background image

10 

 

WARNING: The exposed surfaces of motors, refrigerant 
piping, and other fluid circuit components can be very 
hot and can cause burns if touched with unprotected 
hands. 

 

 

CAUTION: Disconnect and lock out incoming power 
before installing, servicing, or maintaining the 
equipment. Connecting power to the main terminal 
block energizes the entire electric circuitry of the unit. 
Electric power at the main disconnect should be shut 
off before opening access panels for repair or 
maintenance. 

 

 

CAUTION: Wear eye protection when installing, 
maintaining, or repairing the equipment to protect 
against any sparks, debris, or fluid leaks. 

 

 

CAUTION: Wear protective gloves when installing, 
maintaining, or repairing the equipment to protect 
against any sparks, debris, or fluid leaks. 

 

 

CAUTION: Wire the unit ground in compliance with 
local and national codes. 

 

 

CAUTION: The unit requires the main power to remain 
connected during off-hours to energize the 
compressor’s crankcase heater. Disconnect main 
power only when servicing the chiller. The crankcase 
heater should remain on when the compressor is off to 
ensure liquid refrigerant does not accumulate in the 
compressor crankcase. Connect main power at least 
24 hours prior to initial startup. 

 

Compressor Control Logic 

The chiller uses variable capacity control. The 
compressor has a slide valve to provide variable 
capacity control from 25-100% by directly 
controlling the amount of refrigerant gas taken in by 
the compressor rotors. The amount of gas taken in 
depends on the valve position. The loader and 
unloader solenoid valves control the slide valve 
position. These valves are pulsed in short time 
increments to balance compressor capacity with the 
chiller load. The chiller has a minimum compressor 
recycle timer to protect the compressor from rapid 
cycling. The recycle timer begins once a compressor 
starts and will not let that compressor restart until 
the recycle timer has timed-out. 
 
When the start button is pressed any pumps 
controlled by the chiller will turn on, any condenser 
water-regulating valves will open, and the electronic 
expansion valve and liquid line solenoid valve for the 
lead chiller circuit will open and that compressor will 
start. The compressor will run unloaded for 

approximately two minutes after which it will 
load/unload as required to maintain the fluid set 
point temperature. If there are multiple chillers in a 
master/slave arrangement, additional compressors 
will start and then load/unload as needed. 
 
After pressing the stop button all compressors run 
unloaded for approximately 60 seconds and then 
shutdown one at a time with a two-second time 
delay between compressors. After all compressors 
are stopped, all liquid line solenoid valves, 
condenser water regulating valves, and electronic 
expansion valves in the system close. Any pumps 
controlled by the chiller run for 60 seconds and then 
stop. The system is now ready to begin the next 
startup sequence. 
 

Master/Slave 

It is possible to link together multiple chillers to form 
a single system, using single or dual compressor 
chillers with a maximum of six compressors 
connected. Any chiller can be setup to be a master 
or a slave. The master chiller controls the staging 
order of the compressors and the running demand 
of all the compressors in the system in order to 
maintain the common chilled water set point. A slave 
chiller becomes dependent on the master only for its 
compressor staging order and running demand. The 
slave chiller PLC performs all other operations. The 
chilled water piping must be connected using a 
manifold and the supply sensor must be positioned 
downstream of all individual chilled water streams to 
read a mixed water temperature. Wire the supply 
and return water temperature sensors in the 
common return chilled water piping to the chiller 
PLC designated as the master. 
 

 

Summary of Contents for Accuchiller MX Series

Page 1: ......

Page 2: ......

Page 3: ...rmining Equivalent Line Length 6 Table 1 Equivalent Lengths of Elbows 7 Liquid Line Sizing 7 Table 2 Liquid Line Size Circuit inches OD 7 Discharge Hot Gas Line Sizing 7 Figure 4 Vertical Riser Traps...

Page 4: ...nputs Outputs Screens 16 Figure 20 Digital Inputs Screen 16 Figure 21 Digital Outputs Screen 16 Figure 22 Analog Inputs Screen 16 Figure 23 Analog Outputs Screen 17 Figure 24 RTD Inputs Screen 17 Menu...

Page 5: ...Restore Factory Settings 23 Figure 36 Factory Settings Restored 23 Menu 2 Remote Mode 23 Menu 2 Backup Chiller 23 Figure 37 Backup Chiller Screen 23 Menu 2 Modbus BAS 23 Figure 38 Modbus Setup Screen...

Page 6: ...Checking Compressor Oil Level 29 Cleaning the Operator Interface 29 General Troubleshooting 29 Preventive Maintenance Checklist 32 Drawings 32...

Page 7: ...erant for heat transfer purposes This chemical is sealed and tested in a pressurized system containing ASME coded vessels however a system failure will release it Refrigerant gas can cause toxic fumes...

Page 8: ...aining or repairing the equipment to protect against any sparks debris or fluid leaks Pre Installation Receiving Inspection When the unit arrives verify the information on the unit nameplate agrees wi...

Page 9: ...d impact loading caused by sudden jerking when lifting or lowering the chiller Use pads where abrasive surface contact may occur Process Fluid Piping Proper insulation of chilled process fluid piping...

Page 10: ...meter elevation when operating Wear ear protection as required for personal comfort when operating or working in close proximity to the chiller CAUTION Wear protective gloves when installing maintaini...

Page 11: ...ide lifting brackets Use spreader bars when lifting to apply the lifting force vertically Under no circumstances use the coil headers or return bends in the lifting or moving of the condenser Mounting...

Page 12: ...er than 100 actual feet without a minimum of 2 efficiency decrease 4 To form a proper liquid seal at the condenser immediately drop at least 15 inches down from the liquid outlet before routing the pi...

Page 13: ...ght from the condenser liquid line connection The liquid line does not require pitching Install a pressure tap valve at the condenser to facilitate measuring pressure for service Liquid lines do not t...

Page 14: ...Systems Designed for 40 F to 80 F Set Point 50 Ton 75 Ton 100 Ton 125 Ton 50 Ton 75 Ton 100 Ton 125 Ton 25 A 1 3 8 1 5 8 1 5 8 1 5 8 1 3 8 1 5 8 1 5 8 2 1 8 B 1 5 8 2 1 8 2 1 8 2 5 8 1 5 8 2 1 8 2 1...

Page 15: ...leg is not within the specified range notify the supplier and correct before operating the unit Voltage imbalance must not exceed two percent Excessive voltage imbalance between the phases of a three...

Page 16: ...begins once a compressor starts and will not let that compressor restart until the recycle timer has timed out When the start button is pressed any pumps controlled by the chiller will turn on any con...

Page 17: ...s screen displays for 5 seconds after the Programmable Logic Controller PLC and Human Machine Interface HMI establish communications The control system version is located on this start up screen Figur...

Page 18: ...is button displays the set point and process temperatures in a large font Figure 9 Alarms Button A listing of active and prior alarm history Figure 11 Figure 12 Figure 13 Detail Provide additional cir...

Page 19: ...Figure 25 EXV Control Electric Expansion Valve Setup Figure 26 Discharge Control Water Regulating Valve Setup Discharge Pressure Control Figure 27 Figure 28 Capacity Control This shows the compressor...

Page 20: ...ion of the display will be blank All alarms must be resolved and reset using the RESET ALARM button Alarm Setup The Alarm Setup screen allows changes to alarm settings Figure 12 Alarm Setup Alarm Glyc...

Page 21: ...Screen will display the Interlock Screen If the compressor is not starting the reason for the fault will clearly be visible on this screen Figure 16 Interlocks Touching the CRITICAL button opens the...

Page 22: ...puts Outputs Inputs Outputs Screens The Inputs Outputs screens provide the status of all digital inputs digital outputs analog inputs and outputs When the PLC input LED is on the corresponding input o...

Page 23: ...Value Mode Selection AUTO MODE The valve will always respond relative to the demand PID regardless of how many compressors are running MANUAL MODE The manual mode value percent will be the output to t...

Page 24: ...eat The difference between the saturated suction temperature and the suction line temperature is the superheat The superheat is factory set for 10 F and should never exceed 15 F or go below 4 F Only a...

Page 25: ...cription Default Value Mode In Auto Mode the valve adjusts to maintain optimum performance In manual mode it holds to the input valve AUTOMATIC Discharge Setpoint Discharge Setpoint Value 133 PSIG Low...

Page 26: ...25 100 of full capacity Figure 29 Capacity Control Screen Table 12 Capacity Control Parameters Menu Item Description Default Value Automatic or Manual Mode In Auto Mode the control system adjusts the...

Page 27: ...or Staging Screen Table 14 Compressor Staging Parameters Menu Item Description Default Value Stage Up Trigger This parameter in conjunction with the Stage Up Delay determines at what percent the next...

Page 28: ...view Figure 34 Menu 2 Screen Table 16 Menu 2 Functions Function Description Screen Reference Defaults Provides the ability to restore the control system back to factory defaults in the case that an un...

Page 29: ...rt stop When active the Remote Mode toggle will indicate Remote Start Stop Enabled and when not active it will indicate Remote Start Stop Disabled Menu 2 Backup Chiller If this feature has been enable...

Page 30: ...ankcase heater Disconnect main power only when servicing the chiller The crankcase heater should remain on when the compressor is off to ensure liquid refrigerant does not accumulate in the compressor...

Page 31: ...ecialist in the industry is involved Table 17 shows the list of water characteristics and quality limitations Table 17 Fill Water Chemistry Requirements Water Characteristic Quality Limitation Alkalin...

Page 32: ...vital that the Freezestat is set properly Step 6 Turn On Control Power Turn on the control power by turning the control power switch to On The panel displays should now be illuminated Due to extreme...

Page 33: ...that there are locations for voltage readings amperages etc for monitoring over time With this information maintenance personnel may be able to correct a potential problem before it causes any downtim...

Page 34: ...se heater when the heater is on Once a Year Repeat items 1 through 17 land continue with the following 18 Check the condition of the chilled water for algae and particulate fouling Back flush the evap...

Page 35: ...r for five seconds Incorrect three phase rotation Correct phasing of incoming power Loss of phase Check incoming power High motor temperature Check oil level superheat liquid injection High oil discha...

Page 36: ...e High condenser water temperature MXW models only Maximum temperature is 105 F Condenser water regulating valve MXW models only Replace if faulty High condenser air temperature MXR models only Maximu...

Page 37: ...apacity Check to make sure chiller is properly sized for process load Thermocouple Replace if faulty Microprocessor input card process sensor Replace if faulty Temperature values unsteady or out of ra...

Page 38: ...2 Amps Compressor L3 Amps Refrigerant Superheat Refrigerant Subcooling Compressor Discharge Check Valve Compressor Crankcase Heater Evaporator PSID Condenser PSID Clean Condenser Clean Evaporator Oil...

Page 39: ......

Page 40: ...Sales Customer Service Parts Department 847 966 2260 info thermalcare com 847 966 2260 847 966 9358 fax 847 966 2636 847 966 8560 847 966 9358 fax www thermalcare com info thermalcare com service the...

Reviews: