background image

Page 13

6.  Connect wire clamp to

“pigtail” as shown in Figure

15.  Insert “pigtail” wires

into j-box and fix wire

clamp to j-box using nut

supplied with wire clamp 

V

V

V

V

V

.

7.  Run five wires (#16

AWG) in 1/2” conduit from

the remote blower to the

second conduit connector.

8.  Connect the black,

white, red, and blue wires

from the remote ventilator

to the black, white, red, and

blue wires of the “pigtail

respectively.  Connect the

remote blower green/yellow

(ground) wire to the ground

wire from the service panel.

9.  Close junction box cover.

Check that all light bulbs

are secure in their sockets.

Install filters.  Turn power

on at service panel, and

check lights and blower

operation per Care & Use

section of this manual.

Summary of Contents for PHE

Page 1: ...G PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING PLEASE READ ENTIRE INSTRUCTIONS BEFORE PROCEEDING INST INST INST INST INSTALLA ALLA ALLA ALLA ALLATION MUST COMPL TION MUST COMPL TION MUST COMPL TION MUST COMPL TION MUST COMPLY Y Y Y Y WITH WITH WITH WITH WITH ALL LOC ALL LOC ALL LOC ALL LOC ALL LOCAL CODES AL CODES AL CODES AL CODES AL CODES IM...

Page 2: ...A APEUR OU LES MATIÈRES TIÈRES TIÈRES TIÈRES TIÈRES EXPLOSIVES OU DANGEREUSES EXPLOSIVES OU DANGEREUSES EXPLOSIVES OU DANGEREUSES EXPLOSIVES OU DANGEREUSES EXPLOSIVES OU DANGEREUSES A Utiliser cet appareil seulement dans la manière destinée par le fabricant Si vous avez des questions contacter le fabricant B Avant l entretien ou le nettoyage de l appareil couper le courant au tableau de service et...

Page 3: ...allation 1 For the most efficient air flow exhaust use a straight run or as few elbows as possible CAUTION CAUTION CAUTION CAUTION CAUTION Vent unit to outside of building only 2 Use flex ducting only to connect rigid duct directly to transitions 3 COLD WEATHER installa tions should have an addi tional backdraft damper installed to minimize back ward cold air flow and a nonmetallic thermal break t...

Page 4: ...es marked A A A A A in Figure 1 to the top of the hood Each plate is held in place by two sheetmetal screws Assembly of the T Assembly of the T Assembly of the T Assembly of the T Assembly of the Transition ransition ransition ransition ransition The transition supplied with the PHE hood mounts to the top or rear of the hood depending on the discharge direction 1 Align mounting holes at base of tr...

Page 5: ...2 covers as appropriate to accommodate ceiling height and desired hood height The duct cover structure is supported by the hood 1 Hood Installation Height After the hood installation height has been determined draw a horizontal line at a distance above the cooktop equal to the desired hood installation height plus 15 5 This line is the mounting location of the wooden bracket shipped with the hood ...

Page 6: ...rough the wooden bracket drywall and into the stud 7 Use 2 4 6mm x 80 mm screws to attach the bracket to the wall as shown in Figure 3 For support of longer hoods use three or four studs as available Countersink the heads to prevent interfer ence with the hood 8 On the wood bracket mark the locations used to hang the hood according to Figure 4 Figure 4 9 Drill a 1 8 tap hole through the wooden bra...

Page 7: ...lied with the PHE connects to standard 10 round duct Figure 6 shows the transition connected for horizon tal discharge Figure 7 below shows the PHE configured for vertical discharge Installations using this type of method require a cutout in the ceiling to accomodate 10 duct and the 1 2 conduit carrying power to the unit Figure 7 Duct covers sold separately are available to cover the space between...

Page 8: ...duct covers are available and may be or dered separately 1 If multiple duct covers are used connect the pieces together using sheetmetal screws provided with chimneys Figure 9 2 Attach the duct cover s to the hood using sheetmetal screws as shown in Figure 9 Cabinet Installation Cabinet Installation Cabinet Installation Cabinet Installation Cabinet Installation The PHE hood can be in stalled under...

Page 9: ...mm x 18 mm screws provided with hood leaving 1 4 exposed 2 If the hood is installed for vertical discharge use Figure 11 to create clearance holes for passage of the transition and conduit Dimension A in Figure 11 depends on the hood model being installed and can be located in the table above Figure 10 Figure 11 ...

Page 10: ...izontal discharge use Figure 5 for the geometry of the cutout required for clearance of the transition 4 Hang hood from screws and tighten securely 5 Install two wall anchors as described in step 15 on the previous page ...

Page 11: ... the PHE with an iring the PHE with an iring the PHE with an Integral motor Integral motor Integral motor Integral motor Integral motor W W W W War ar ar ar arning Tur ning Tur ning Tur ning Tur ning Turn of n of n of n of n off elec f elec f elec f elec f elec tricity at the service tricity at the service tricity at the service tricity at the service tricity at the service panel befor panel befor...

Page 12: ...er Remote Blower Remote Blower Remote Blower Remote Blower W W W W War ar ar ar arning Tur ning Tur ning Tur ning Tur ning Turn of n of n of n of n off electric f electric f electric f electric f electric ity at the service panel ity at the service panel ity at the service panel ity at the service panel ity at the service panel befor befor befor befor before wiring the unit e wiring the unit e wir...

Page 13: ...duit connector 8 Connect the black white red and blue wires from the remote ventilator to the black white red and blue wires of the pigtail respectively Connect the remote blower green yellow ground wire to the ground wire from the service panel 9 Close junction box cover Check that all light bulbs are secure in their sockets Install filters Turn power on at service panel and check lights and blow...

Reviews: