background image

 

 

WARNING: This equipment contains refrigerant under 
pressure. Accidental release of refrigerant under 
pressure can cause personal injury and or property 
damage. 

 

 

WARNING: The exposed surfaces of motors, refrigerant 
piping, and other fluid circuit components can be very 
hot and can cause burns if touched with unprotected 
hands. 

 

 

CAUTION: Disconnect and lock out incoming power 
before installing, servicing, or maintaining the 
equipment. Connecting power to the main terminal 
block energizes the entire electric circuitry of the unit. 
Shut off the electric power at the main disconnect 
before opening access panels for repair or 
maintenance. 

 

 

CAUTION: Wear eye protection when installing, 
maintaining, or repairing the equipment to protect 
against any sparks, debris, or fluid leaks. 

 

 

CAUTION: The equipment will exceed 70 dBA sound 
pressure at 1 meter distance and 1 meter elevation 
when operating. Wear ear protection as required for 
personal comfort when operating or working in close 
proximity to the chiller. 

 

 

CAUTION: Wear protective gloves when installing, 
maintaining, or repairing the equipment to protect 
against any sparks, debris, or fluid leaks. 

 

Pre-Installation 

Receiving Inspection 

When the equipment arrives, verify the information 
on the nameplate agrees with the order 
acknowledgement and shipping papers. Inspect the 
equipment for any visible damage and verify all 
items shown on the bill of lading are present. If 
damage is evident, document it on the delivery 
receipt by clearly marking any item with damage as 
“unit damage” and notify the carrier. In addition, 
notify our Customer Service Department for 
assistance with preparing and filing freight damage 
claims, including arranging for an estimate on repair 
costs; however, filing the shipping damage claim is 
the responsibility of the receiving party. Do not 
install damaged equipment without getting the 
equipment repaired. 
 
Shipping damage is the responsibility of the carrier. 
To protect against possible loss due to damage 
incurred during shipping and to expedite payment 
for damages, it is important to follow proper 
procedures and keep records. Photographs of 

damaged equipment are excellent documentation 
for your records. 
 
Start unpacking the equipment, inspect for 
concealed damage, and take photos of any damage 
found. Once received, equipment owners have the 
responsibility to provide reasonable evidence that 
the damage did not occur after delivery. Photos of 
the equipment damage while it is still partially 
packed will help in this regard. Refrigerant lines can 
be susceptible to damage in transit. Check for 
broken lines, oil leaks, damaged controls, or any 
other major component torn loose from its 
mounting point. 
 
Record any signs of concealed damage and file a 
shipping damage claim immediately with the 
shipping company. Most carriers require concealed 
damages be reported within 15 days of receipt of 
the equipment. In addition, notify our Customer 
Service Department for assistance with preparing 
and filing freight damage claims, including arranging 
for an estimate on repair costs; however, filing the 
shipping damage claim is the responsibility of the 
receiving party. 
 

Equipment Storage 

When storing the equipment, it is important to 
protect it from damage. Blow out any water from the 
chiller; cover it to keep dirt and debris from 
accumulating or getting in, and store in an indoor 
sheltered area that does not exceed 145°F. 
 

Installation - Chiller 

Foundation 

Install the chiller on a rigid, non-warping mounting 
pad, concrete foundation, or level floor suitable to 
support the full operating weight of the equipment. 
When installed the equipment must be level within 
¼ inch over its length and width.

Summary of Contents for Accuchiller TCFW375

Page 1: ......

Page 2: ......

Page 3: ...ndary 5 Control Operation 6 Screen Navigation 6 System Initialization 6 Figure 1 Start Up Splash 6 Home Chiller Home Screen 7 System Overview 7 Figure 2 Chiller Home 7 Table 1 System Overview Function...

Page 4: ...Inputs Outputs 13 Figure 25 Inputs Outputs Menu 13 Figure 26 Inputs Outputs Temperature Inputs 13 Figure 27 Inputs Outputs Pressure Inputs 13 Figure 28 Inputs Outputs Analog Inputs 13 Figure 29 Input...

Page 5: ...s 18 Figure 45 User Setup IP Address Setup 18 User Setup Units 18 Figure 46 User Setup Display Units Setup 18 User Setup Remote Setpoint 18 Figure 47 User Setup Remote Setpoint Setup 18 User Setup Pri...

Page 6: ...Screen 21 Modbus 22 Table 10 Modbus 22 Start Up 23 Step 1 Connect Main Power 23 Step 2 Fill Coolant Circuit 23 Step 3 Condenser Water Temperature and Flow 24 Step 4 Check Refrigerant Valves 24 Step 5...

Page 7: ...We recommend the use of a refrigerant management program to document the type and quantity of refrigerant in the equipment In addition we recommend only licensed and EPA certified service technicians...

Page 8: ...ng the shipping damage claim is the responsibility of the receiving party Do not install damaged equipment without getting the equipment repaired Shipping damage is the responsibility of the carrier T...

Page 9: ...conditions may result in the chiller shutting down due to high refrigerant pressure Allowing the condenser to plug up from contaminants in the condenser water stream adversely affects performance In...

Page 10: ...age at the main power source Voltage must be within the voltage utilization range given on the drawings included with the unit If the measured voltage on any leg is not within the specified range noti...

Page 11: ...start if the process heat load continues to increase after the lead compressor is running and fully loaded Both compressors will share the load and modulate their capacities in order to maintain the...

Page 12: ...assword protected to prevent unintended changes There are two levels of security Username is case sensitive User Level Password 9999 Supervisor Level Password 7720 When navigating screens any user adj...

Page 13: ...tatus Messaging Provides information about any warnings or alarms which may have occurred None Setpoint Modify the Setpoint by touching the current Setpoint on the HMI An authorized security level pas...

Page 14: ...l system Some parameters are password protected The main User level password is for gaining access to changing the main system set point and various other warning and alarm settings A few higher level...

Page 15: ...e above shows there are no alarms in history if an alarm condition previously existed it would appear in this window Warning Glycol If the Chiller Setpoint goes below 45 F the Glycol Warning Screen wi...

Page 16: ...rmation about the various portions of the system Figure 10 Diagnostics Menu 1 Figure 11 Diagnostics Menu 2 Figure 12 Diagnostics Circuit Details Figure 13 Diagnostics Circuit Turbocor Figure 14 Diagno...

Page 17: ...l of supervisory control to some operating parameters the control system includes security level protections If you are attempting to access an area where neither of these passwords is accepted you ma...

Page 18: ...gure 22 Security Edit User Figure 23 Security Delete User Figure 24 Security Change Password Table 2 Security Users and Passwords User Name Password Screen Reference User 9999 None Supervisor 7720 Non...

Page 19: ...itoring system operation and for diagnosing any performance issues or alarms that arise Figure 25 Inputs Outputs Menu Figure 26 Inputs Outputs Temperature Inputs Figure 27 Inputs Outputs Pressure Inpu...

Page 20: ...meters In most cases the factory default settings are sufficient however adjustment of parameters and settings is possible through the User Setup menus Figure 32 User Setup Menu 1 Figure 33 User Setup...

Page 21: ...ypass Delay time once the system has started before monitoring High and Low temperature Alarms 1200 sec Flow Delay Flow Sensor fault delay timer 5 sec User Setup Hot Gas Bypass Figure 38 User Setup Ho...

Page 22: ...Mode In Auto Mode the control system adjusts the number of staged compressors relative to the demand and available compressors In manual mode the number of staged compressors depends on the Manual Mo...

Page 23: ...r regulating valve is standard The valve is a butterfly type valve with a modulating actuator and is located in the condenser water piping at the outlet of the condenser The valve regulates the flow o...

Page 24: ...Address Setup User Setup Units Figure 46 User Setup Display Units Setup User Setup Remote Setpoint When the remote setpoint option is active an incoming 4 20mA or 0 10VDC signal controls the setpoint...

Page 25: ...tment Figure 50 User Setup Date Time Setup User Setup Evaporator Valve Evaporator Valve Control Screen This feature provides the ability to close off evaporator fluid flow when a circuit is not in ope...

Page 26: ...ly start if a power outage has occurred during a run state When active the Automatic Start toggle will indicate Automatic Start Enabled and when not active it will indicate Automatic Start Disabled Us...

Page 27: ...erature and optional hot gas bypass valve resisters if present for easy analysis of the system operation Trending is always enabled and always running Figure 55 System Trending 1 Figure 56 System Tren...

Page 28: ...utRegister 1 2 PLC_VERSION Real InputRegister 3 1 SYSTEM_DEMAND_PERCENT Int InputRegister 4 1 HMI_ALARM_DISPLAY Int InputRegister 5 1 CHILLER_STATUS UInt InputRegister 6 2 CKT1_RFRG_SUCTION_TEMP_HMI R...

Page 29: ...s incorrect open the main power disconnect and switch two line leads on the main power terminal blocks or the unit mounted disconnect All electrical components are in phase at the factory Do not inter...

Page 30: ...he Low Temperature Fault to the appropriate setting CAUTION The manufacturer s warranty does not cover the evaporator from freezing It is vital that the Evaporator Low Temperature Fault is set properl...

Page 31: ...y reduced downtime reduced repair costs and an extended useful lifetime for the chiller Any monetary costs of implementing these procedures will usually more than pay for itself Once a Week 1 Check to...

Page 32: ...dust build up and clean if necessary 19 Check calibration of temperature pressure sensors 20 Check operation of the inlet guide vane IGV assembly Once Every 5 years Repeat items 1 through 20 and conti...

Page 33: ...t out Insufficient refrigerant charge Check refrigerant charge Faulty sensor Check sensor Fluid temperatures too low Check set points Low fluid flow Check fluid flow Compressor does not power up No Lo...

Page 34: ...mperature set points Faulty chilled water temperature sensors Check chilled water temperature sensors No main power Check power at terminal block Low water flow Check water flow Drawings We have prepa...

Page 35: ......