Hardware Manual COMBILOG 1020
133
D0 - Dn ....... databytes (max. 64)
CRC ............ check sum
CRC polynom: u
15
+ u
13
+ 1
CRC start value: hex FFFF
Read Input Register
Description:
By this command input registers (read-only registers) can be
read.
request telegram
ADR FNR REGSTA
REGNUM CRC
04
MSB LSB MSB LSB MSB LSB
response telegram
ADR FNR BYTNUM D0 D1
Dn CRC
04
…
MSB
LSB
ADR ............ module address (hex 00..7F)
FNR ............ function number (hex 04)
REGSTA ..... address of the first register to be read
REGNUM .... number of registers to be read
BYTNUM ..... number of databytes (max. 64)
D0 - Dn ....... databytes (max. 64)
CRC ............ check sum
CRC polynom: u
15
+ u
13
+ 1
CRC start value: hex FFFF