Hardware Manual COMBILOG 1020
17
All data can be transmitted via the integrated RS485 communi-
cation interface to a subsequent control (PLC) or to a computer
(PC). Up to 127 modules can be connected with the two-wire line
over distances of several km. At the same time the communica-
tion interface features programming and configuring the individual
application from a PC.
If the datalogger
COMBILOG 1020
is not integrated in a bus, an
additional RS232-interface is available for the user. This interface
allows only a point-to-point connection up to max. 20 m (65 feet),
but all functions of the RS485-interface remain available.
Furthermore the datalogger can send messages in case of user
definable conditions automatically via modem or SMS.
A configuration program is included (requires Microsoft
WINDOWS 98,ME,NT,2000, XP).
2.3 Features
Function:
Measurement inputs for all common types of sensors for I, U
and R.
Several different sensors can be connected simultaneously
Measured values monitored by programmable thresholds
Detection of sensor errors
Detection of communication errors
Programmable error handling
Calculation of average values, minima, maxima, standard
deviation and other arithmetic functions
256 kB RAM internal data storage, extendadble upto 8 MB
with PCMCIA SRAM card (max. 65536 datasets)
linear Flash memory cards up to 16 MB
Summary of Contents for COMBILOG 1020
Page 1: ...COMBILOG 1020 Datalogger Hardware Manual Version 3 09...
Page 2: ...Hardware Manual COMBILOG 1020 2 Issue 03 11 2005 Technical data are subject to change...
Page 4: ...Hardware Manual COMBILOG 1020 4...
Page 6: ...Hardware Manual COMBILOG 1020 6...
Page 12: ...Hardware Manual COMBILOG 1020 12...
Page 86: ...Hardware Manual COMBILOG 1020 86 Bild 8 1 Example Master Slave System...
Page 169: ...Hardware Manual COMBILOG 1020 169...
Page 170: ...Hardware Manual COMBILOG 1020 170...