Hardware Manual COMBILOG 1020
78
7
DATA STORAGE
7.1 General Remarks to Data Storage
Data storage with the COMBILOG 1020 can be accomplished in
three different manners:
Internal RAM
: 252 KByte are available as circulated buffer for
data recording.
External PCMCIA SRAM Card:
This is an extension up to 32
Mbytes memory. The internal RAM will be deactivated if an
SRAM Card is used, i.e. the card replaces the internal RAM. The
maximum number of datarecords is limited to 65565.
External PCMCIA Flash Card:
The records are continuously
stored on this card. The maximum memory capacity is 16 MByte.
7.2 Modes of Data Storage
No Data Storage
In this mode the COMBILOG 1020 operates as measuring mo-
dule, processes measuring values and sends the results to a PC
upon command.
Continuous Data Storage
This is the normal operation of the datalogger. The measured val-
ues, selected for storage, are continuously written to internal or
external memory, with the preset averaging interval.