Hardware Manual COMBILOG 1020
38
4.5 Scan Rate and power consumption
The A/D-converter digitalizes every signal at a rate that can be
preset by the user. The scan rate can be selected between 0.5
sec. and 1 hour. In this selected time period all configured chan-
nels are scanned and processed correspondingly. The power
consumption of the datalogger
COMBILOG 1020
depends on this
scan rate. Between the measuring cycles the datalogger will be
set into a so-called “Sleep-Mode“. During this mode the datalog-
ger needs only about 5 mW. The average current consumption
over a longer time period will be accordingly:
filter
number of used
scan rate
analog inputs
1 sec
10 sec
60 sec
1
20 mA
6.5 mA
5.3 mA
2
25 mA
7.0 mA
5.3 mA
3
30 mA
7.5 mA
5.4 mA
50 / 60 Hz
4
35 mA
8.0 mA
5.5 mA
5
40 mA
8.5 mA
5.6 mA
6
45 mA
9.0 mA
5.7 mA
7
50 mA
9.5 mA
5.8 mA
8
55 mA
10.0 mA
5.8 mA
1
16.3 mA
6.1 mA
5.2 mA
2
17.5 mA
6.3 mA
5.2 mA
3
18.8 mA
6.4 mA
5.2 mA
200 Hz
4
20.0 mA
6.5 mA
5.3 mA
Accu-operation
5
21.3 mA
6.6 mA
5.3 mA
6
22.5 mA
6.8 mA
5.3 mA
7
23.8 mA
6.9 mA
5.3 mA
8
25.0 mA
7.0 mA
5.3 mA
Table 4.1 Current consumption at 12 VDC depending on the scan rate
(5 MHz version)
Summary of Contents for COMBILOG 1020
Page 1: ...COMBILOG 1020 Datalogger Hardware Manual Version 3 09...
Page 2: ...Hardware Manual COMBILOG 1020 2 Issue 03 11 2005 Technical data are subject to change...
Page 4: ...Hardware Manual COMBILOG 1020 4...
Page 6: ...Hardware Manual COMBILOG 1020 6...
Page 12: ...Hardware Manual COMBILOG 1020 12...
Page 86: ...Hardware Manual COMBILOG 1020 86 Bild 8 1 Example Master Slave System...
Page 169: ...Hardware Manual COMBILOG 1020 169...
Page 170: ...Hardware Manual COMBILOG 1020 170...