Seconds
Dim to Value in 1 Minute
Dim to Value in 2 Minutes
Dim to Value in 5 Minutes
Dim to Value in 10 Minutes
Sets the behaviour on receipt of a new dim value via value setting. Please remember that the
time always refers to the complete value range. A time of 30 s therefore means a value
change of 100 % within 30 s. If the value within a scene only changes by 50 %, the change
will only take 15 s.
Time for Dimming
3 Seconds
4 Seconds
5 Seconds
6 Seconds
10 Seconds
20 Seconds
30 Seconds
60 Seconds
Sets the dim time for relative dimming in relation to a value range from 0 to 100 %.
Max. Value for Dimming
50 %
55 %
….
100 %
Use this parameter to configure the maximum dim value that can be set through relative
dimming.
Min. Value for Dimming
0 %
0.5 %
1 %
…
5 %
….
50 %
Use this parameter to configure the minimum dim value that can be set through relative
dimming.