background image

Page 4

Appliance Installation:

Appliance Installation:

Appliance Installation:

Appliance Installation:

Appliance Installation:

The PHE unit can be mounted on

a wall or suspended from a

cabinet.  Both vertical and

horizontal discharge ar

e possible

with either mounting method.

Dischar

Dischar

Dischar

Dischar

Discharge Dirge Dirge Dirge Dirge Dir

ection:  

ection:  

ection:  

ection:  

ection:  

The PHE

hood is shipped ready for vertical

discharge.  To

 change to horizon-

tal discharge simply move the two

plates marked 

A A A A A

 in Figure 1 to

the top of the hood.  Each plate is

held in place by two sheetmetal

screws.

Assembly of the T

Assembly of the T

Assembly of the T

Assembly of the T

Assembly of the Transition:ransition:ransition:ransition:ransition:

The transition supplied with the

PHE hood mounts to the top or

rear of the hood depending on the

discharge direction.

1.  Align mounting holes at base

of transition with mounting holes

on 1/2” flange located at the top

or rear of the hood depending on

direction of discharge.

2.  Fasten transition to hood

using 6 (4 mm x 9.5 mm) screws

(included with hood).

3.  Duct tape connection between

transition and hood.

4.  Remove tape holding damper

closed.

Figure 1

Summary of Contents for PHE 30

Page 1: ... CA 92649 800 735 4328 RO 8593 35 05 196A Thermador Corporation 1998 Litho in U S A 7 98 READ AND SAVE THESE INSTRUCTIONS CARE AND USE FOR PROFESSIONAL WALL HOODS Turn Book Over for Installation Instructions PHE 30 36 42 48 60 Model Serial ...

Page 2: ...low setting 4 Do not leave range unattended when cooking IMPORTANT SAFETY INSTRUCTIONS 5 Always use cookware and utensils appropriate for the type of food being prepared WARNING TO REDUCE THE RISK OF INJURY TO PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE OBSERVE THE FOLLOWING a SMOTHER FLAMES with a close fitting lid cookie sheet or other metal tray then turn off the gas burner or the electric ...

Page 3: ...t nécessaire Chauffer l huile lentement sur un positionnement bas à moyen 4 Ne pas laisser la cuisinière sans surveillance pendant la cuisson 5 Utiliser toujours les batteries de cuisine et les ustensiles appropriés pour le type et la quantité de la nourriture ayant préparée AVERTISSEMENT POUR RÉDUIRE LE RISQUE DE BLESSURE AUX PERSONNES DANS L ÉVÉNEMENT D UN FEU DE GRAISSE DU SOMMET DE LA CUISINIÈ...

Page 4: ...on LED The flashing LED marked D reminds you when the grease filter needs to be cleaned after 40 hours use Follow the instructions for cleaning filters in this booklet Once the grease filters have been cleaned reset reminder by pressing button A for about 3 seconds until you hear the signal beep the LED D will now stop flashing Circuit Self test The control allows the user to perform a self test t...

Page 5: ...ights off Push each handle towards the back and pull downwards Fig 2 To Replace The Metal Grease Filters Reverse procedure Fig 2 CLEANING INSTRUCTIONS Be sure lights are cool before cleaning the hood To Clean Filters It is recommended that the filters be washed at least once a month they can be washed by hand or in the dishwasher Drain water through edge holes and let each filter dry thoroughly be...

Page 6: ...r a G 4 base Follow package directions and do not touch new light with bare hands Reinstall the light cover THERMADOR is a leading manufac turer of Convection Micro Thermal Ovens Convection Thermal Electric Ovens and Ranges Thermador PRO FESSIONAL Dual Fuel and All Gas Ranges Thermador PROFESSIONAL Gas Cooktops Free Standing and Drop In Slide In Ranges Warming Drawers XLO Gas Cooktops Traditional ...

Page 7: ...c regions 5 Repairs due to other than normal home use Thermador Will Pay Will Pay Will Pay Will Pay Will Pay For All repair labor and replacement parts found to be defective due to materials and workmanship Service must be provided by a Factory Authorized Service Agency during normal working hours For a Service Agency nearest you please call 800 735 4328 This warranty applies to appliances used in...

Page 8: ...duit connector 8 Connect the black white red and blue wires from the remote ventilator to the black white red and blue wires of the pigtail respectively Connect the remote blower green yellow ground wire to the ground wire from the service panel 9 Close junction box cover Check that all light bulbs are secure in their sockets Install filters Turn power on at service panel and check lights and blow...

Page 9: ...er Remote Blower Remote Blower Remote Blower Remote Blower W W W W W ar ar ar ar arning Tur ning Tur ning Tur ning Tur ning Turn of n of n of n of n off electric f electric f electric f electric f electric ity at the service panel ity at the service panel ity at the service panel ity at the service panel ity at the service panel befor befor befor befor before wiring the unit e wiring the unit e wi...

Page 10: ... the PHE with an iring the PHE with an iring the PHE with an Integral motor Integral motor Integral motor Integral motor Integral motor W W W W W ar ar ar ar arning Tur ning Tur ning Tur ning Tur ning Turn of n of n of n of n off elec f elec f elec f elec f elec tricity at the service tricity at the service tricity at the service tricity at the service tricity at the service panel befor panel befo...

Page 11: ...izontal discharge use Figure 5 for the geometry of the cutout required for clearance of the transition 4 Hang hood from screws and tighten securely 5 Install two wall anchors as described in step 15 on the previous page ...

Page 12: ...mm x 18 mm screws provided with hood leaving 1 4 exposed 2 If the hood is installed for vertical discharge use Figure 11 to create clearance holes for passage of the transition and conduit Dimension A in Figure 11 depends on the hood model being installed and can be located in the table above Figure 10 Figure 11 ...

Page 13: ...duct covers are available and may be or dered separately 1 If multiple duct covers are used connect the pieces together using sheetmetal screws provided with chimneys Figure 9 2 Attach the duct cover s to the hood using sheetmetal screws as shown in Figure 9 Cabinet Installation Cabinet Installation Cabinet Installation Cabinet Installation Cabinet Installation The PHE hood can be in stalled under...

Page 14: ...lied with the PHE connects to standard 10 round duct Figure 6 shows the transition connected for horizon tal discharge Figure 7 below shows the PHE configured for vertical discharge Installations using this type of method require a cutout in the ceiling to accomodate 10 duct and the 1 2 conduit carrying power to the unit Figure 7 Duct covers sold separately are available to cover the space between...

Page 15: ...rough the wooden bracket drywall and into the stud 7 Use 2 4 6mm x 80 mm screws to attach the bracket to the wall as shown in Figure 3 For support of longer hoods use three or four studs as available Countersink the heads to prevent interfer ence with the hood 8 On the wood bracket mark the locations used to hang the hood according to Figure 4 Figure 4 9 Drill a 1 8 tap hole through the wooden bra...

Page 16: ...2 covers as appropriate to accommodate ceiling height and desired hood height The duct cover structure is supported by the hood 1 Hood Installation Height After the hood installation height has been determined draw a horizontal line at a distance above the cooktop equal to the desired hood installation height plus 15 5 This line is the mounting location of the wooden bracket shipped with the hood ...

Page 17: ...es marked A A A A A in Figure 1 to the top of the hood Each plate is held in place by two sheetmetal screws Assembly of the T Assembly of the T Assembly of the T Assembly of the T Assembly of the Transition ransition ransition ransition ransition The transition supplied with the PHE hood mounts to the top or rear of the hood depending on the discharge direction 1 Align mounting holes at base of tr...

Page 18: ...allation 1 For the most efficient air flow exhaust use a straight run or as few elbows as possible CAUTION CAUTION CAUTION CAUTION CAUTION Vent unit to outside of building only 2 Use flex ducting only to connect rigid duct directly to transitions 3 COLD WEATHER installa tions should have an addi tional backdraft damper installed to minimize back ward cold air flow and a nonmetallic thermal break t...

Page 19: ... MA APEUR OU LES MATIÈRES TIÈRES TIÈRES TIÈRES TIÈRES EXPLOSIVES OU DANGEREUSES EXPLOSIVES OU DANGEREUSES EXPLOSIVES OU DANGEREUSES EXPLOSIVES OU DANGEREUSES EXPLOSIVES OU DANGEREUSES A Utiliser cet appareil seulement dans la manière destinée par le fabricant Si vous avez des questions contacter le fabricant B Avant l entretien ou le nettoyage de l appareil couper le courant au tableau de service ...

Page 20: ...G PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING INST INST INST INST INSTALLA ALLA ALLA ALLA ALLATION MUST COMPL TION MUST COMPL TION MUST COMPL TION MUST COMPL TION MUST COMPLY Y Y Y Y WITH WITH WITH WITH WITH ALL LOC ALL LOC ALL LOC ALL LOC ALL LOCAL CODES AL CODES AL CODES AL CODES AL CODES IM...

Reviews: