background image

3.2 Blower Switch

Turning “ON" the fan switch will cause the unit’s internal blower 
to run continuously, whether the unit is dehumidifying or not. This 
function is desirable if the unit is used for air circulation.

4. Maintenance

4.1 Air Filter

The Santa Fe Classic is equipped with 2 air filters. A foam pre-
filter followed by a standard MERV-11 65% efficient pleated fabric 
filter. These should be checked every six months. Operating 
the unit with dirty filters will reduce dehumidifier capacity and 
efficiency and may cause the compressor to cycle off and on 
unnecessarily on the defrost control.

If dirty, the foam pre-filter can be vacuumed or carefully hand 
washed with warm water and mild detergent, then rinsed. The 
pleated fabric filter can generally be vacuumed clean several 
times before needing replacement. Replacement filters can be 
ordered from the factory or purchased locally if available. 

DO NOT

 

operate the unit without the filters or with a less effective filter. 
The heat exchange coils inside the unit could become clogged and 
require disassembly to clean.

5. Service

 

CAUTION!

Servicing the Santa Fe Classic with its high pressure 
refrigerant system and high voltage circuitry presents a 
health hazard which could result in death, serious bodily 
injury, and/or property damage. Only qualified service people 
should service this unit.

5.1 Warranty

A warranty certificate has been enclosed with this unit. Read 
it before any repair is initiated. If a warranty repair is required, 
call the factory first at 1-800-533-7533 for warranty claim 
authorization and technical assistance.

5.2 Technical Description

The Santa Fe Classic uses a refrigeration system similar to an air 
conditioner’s to remove heat and moisture from incoming air, and 
add heat to the air that is discharged (see figure 1).

Hot, high pressure refrigerant gas is routed from the compressor 
to the condenser coil (see figure 1). The refrigerant is cooled 
and condensed by giving up its heat to the air that is about to 
be discharged from the unit. The refrigerant liquid then passes 
through a filter/drier and capillary tubing which cause the refrigerant 
pressure and temperature to drop. It next enters the evaporator coil 
where it absorbs heat from the incoming air and evaporates 

The evaporator operates in a flooded condition, which means that 
all the evaporator tubes contain liquid refrigerant during normal 
operation. A flooded evaporator should maintain constant pressure 
and temperature across the entire coil, from inlet to outlet. 

The mixture of gas and liquid refrigerant enter the accumulator 
after leaving the evaporator coil. The accumulator prevents any 
liquid refrigerant from reaching the compressor. The compressor 
evacuates the cool refrigerant gas from the accumulator and 
compresses it to a high pressure and temperature gas to repeat 
the process.

5.3 Troubleshooting
No dehumidification. Neither blower nor compressor run with 
fan switch “FAN AUTO”. 

1.  Unit unplugged or no power to outlet.
2.  Humidity control set too high or defective  
  (Sec. 3.1 & 5.7).
3.  Loose connection in internal wiring.

No dehumidification. Compressor does not run but blower 
runs with fan switch “FAN AUTO” and humidity control turned 
to ON (all the way clockwise).

1.  Defective compressor or compressor run capacitor    
  (Sec. 5.6).
2.  Loose connection in compressor circuit (see Fig. 2).
3.  Defective compressor overload (Sec. 5.6A).
4.  Defective compressor (Sec. 5.6).
5.  Defrost thermostat open (Sec. 5.8).

Blower runs with fan switch “FAN AUTO”, but compressor cycles 
ON & OFF.

1.   Low ambient temperature and/or humidity causing    

 unit to cycle through defrost mode.

2.  Defective compressor overload (Sec. 5.6A).
3.  Defective compressor (Sec. 5.6).
4.  Defrost thermostat defective (Sec. 5.8).

Blower does not run with fan switch in either position. 
Compressor runs briefly but cycles ON & OFF.

1.  Loose connection in blower circuit (see Fig. 2).
2.  Obstruction prevents impeller rotation.
3.  Defective blower.
4.  Blower switch defective. 

SANTA FE CLASSIC INSTALLER'S AND OWNER'S MANUAL

4

Santa Fe Classic Installer’s & Owner’s Manual

Summary of Contents for Santa-Fe Classic

Page 1: ...operating and safety instructions warranty information and all ancillary products n Read and save these instructions For small usage 420l Lien Rd Madison WI 53704 TOLL FREE 1 800 533 7533 www thermast...

Page 2: ...to remove corrugated shipping cardboard from top of unit Specifications Part Number 4029700 Blower 275 CFM 0 0 WG Power 720 watts 80 F and 60 RH Supply Voltage 115 volt 1 phase 60 Hz Current Draw 6 4...

Page 3: ...he room in which it s located An adequate air flow path must exist between the two rooms for this method to work well An additional humidity control may need to be mounted in the humid area and wired...

Page 4: ...t is cooled and condensed by giving up its heat to the air that is about to be discharged from the unit The refrigerant liquid then passes through a filter drier and capillary tubing which cause the r...

Page 5: ...yellow wires from compressor terminals R S Using an ohmmeter check continuity between the points listed below 4 Compressor terminals C and S No continuity indicates an open start winding The compress...

Page 6: ...ith 35 to 50 PSIG refrigerant vapor charge Leave the vapor charge in the system from at least 5 minutes before removing it Repeat the vapor charge wait remove sequence twice more and then charge the s...

Page 7: ...6 Wiring Diagram SANTA FE CLASSIC WIRING DIAGRAM 7 Santa Fe Classic Installer s Owner s Manual Figure 2 Electrical Schematic of the Santa Fe Classic Dehumidifier...

Page 8: ...4025741 1 Defrost Thermostat 4021648 1 Defrost Control Mounting Clip 12 4028225 1 Evaporator Coil 13 4029510 1 Filter Drier 14 4021626 1 Hose Drain 56 ID x 8 15 4021469 1 Humidity Controller 16 402149...

Page 9: ...Insert a romex connector or conduit connector into the hole in the cabinet that is left after the dehumidistat is removed Pass the cable to be used to connect to the remote dehumidistat through the c...

Page 10: ...are located near the bottom and on the same side of the unit as the drain hose STEP 5 Example of hose cut at a 45 angle The angle prevents the hose from sealing tight against the bottom of the pump re...

Page 11: ...ach the inlet to the guides 4 Replace the filters in the unit Exhaust Collar Mounting Instructions 5 The six inch opening may be used as a fresh air inlet from outside 6 Remove the exhaust collar from...

Page 12: ...and 2 screws are not used on the Santa Fe Classic Loosen these 2 screws enough to slide the silencer under the screw heads Insert 1 screw from the enclosed parts and tighten Santa Fe Classic Muffler...

Page 13: ...er s Owner s Manual Instructions To prevent damaging the foam filter place it grid side up on top of the pleated filter and slide them both into the filter slot Foam filter with plastic grid up Pleate...

Page 14: ...ent that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsibilities As a further condition to obtaining warr...

Page 15: ...uced or transmitted in any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2008 Therma Stor LLC All rights reserved 4201 Lien Rd...

Reviews: