background image

 

24 

 

WARNING: Ethylene Glycol is flammable at higher 
temperatures in a vapor state. Carefully handle this 
material and keep away from open flames or other 
possible ignition sources. 

 

Step 3 - Condenser Water Temperature and 
Flow 

Check the condenser water lines to make sure all 
connections are secure. Make sure sufficient 
condenser fluid flow and pressure are available, and 
all shut-off valves are open. The chiller includes a 
factory mounted condenser water-regulating valve 
to regulate condenser water flow to maintain the 
proper refrigerant pressures. The electronic water 
regulating valve ships in the closed position and 
opens after enabling the circuit. The nominal design 
is for 220 gpm of 40% ethylene glycol or water @ 
85°F entering the condenser with a 10 psi pressure 
drop. The chiller will start and operate with inlet 
water temperatures between 55°F and 95°F. The 
actual flow requirements will vary. 
 

Step 4 – Check Refrigerant Valves 

During shipment or installation, valves are 
sometimes closed. Verify that all refrigerant valves 
are open. 
 

Step 5 – Check Low Temperature Alarm 

Make sure the Low Temperature Alarm Set Point is 
proper for the operating conditions of the chiller. 
The Low Temperature Alarm setting is in a 
password-protected menu of the chiller controller. 
Refer to the control section of this manual for 
instructions on how to access this menu. Set the Low 
Temperature Alarm 10°F below the minimum chilled 
water temperature setting that the chiller will be 
operating. Also, ensure the process coolant has 
sufficient freeze protection (glycol) to handle at least 
5°F below the Low Temperature Fault setting. All 
chillers ship with the Low Temperature Fault set at 
38°F. This protects against a possible freeze-up if no 
glycol is present. Once the proper glycol solution is 
present, adjust the Low Temperature Fault to the 
appropriate setting. 
 

 

CAUTION: The manufacturer’s warranty does not 
cover the evaporator from freezing. It is vital that the 
Evaporator Low Temperature Fault is set properly. 

 

Step 6 – Turn On Control Power 

Turn on the control power by turning the control 
power switch to "On.” The panel should be on. Due 
to extreme ambient temperatures during shipment 
and installation, you may encounter a High 
Refrigerant Pressure alarm when you turn on the 
control power. If this is the case, reset the alarm and 
wait until no further alarm conditions are present. 
 

Step 7 – Establish Coolant Flow 

Establish flow through the chiller. 
 

Note: The compressor will not start as long as the flow switch is 
open. The compressor only operates if there is a positive flow 
through the evaporator. 
 

Set flow using a discharge throttling valve or flow 
control valve (by others). The valve should be the 
same size as the To Process connection of the chiller. 
The nominal flow rates of the chiller are 467 gpm of 
40% ethylene glycol @ 10°F setpoint with a 16 psi 
pressure drop and 427 gpm of 40% ethylene glycol 
@ 15°F set point with a 12 psi pressure drop. 
 

Step 8 – Initial Chiller Operation 

Enter the desired leaving fluid temperature on the 
chiller HMI. The chiller has an intended operating 
range of 10°F to 15°F and a set point range of 10°F 
to 55°F. Under normal operation, the entering water 
temperature should not exceed 80°F; however, the 
chiller can start and operate short-term with 
entering fluid temperatures up to 90°F to allow the 
chiller to pull down the temperature of a reservoir or 
process fluid loop on start-up. The chiller should 
now be controlling to the selected temperature. 
Please note that if there is insufficient load the 
compressor may cycle on and off causing swings in 
temperature. 
 

 

WARNING: Under no circumstance, deactivate the 
High Refrigerant Pressure or the Low Compressor 
Pressure switches. Failure to heed this warning can 
cause serious compressor damage, severe personal 
injury, or death. 

 

Summary of Contents for Accuchiller TCFW375

Page 1: ......

Page 2: ......

Page 3: ...ndary 5 Control Operation 6 Screen Navigation 6 System Initialization 6 Figure 1 Start Up Splash 6 Home Chiller Home Screen 7 System Overview 7 Figure 2 Chiller Home 7 Table 1 System Overview Function...

Page 4: ...Inputs Outputs 13 Figure 25 Inputs Outputs Menu 13 Figure 26 Inputs Outputs Temperature Inputs 13 Figure 27 Inputs Outputs Pressure Inputs 13 Figure 28 Inputs Outputs Analog Inputs 13 Figure 29 Input...

Page 5: ...s 18 Figure 45 User Setup IP Address Setup 18 User Setup Units 18 Figure 46 User Setup Display Units Setup 18 User Setup Remote Setpoint 18 Figure 47 User Setup Remote Setpoint Setup 18 User Setup Pri...

Page 6: ...Screen 21 Modbus 22 Table 10 Modbus 22 Start Up 23 Step 1 Connect Main Power 23 Step 2 Fill Coolant Circuit 23 Step 3 Condenser Water Temperature and Flow 24 Step 4 Check Refrigerant Valves 24 Step 5...

Page 7: ...We recommend the use of a refrigerant management program to document the type and quantity of refrigerant in the equipment In addition we recommend only licensed and EPA certified service technicians...

Page 8: ...ng the shipping damage claim is the responsibility of the receiving party Do not install damaged equipment without getting the equipment repaired Shipping damage is the responsibility of the carrier T...

Page 9: ...conditions may result in the chiller shutting down due to high refrigerant pressure Allowing the condenser to plug up from contaminants in the condenser water stream adversely affects performance In...

Page 10: ...age at the main power source Voltage must be within the voltage utilization range given on the drawings included with the unit If the measured voltage on any leg is not within the specified range noti...

Page 11: ...start if the process heat load continues to increase after the lead compressor is running and fully loaded Both compressors will share the load and modulate their capacities in order to maintain the...

Page 12: ...assword protected to prevent unintended changes There are two levels of security Username is case sensitive User Level Password 9999 Supervisor Level Password 7720 When navigating screens any user adj...

Page 13: ...tatus Messaging Provides information about any warnings or alarms which may have occurred None Setpoint Modify the Setpoint by touching the current Setpoint on the HMI An authorized security level pas...

Page 14: ...l system Some parameters are password protected The main User level password is for gaining access to changing the main system set point and various other warning and alarm settings A few higher level...

Page 15: ...e above shows there are no alarms in history if an alarm condition previously existed it would appear in this window Warning Glycol If the Chiller Setpoint goes below 45 F the Glycol Warning Screen wi...

Page 16: ...rmation about the various portions of the system Figure 10 Diagnostics Menu 1 Figure 11 Diagnostics Menu 2 Figure 12 Diagnostics Circuit Details Figure 13 Diagnostics Circuit Turbocor Figure 14 Diagno...

Page 17: ...l of supervisory control to some operating parameters the control system includes security level protections If you are attempting to access an area where neither of these passwords is accepted you ma...

Page 18: ...gure 22 Security Edit User Figure 23 Security Delete User Figure 24 Security Change Password Table 2 Security Users and Passwords User Name Password Screen Reference User 9999 None Supervisor 7720 Non...

Page 19: ...itoring system operation and for diagnosing any performance issues or alarms that arise Figure 25 Inputs Outputs Menu Figure 26 Inputs Outputs Temperature Inputs Figure 27 Inputs Outputs Pressure Inpu...

Page 20: ...meters In most cases the factory default settings are sufficient however adjustment of parameters and settings is possible through the User Setup menus Figure 32 User Setup Menu 1 Figure 33 User Setup...

Page 21: ...ypass Delay time once the system has started before monitoring High and Low temperature Alarms 1200 sec Flow Delay Flow Sensor fault delay timer 5 sec User Setup Hot Gas Bypass Figure 38 User Setup Ho...

Page 22: ...Mode In Auto Mode the control system adjusts the number of staged compressors relative to the demand and available compressors In manual mode the number of staged compressors depends on the Manual Mo...

Page 23: ...r regulating valve is standard The valve is a butterfly type valve with a modulating actuator and is located in the condenser water piping at the outlet of the condenser The valve regulates the flow o...

Page 24: ...Address Setup User Setup Units Figure 46 User Setup Display Units Setup User Setup Remote Setpoint When the remote setpoint option is active an incoming 4 20mA or 0 10VDC signal controls the setpoint...

Page 25: ...tment Figure 50 User Setup Date Time Setup User Setup Evaporator Valve Evaporator Valve Control Screen This feature provides the ability to close off evaporator fluid flow when a circuit is not in ope...

Page 26: ...ly start if a power outage has occurred during a run state When active the Automatic Start toggle will indicate Automatic Start Enabled and when not active it will indicate Automatic Start Disabled Us...

Page 27: ...erature and optional hot gas bypass valve resisters if present for easy analysis of the system operation Trending is always enabled and always running Figure 55 System Trending 1 Figure 56 System Tren...

Page 28: ...utRegister 1 2 PLC_VERSION Real InputRegister 3 1 SYSTEM_DEMAND_PERCENT Int InputRegister 4 1 HMI_ALARM_DISPLAY Int InputRegister 5 1 CHILLER_STATUS UInt InputRegister 6 2 CKT1_RFRG_SUCTION_TEMP_HMI R...

Page 29: ...s incorrect open the main power disconnect and switch two line leads on the main power terminal blocks or the unit mounted disconnect All electrical components are in phase at the factory Do not inter...

Page 30: ...he Low Temperature Fault to the appropriate setting CAUTION The manufacturer s warranty does not cover the evaporator from freezing It is vital that the Evaporator Low Temperature Fault is set properl...

Page 31: ...y reduced downtime reduced repair costs and an extended useful lifetime for the chiller Any monetary costs of implementing these procedures will usually more than pay for itself Once a Week 1 Check to...

Page 32: ...dust build up and clean if necessary 19 Check calibration of temperature pressure sensors 20 Check operation of the inlet guide vane IGV assembly Once Every 5 years Repeat items 1 through 20 and conti...

Page 33: ...t out Insufficient refrigerant charge Check refrigerant charge Faulty sensor Check sensor Fluid temperatures too low Check set points Low fluid flow Check fluid flow Compressor does not power up No Lo...

Page 34: ...mperature set points Faulty chilled water temperature sensors Check chilled water temperature sensors No main power Check power at terminal block Low water flow Check water flow Drawings We have prepa...

Page 35: ......

Page 36: ...Sales Customer Service Parts Department 847 966 2260 info thermalcare com 847 966 2260 847 966 2636 847 966 8560 847 966 9358 fax www thermalcare com sales thermalcare com service thermalcare com tcp...

Reviews: