background image

5

www.thermastor.com • sales@thermastor.com

Toll-Free 1-800-533-7533

coil where it absorbs heat from the incoming air and 
evaporates.

The evaporator operates in a flooded condition, which 
means that all the evaporator tubes contain liquid 
refrigerant during normal operation. A flooded evaporator 
should maintain constant pressure and temperature 
across the entire coil, from inlet to outlet.
The mixture of gas and liquid refrigerant enter the 
accumulator after leaving the evaporator coil. The 
accumulator prevents any liquid refrigerant from reaching 
the compressor. The compressor evacuates the cool 
refrigerant gas from the accumulator and compresses it to 
a high pressure and temperature to repeat the process.

4.3 Troubleshooting

No dehumidification. Neither blower or compressor run. 
Power switch does not light when ON.

.  Unit unplugged or no power to outlet.
2.  Power switch defective (Sec. 2.6).
3.  Loose connection in internal wiring (Fig. 3).

No dehumidification. Neither blower or compressor run. 
Power switch ON and lit.

.  Low pressure control open (Sec. 2.).
2.  Power switch defective (Sec. 2.6).
3.  Loose connection in internal wiring (Fig. 3).

Some dehumidification, blower runs continuously but 
compressor only runs sporadically.

.  Unit is in defrost cycle (Sec. 2.0 and 4.7).
2.  Defrost thermostat defective or loose 
 

(Sec. 2.0 and 4.7).

3.  Loose connection in compressor circuit 
 

(see Fig. 3).

4.  Defective compressor overload (Sec. 4.6A).

5.  Defective compressor (Sec. 4.6).
6.  Defective relay (Sec. 4.9).
7.  Defective time delay (Sec. 4.0).

No dehumidification. Blower runs but compressor does not. 
Pump fail light not lit.

.  Bad connection in compressor circuit (Fig. 3).
2.  Defective compressor capacitor (Sec. 4.6A).
3.  Defective compressor overload (Sec. 4.6A).
4.  Defective compressor (Sec. 4.6).
5.  Defective relay (Sec. 4.9).
6.  Defective time delay (Sec. 4.0).

No dehumidification. Pump Fail Light lit. Blower runs but 
not compressor.

.  Bad connection in pump circuit (Fig. 3).
2.  Pump float switch or safety switch defective (Sec. 4.8).
3.  Pump motor defective (Sec. 4.8).

Blower does not run. Compressor runs briefly but cycles on 
and off.

.  Loose connection in blower circuit (Fig. 3).
2.  Obstruction prevents impeller rotation.
3.  Defective blower (Sec. 4.5).

Unit removes some water but not as much as expected.

.  Air temperature and/or humidity have dropped.
2.  Humidity meter and/or thermometer used are out of 

calibration.

3.  Unit has entered defrost cycle (Sec. 2.0 and 4.7).
4.  Air filter dirty (Sec. 3.).
5.  Defrost timer incorrectly set for conditions (Sec. 2.0 

and 4.7).

6.  Defective defrost thermostat (Sec. 4.7)
7.  Low refrigerant charge (Sec. 4.4).
8.  Air leak such as loose cover.
9.  Defective compressor (Sec. 4.6).
0. Restrictive exhaust ducting (Sec. 2.5)

Unit runs but does not pump water.

.  Hose kinked or plugged.
2.  Pump check valve plugged (Sec. 4.8).
3.  Bad connection in pump circuit (Fig. 3).
4.  Hose disconnected internally.

Unit pumps water automatically but not when purge switch 
is pushed.

.  Bad connection in purge switch circuit (Fig. 3).
2.  Defective purge switch (Sec. 2.7).

Figure 2: Refrigeration system of Phoenix

Summary of Contents for 4022599

Page 1: ...s filtration dramatically improves the air quality in the areas being dried and assures continued optimal performance of the refrigeration system The Phoenix 300 High Capacity Dehumidifier High capacity Up to 38 gallons per day High energy efficiency Plugs into a grounded 115V outlet Pleated media filter Built in air filter reduces dust and mold Twist on duct collar Direct the drying power where y...

Page 2: ...st 1 foot from walls and other obstructions to air flow If the humid area is very large dehumidification can be improved by adding an outlet duct to circulate air to stagnant areas see Sec 2 5 Table of Contents Introduction 1 1 Specifications 2 2 Operation 2 2 1 Transporting the Phoenix 300 2 2 2 Location 2 2 3 Electrical Requirements 2 2 4 Condensate Removal 3 2 5 Ducting 3 2 6 Power Switch 3 2 7...

Page 3: ...e hose stops 2 8 Pump Fail Light If the condensate pump fails water draining into the pump reservoir will fill above its normal level A safety float switch will then turn on the pump fail light located next to the pump purge switch and stop the compressor This prevents water from overflowing and wetting the floor The safety switch will not allow the compressor to restart until water has been remov...

Page 4: ...the Phoenix 300 is stored between uses and both pertain to the water trapped in the unit damage caused by freezing and biological growth The effect of the trapped water can be greatly reduced if precautions are taken to remove as much as possible before storage 1 Use the pump purge switch see Sec 2 7 and Fig 3 to reduce the water level in the reservoir 2 Stretch the hose flat to drain it completel...

Page 5: ...c 4 6A 5 Defective compressor Sec 4 6 6 Defective relay Sec 4 9 7 Defective time delay Sec 4 10 No dehumidification Blower runs but compressor does not Pump fail light not lit 1 Bad connection in compressor circuit Fig 3 2 Defective compressor capacitor Sec 4 6A 3 Defective compressor overload Sec 4 6A 4 Defective compressor Sec 4 6 5 Defective relay Sec 4 9 6 Defective time delay Sec 4 10 No dehu...

Page 6: ...e relay terminal that the black wire from the compressor connects to and b the capacitor terminal with the 3 white wires and 1 red wire connected If voltage is present go to step 3 If no voltage the low pressure control the time delay or the relay are open or there is a loose connection in the compressor circuit Test each component for continuity see the appropriate section if a defect is suspecte...

Page 7: ...the system for at least an hour 8 Operate the system for a short period of time monitoring the suction pressure to determine that the suction filter is not becoming plugged Replace the suction filter drier if pressure drop occurs If a severe running burn out has occurred several filter driers may have to be replaced to remove all of the acid and moisture NOTE NEVER use the compressor to evacuate t...

Page 8: ...low pressure control time delay HP model defrost thermostat and timer 4 10 Time Delay HP model only The HP model has a time delay relay in the compressor control circuit This relay delays the compressor start about 2 minutes after the power switch is turned on This reduces the unit s starting amp draw by starting the blower and compressor at different times This reduces the chance of tripping a ci...

Page 9: ...2 4021908 1 Drain Hose 38 ID x 56 OD x 33 long 13 4022611 1 Outlet Collar for Ducting Outlet 14 4022593 1 Filter Drier not shown 15 4021597 1 Hour Meter 16 4021089 1 Indicator Light Red 125V 17 4022616 1 Instruction Label not shown 18 4022219 1 Low Pressure Control 19 1970010 1 Relay 20 4022740 1 Run Capacitor 30 MFD 370V 21 4021997 6 Spring 22 4021796 1 Switch Pump Purge 23 4021822 1 Switch Power...

Page 10: ...10 www thermastor com sales thermastor com Toll Free 1 800 533 7533 This page intentionally left blank ...

Page 11: ...ther reasonable and reliable means The end user is responsible for normal care This warranty does not cover any defect malfunction etc resulting from misuse abuse lack of normal care corrosion freezing tampering modification unauthorized or improper repair or installation accident acts of nature or any other cause beyond Therma Stor LLC s reasonable control Limitations and Exclusions If any Phoeni...

Reviews: