Hardware Manual COMBILOG 1020
93
Note:
These specifications refer to bus cables with a conductor
cross section of 0.22 mm² and a permissible signal attenuation of
max. 6 dB referred to the overall length. According to previous
experience the line length can be twice as long if a two-wire cir-
cuit with a conductor cross section of at least 0.5 mm² is used.
10.4 Bus Cable
For setting up a bus topology a shielded twisted pair with at least
two leads and the following electric characteristic values should
be used:
characteristic impedance :
100 ... 130
Ω
at f > 100 kHz
operating capacity
:
max. 60 pF/m
conductor cross section :
min. 0.22 mm² (AWG 24)
attenuation
:
max. 6dB referred to the overall
length