Hardware Manual COMBILOG 1020
75
Channels settings:
Meas. of Voltage
0.831 V
Main Menu
9
8
Offset
0.00000
Factor
1.00000
Default Value
55
9
8
New Set-Value
55.00000
(1)
(2)
In order to change the values the press/rotary knob must be
pressed. Thereby a cursor will be set on the first character of the
value. Pressing the knob again moves the cursor one character
to the right. The value at the place of the cursor can be altered by
turning the knob. Clockwise (=upwards) or counterclockwise
(=downwards).
Note:
Depending on the type of channel different settings can be
made.
(1)
the definition of offset and factor is possible for the analog
input channel, the digital input channel and the digital output
channel. These settings are used to convert the measure-
ment value from the unit of the measured value to the unit of
the measurement display.
(2)
For the setpoint channel a setpoint value can be defined if
this is allowed by the configuration software
COMBILOG.EXE
. This value can be used by the datalogger
for further processing (e.g. for the arithmetic channel).
For the arithmetic channel and the alarm channel no settings can
be made.
Summary of Contents for COMBILOG 1020
Page 1: ...COMBILOG 1020 Datalogger Hardware Manual Version 3 09...
Page 2: ...Hardware Manual COMBILOG 1020 2 Issue 03 11 2005 Technical data are subject to change...
Page 4: ...Hardware Manual COMBILOG 1020 4...
Page 6: ...Hardware Manual COMBILOG 1020 6...
Page 12: ...Hardware Manual COMBILOG 1020 12...
Page 86: ...Hardware Manual COMBILOG 1020 86 Bild 8 1 Example Master Slave System...
Page 169: ...Hardware Manual COMBILOG 1020 169...
Page 170: ...Hardware Manual COMBILOG 1020 170...