15
Step 6: Electrical Requirements, Connection & Grounding
Dual Fuel models must be connected to the power supply utilizing one of the following methods. For all methods
of connection, the length of the cord or conduit/wiring must allow the unit to be slid completely out of the cabinet
without having to unplug or disconnect the unit from the power supply. Recommended minimum free length of
cord or conduit is four feet. Electrical installations and grounding must be in accordance with all local codes and
ordinances, and/or the National Electric Code, as applicable.
•
4-CONDUCTOR CORD -
NORMALLY, A UNIT MUST
BE CONNECTED TO THE
POWER SUPPLY WITH A 3-
POLE, 4-CONDUCTOR
CORD KIT RATED 125/250
VOLTS, 50 AMPERES, AND
MARKED FOR USE WITH
RANGES.
The cord kit must
be attached to the range junc-
tion box with a strain relief
which will fit a 1" diameter hole.
If not already equipped, the
cord must have 1/4" faston
closed-loop lugs attached to
the free ends of the individual
conductors, preferably sol-
dered in place.
•
PERMANENT CONNECTION
(HARD WIRING)
- Units may
be hard wired to the power
supply. The installer must
provide approved flexible
aluminum conduit, 3/4" trade
size, maximum 6 feet long.
Locate the junction box on the
rear of the unit and remove
cover. Refer to Fig. 9. Remove
the ground strap retaining
screw and bend the ground
strap up. Refer to Fig. 9. The
conduit must be installed to
the junction box using an
approved conduit connector.
Wiring for the unit is to be
brought into the junction box
through the conduit. Refer to
Chart C on Page 14 for rating
of wiring and sizing of indi-
vidual conductors. The ends
of the wiring must have
1/4" faston closed-loop lugs
attached, preferably soldered
in place. Make the connec-
tions to the terminal block pro-
vided. Secure the ground lead
to the junction box with the
screw previously used to se-
cure the ground strap. Refer
to Fig. 10. The free end of the
conduit must be connected to
a junction box provided in the
gas and electrical supply zone,
as shown in Figure 3A on Page
7.
•
3-CONDUCTOR CORD –
WHERE LOCAL CODES
AND ORDINANCES PERMIT
GROUNDING THROUGH
NEUTRAL, AND CONVER-
SION OF SUPPLY TO 4
WIRE IS IMPRACTICAL,
UNIT MAY BE CONNECTED
TO THE POWER SUPPLY
FIG. 8 – Location of Junction
Box on dual fuel ranges.
WITH A 3-POLE,
3-CONDUCTOR CORD KIT
RATED 125/250 VOLTS, 50
AMPERES, AND MARKED
FOR USE WITH RANGES.
The cord kit must be attached
to the range junction box with a
strain relief which will fit a 1"
diameter hole. If not already
equipped, the cord must have
1/4" faston closed-loop lugs at-
tached to the free ends of the
individual conductors, prefer-
ably soldered in place.