Drain Installation

The Santa Fe Compact70 generates condensate.
Place a secondary drain pan under the dehumidifier if it is suspended above a finished area or above an area where wa-

ter leakage could cause damage.
A drain trap is required for the dehumidifier to run properly. Install a 3/4" threaded male NPT adapter to the drain  or 

drain pan if one is being used. Install a drain pipe assembly utilizing 3/4" PVC pipe to transport the condensate to a 

drain. Pitch of drain should be 1" per 10'.
An optional condensate pump kit is available for use with the Santa Fe Compact70 and may be installed if lift is required 

to dispose of condensate. Condensate is automatically pumped to a remote location when the water level in the pump’s  

reservoir rises to close the float switch.
Note: An optional condensate pump kit can be purchased from a local dealer or online.

Drain Installation

Front View

Secondary Drain Pan

(Optional)

Drain Port

Drain Trap

Pretzel Loop

Floor Bend

PVC Trap

PVC materials available from your local hardware store.

The Santa Fe Compact70 requires a drain trap. Creating a drain 

trap allows a small amount of water to build up in the trap area 

of the clear hose. This prevents air from back flowing through 

the hose and into the dehumidifier; essentially causing the unit 

to backflow water out of the corners of the machine. Position the 

trap in the hose approximately 8"-10” from the dehumidifier and 

make sure the highest point of the trap is still at least 2” below 

the black drain port adapter on the dehumidifier. If the highest 

point of the trap is above the drain port, water will back flow into 

the dehumidifier. Check the hose regularly to ensure water is 

draining properly.

For additional information on how to create a  

proper trap, see our instructional video at:  

www.Santa-Fe-Products.com\drain-trap\
Use care to keep the hose as flat to the floor as  

possible after your trap is in place. Be sure the hose is 

not kinked or otherwise restricted so water can pass 

through the hose freely. Improper installation of the 

drain hose may result in water leakage.
If the Santa Fe Compact70 is located too far from the floor 

drain and the provided hose does not reach, you may use 

a 1/2 PVC rigid pipe that will fit inside the 3/4 hose as a 

means to extend the drain line. Rigid PVC tubing is readily 

available from your local hardware store. Be sure the  

extension is at a down-word slope to the drain.
An optional condensate pump kit may be installed if  

lift is required to remove condensate. To order,  

contact your local dealer or visit our website at  

www.santa-fe-products.com. You may also reach  

us by phone at (800) 533-7533.

Standard Loop

Summary of Contents for 4033600

Page 1: ...mpact70 is designed for superior basement and crawl space dehumidification Tight spaces are no problem for the Santa Fe Compact70 dehumidifier Its compact size works perfect in low crawl spaces and small basements without sacrificing power and performance Designed to fit in a variety of small spaces the Compact70 provides multiple installation options for greater flexibility MADISON WI ...

Page 2: ... Precautions 5 Location Considerations 5 Installing Leveling Feet 5 Ducting to Finished Areas Optional 6 Attaching Duct Collars 6 Recommended Installations 7 Drain Installation 8 Operation 9 Humidity Control Adjustment 9 Defrost Cycle 9 Fan Operation 9 Air Filtration 10 Changing The Filter 10 MERV Rating Chart 11 Electrical Requirements 12 Service 13 Replacement Parts 13 Refrigerant Charging 13 Co...

Page 3: ... unit unattended ensure children do not have access to the equipment Do not allow children to play with or near the unit or in its air flow The unit is designed to be installed indoors only No user serviceable components Contact installer or call 1 800 533 7533 for all repair or warranty needs Intended Application s The Santa Fe Compact70 is intended for use in crawl spaces or basements however th...

Page 4: ...ower Cord 9 115 VAC Ground Drain Connection 3 4 Threaded Female NPT Drain Hose 8 Direct Gravity Drain Hose 5 8 ID x 7 8 OD Refrigerant Type R410A Refer to manufacturers label for more information Refrigerant Amount 15 oz Dimensions Unit Shipping Width 12 18 Height 12 18 Length 21 27 Weight 55 lbs 64 lbs Width 12 12 15 5 8 WITH C OLLARS W OUT C OLLARS 21 12 FRONT 12 12 9 11 21 12 12 FRONT 12 12 9 1...

Page 5: ...raise the base of the unit Location Considerations Locate the dehumidifier near a suitable drain 8 drain hose included Allow for proper drainage and routing of needed drain pipes Locate the dehumidifier in an area where the cord s length 9 easily reaches a 115 VAC electrical outlet with a minimum of a 15 Amp circuit capacity The unit is designed to operate while level If the unit is placed on an u...

Page 6: ...cal Flow Through Remove the exhaust panel Rotate the panel so the exhaust collar is located on the top of the unit Align screw holes and snap the panel onto the base Secure the exhaust panel to the base by replacing the six screws Front View Horizontal Flow Through End Discharge Rear View Vertical Flow Through Top Discharge 8 Return Air Inlet 8 Supply Air Outlet A B A A B A 8 Return Air Inlet 8 Su...

Page 7: ...or with an optional pump kit Using the supply and return duct kit supply the dry air from the dehumidifier into a large open area of the fin ished basement Use the return duct kit to draw air back through the dehumidifier Be sure the return and supply are at least 10 feet away from each other for proper air flow throughout the basement Add a passive grill between the finished and unfinished areas ...

Page 8: ...This prevents air from back flowing through the hose and into the dehumidifier essentially causing the unit to backflow water out of the corners of the machine Position the trap in the hose approximately 8 10 from the dehumidifier and make sure the highest point of the trap is still at least 2 below the black drain port adapter on the dehumidifier If the highest point of the trap is above the drai...

Page 9: ...he humidity dial clockwise to the recommended NORMAL position and set fan control to FAN AUTO To turn the unit off turn the humidity dial counter clockwise to the OFF position and set fan control to FAN AUTO Defrost Cycle This product includes a defrost thermostat This feature prevents internal damage caused by excessive frost forming within the unit When the unit is experiencing excessive frost t...

Page 10: ...he 1 4 pre filter by gently pulling on the bottom of the filter frame Remove the MERV 13 filter by gently pulling on the bottom of the filter frame Step 2 Installing the Filters Angle the top of the MERV 13 filter and gently slide the filter into the filter slot Do not force If resistance is felt check alignment for obstructions or debris inside the filter housing Be sure the arrows on the filter ...

Page 11: ...l Bag Filter Nonsupported Legionella microfine fiberglass or 11 60 65 95 Humidifier Dust Better Commercial Buildings synthetic media 12 36 in deep 6 12 pockets Lead Dust 10 50 55 95 Milled Flour Box Filter Rigid Style Cartridge Filters 6 to 12 deep may use lofted or paper media Auto Emissions Hospital Laboratories 9 40 45 90 Welding Fumes 8 30 35 90 3 0 10 0 pm Particle Size Commercial Buildings P...

Page 12: ...ounded 115VAC outlet The device draws 5 1 Amps at 80 F and 60 RH Locate the dehumidifier in an area where the cord s length 9 easily reaches a 115 VAC electrical outlet with a minimum of 15 Amp circuit capacity If used in an area that may become wet a GFCI protected circuit is recommended The unit should not be used in areas prone to flooding Consult local electrical codes for any further informat...

Page 13: ...ANTA FE COMPACT70 WITH ITS HIGH PRESSURE REFRIGERANT SYSTEM AND HIGH VOLTAGE CIRCUITRY PRESENTS A HEALTH HAZARD WHICH COULD RESULT IN DEATH SERIOUS BODILY INJURY AND OR PROPERTY DAMAGE ONLY QUALIFIED SERVICE PEOPLE SHOULD SERVICE THIS UNIT Troubleshooting CAUTION TROUBLESHOOTING SHOULD BE PERFORMED BY A QUALIFIED HVAC TECHNICIAN Symptom Possible Reason Neither fan nor compressor running Dehumidifi...

Page 14: ... temp Rh you should see some water production out of the hose within 30 minutes or so Note If the room temperature is 55 degrees or below and or in area of low relative humidity the dehumidifier will produce little to no water 7 Collecting the water removed in a 24 hour period will give a measurement of performance WARNING ELECTRICAL SHOCK HAZARD ELECTRICAL POWER MUST BE PRESENT TO PER FORM SOME T...

Page 15: ...r any costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibilities As a further condition to obtaining warranty coverage hereunder the Customer must send a valid warranty claim to Therma Stor such that Therma Stor receives such claim prior to the end of ...

Page 16: ...Santa Fe Products com 800 533 7533 DEHUMIDIFIERS ...

Reviews: