background image

3.4C Ducting for Fresh Air 

Fresh air can be brought into the structure by connecting an 
insulated duct from outside to the 6" Ultra-Aire XT150H inlet and 
by turning on the fan switch or activating the humidity control (on 
units with the humidity control panel). Activate the ventilation timer 
on units with the ventilating and humidity control panel to bring in 
fresh air. Refer to Section 4.5 for programming instructions for the 
ventilation timer. Advantages of this form of ventilation include: 

1. Outside air is filtered before entering the building. 
2.  Outside air will be dehumidified before entering if the Ultra-

Aire XT150H is running in dehumidification mode. 

3.  Drawing air from outside and blowing inside aids in slightly 

pressurizing the structure. This helps prevent dirty and humid 
air from entering elsewhere. It also reduces the potential for 
carcinogenic radon gas to enter and provides make-up air for 
open combustion and exhaust devices like the clothes drier, 
fireplace, and water heater. 

4.  Adequate exhaust fans are recommended in the bath rooms 

and kitchen. 

In cold climates or areas where the outdoor dew point is low 
at times, ventilation can be used to dehumidify the structure. 
This is accomplished by bringing the dry, low dew point air into 
the structure during these times. This approach is often more 
economical than running the dehumidifier to remove excess 
moisture from the structure. In cold climates, it is critical to 
adequately ventilate to reduce the inside moisture content to 
avoid moisture accumulating in the wall cavities. For example; in a 
house that experiences condensation on the interior surface of the 
windows during the winter, increasing the amount of ventilation will 
often cure the problem. 

An insulated 6" diameter duct is generally sufficient to provide up 
to 125 CFM of outside air. Large quantities of outside air will either 
positively or negatively impact the performance of the Ultra-Aire 
XT150H, depending upon inside and outside air conditions. Consult 
the factory by calling 1-800-533-7533 for recommendations 
regarding the use of higher flows with your specific application. 

The outside air duct should be connected to the 6" round collar 
on the filter enclosure of the unit. The 6" round collar includes a 
manual damper. Adjust the manual damper to provide the desired 
amount of fresh air for ventilation. The amount of fresh air should 
be based on the size and occupancy of the residence. If you are 
unsure of your ventilation air requirements, consult the factory by 
calling 1-800-533-7533 for assistance. 

3.4D Installation in a Basement or Crawlspace  

with an Existing Forced Air HVAC System 

It is recommended that a new, separate return duct be installed for 
the Ultra-Aire XT150H from a central area of the house. If this is not 
possible, and if the existing system has multiple returns, select one 
to disconnect from the existing forced air system and use it for the 
dedicated Ultra-Aire XT150H return. Always select a return from a 
central location in the structure in an area that is always open to 
the rest of the structure. Do not use a return from a room that may 
have its door closed much of the time.

If the structure in which the Ultra-Aire XT150H is to be installed has 
an existing forced air HVAC system, utilize the HVAC system to make 
the Ultra-Aire XT150H installation easier. 

Basement Installation:

 Install a separate 10" return for the Ultra-

Aire XT150H in a central area of the structure. Duct the supply of the 
Ultra-Aire XT150H to an optional 10" x 10" x 10" tee/damper that 
is 20% open to the basement. This allows the ability to discharge a 
variable amount of dehumidified air into a basement that may not 
be well served by the existing duct system. Duct the other side of 
the tee to the air supply of the existing HVAC system. A backdraft 
damper is required in the duct between the 10" tee and the central 
supply duct to prevent air from being discharged into the basement 
during central fan operation. Connect a duct from outside to the 
6" collar of the Ultra-Aire XT150H if you wish to provide fresh air 
ventilation. 

Crawl Space Installation:

 Install a separate return for the Ultra-

Aire XT150H in a central area of the structure. Duct the supply of 
the Ultra-Aire XT150H to a 10" x 10" x 10" tee/damper that is 20% 
open to the crawl space if desired. Duct the other side of the tee 
to the air supply of the existing HVAC system ventilation. Connect 
an insulated duct from outside to the 6" collar of the Ultra-Aire 
XT150H if you wish to provide optional fresh air. 

FOR HVAC INSTALLER ONLY

6

Ultra-Aire XT150H Installer’s & Owner’s Manual

Summary of Contents for Ultra-Aire XT150H

Page 1: ...tdoor air may be ducted to the unit via a six inch round duct This provides fresh air to dilute pollutants and maintain high oxygen content in the air The amount of fresh air ventilation can be regula...

Page 2: ...igital Control WITHOUT Fresh Air 9 4 2 Humidity Control Adjustment 8 4 3 Fan Filter Switch 8 4 4 Ventilation Timer 8 4 4A Setting the Time 9 4 4B Ventilation Schedule 9 4 4C Automatic or Manual Mode 9...

Page 3: ...th space to access the back or side panels for maintenance and service DO NOT INSTALL UNIT WITH THE SERVICE PANELS INACCESSIBLE Avoid directing the discharge air at people or over the water in pool ar...

Page 4: ...l vibration and or noise A drain pan MUST be placed under the unit if installed above a living area or above an area where water leakage could cause damage Place the Ultra Aire XT150H on supports that...

Page 5: ...ating system can be used to supply air to the home If the existing supply goes to isolated areas of the home discharge the supply of the Ultra Aire XT150H into the supply of the existing heating syste...

Page 6: ...lter enclosure of the unit The 6 round collar includes a manual damper Adjust the manual damper to provide the desired amount of fresh air for ventilation The amount of fresh air should be based on th...

Page 7: ...edrooms den etc By ducting this way the air inside the structure will circulate through the Ultra Aire XT150H to be filtered and dehumidified Avoid discharging all the air from the dehumidifier in one...

Page 8: ...ir Refer to Section 5 4 2 Humidity Control Adjustment Set the humidity control to the desired humidity level for the home Turning the knob clockwise results in a drier setting See the back of the cont...

Page 9: ...the week for this program You can choose Mon Sun Mon Fri Sat Sun or any single day of the week The days chosen are shown along the top of the display on the ventilation timer Next press the h button...

Page 10: ...e lead from the unit or damage to the transformers will result Do not direct connect the white lead on the unit to the violet lead on the ventilation control or damage to the transformer will result H...

Page 11: ...ty Range Accuracy 10 95 RH 5 Auxillary Relay Capacity 5 Amps 24VAC Temp Range Accuracy 30 90 F 2 Size 4 95 L x 1 06 W x 4 19 H Major Operations n Digital control of Relative Humidity Digital Set Point...

Page 12: ...heck and clean the screen on the outdoor fresh air return seasonally The screen may become plugged during the seasons when there are many particles in the outdoor air 7 Service 7 1 Warranty A warranty...

Page 13: ...uch as expected 1 Air temperature and or humidity have dropped 2 Humidity meter and or thermometer used are out of calibration 3 Unit has entered defrost cycle Sec 5 8 4 Air filter dirty Sec 4 1 4 2 5...

Page 14: ...capacitor Plug in and turn on the unit If the compressor fails to start replace the run capacitor 11 If the unit still does not start adding a hard start kit relay capacitor will provide greater start...

Page 15: ...and bring in fresh air from outside The ventilation timer should be set for the required ventilation of the residence The home should be ventilated with fresh air as suggested by applicable codes and...

Page 16: ...Aire XT150H to the blue 5 lead on the control panel If the pump fails this switch opens the compressor control circuit and stops water production before the reservoir overflows The Ultra Aire XT150H...

Page 17: ...FOR HVAC INSTALLER ONLY 17 Pictorial Electrical Diagrams of Ultra Aire XT150H Ultra Aire XT150H Installer s Owner s Manual...

Page 18: ...t No Qty Description 12 4026687 1 45mFd CAPACITOR COMPRESSOR 13 4022487 1 TRANSFORMER 14 4022484 1 RELAY COMPRESSOR 15 4017021 1 15mFd CAPACITOR IMPELLER 16 4026932 1 COLLAR 10 INCH 17 4026947 1 COLLA...

Page 19: ...Electrically Actuated not shown 32 4024153 1 Cover for Items 28 29 not shown 33 4021495 1 Knob Black 25 shaft 34 4024150 1 Instructions Humidity Fan not shown 35 4024122 1 Instructions Ventilation Ti...

Page 20: ...ng door shut Once the door is shut release the door latch Collar Install Remove the 2 round ducts 3 seals and small bag of mounting hardware from inside the rectangle opening Adhere seals onto the bac...

Page 21: ...costs related to changes to a Product or Component that may be required by any codes laws or regulations that may become effective after initial purchase of the Product by Customer Customer Responsib...

Page 22: ...any form or by any means electronic or mechanical for any purpose without the express written permission of Therma Stor LLC 2007 Therma Stor LLC All rights reserved PO Box 8680 Madison WI 53708 Phone...

Reviews: