background image

                   

                                                  4                                                    

Rev.2 1/26/98

 

5.  LED Indicators, Pushbuttons, LCD Displays, and Relays 

a.

 

POWER LED

Green LED indicates Haloguard

 is receiving AC power. 

b.

 

FAULT LED and Relay

 - 

Indicates malfunction.

 

LCD indicates specific type of failure (See 

Figure 4).

 

c.

 

TEST Push-button

 - 

Energizes Alarm LED’s & relays.  Depress button five (5) times to 

sequence through each alarm level. 

d.

 

Adjustable Alarm LEDs & Relays

 -

Indicate

 

Alarm 1&Alarm 2 

Factory set for particular 

refrigerant (See Figure 9).  User adjustable as follows: 

 

 

RANGE 

1 PPM 

INCREMENTS 

10 PPM 

INCREMENTS 

0 - 1000 ppm 

10 - 100 

100 - 1000 

 

 

 

 

 

 

 

Note:   Optional TWA Integration activates Alarm 1 LED and relay when installed. 

 

 

TLV-TWA Alarm is factory set and not user adjustable. 

 

 

e.

 

OFFSCALE LED and Relay

 

- Factory set at 1000ppm

 

f.

 

RESET Push-button

 - 

Silences alarm, disables relays, and resets instrument for 20 minutes.  

LCD displays *CAUTION* and RESET with 20 minute countdown.  Alarms are 

automatically reactivated if alarm condition is not corrected.  Reset is automatically initiated 

on start-up and after power failure (Except when optional UPS is provided.).

 

6.  Optional Features: 

.  TWA Integration - Haloguard

 calculates an 8 hr. Time Weighted Average (TLV-TWA)

,

 

displays this value on LCD, activates Alarm 1 LED and relay if factory set PPM value is 

exceeded. Only used for gases with TLV-TWA less than 1000ppm. 

 

HALOGUARD

 IR 

CONTROLLER 

5 1/2” 

Figure 1 - Dimensional Drawing 

 

4” 

9” 

3/4” 

HALOGUARD

 IR 

MODULE 

6 1/2” 

14 1/4” 

(By 4” Deep) 

Summary of Contents for HALOGUARD Series

Page 1: ...G as Type 1 R 11 2 R 12 3 R 22 4 R 134a 5 6 7 R 123 Range 1 0 1000 ppm M ount 1 W all O utputs 11 4 x 3A Relays 12 0 5 VDC or 0 10 VDC 13 4 20mA O ptions Accessories A Audible Alarm B UPS E Inlet Outl...

Page 2: ...n 10 5 Testing 10 6 Trouble Shooting 10 7 Specifications 11 FIGURES Page 1 Dimension Drawing 4 2 Controller Upper Circuit Board 5 3 Controller Lower Circuit Board 5 4 Controller LCD Display Features 6...

Page 3: ...ase circuit rated 15A minimum Haloguard Controller and IR Sensor Module b Infrared IR Sensor Module should be mounted near potential leaks in a quiet area or downstream from leak source in area with a...

Page 4: ...d relay when installed TLV TWA Alarm is factory set and not user adjustable e OFFSCALE LED and Relay Factory set at 1000ppm f RESET Push button Silences alarm disables relays and resets instrument for...

Page 5: ...Lower Circuit Board RUN GAS ALARM ZERO SPAN AUD J5 ANALOG VOLT mA I C Offscale LED Alarm 2 LED Alarm 1 LED Power LED Fault LED Test Button IR Trim Analog Trim Pot 0 5 or 0 10 VDC UP ENTER DOWN Sensor...

Page 6: ...ailure Scan Stop Gas Type R 11 R 12 R 123 R 134 etc Figure 4 Controller LCD Display Features 8 hr TWA Concentration R 123 Concentration ppm Channels 1 8 Optional Scanner Only Flashing cursor means Aut...

Page 7: ...face plate from Haloguard Controller and IR Sensor Module using screw driver 2 Run cable from Haloguard Controller to IR Sensor Module location Eight feet 8FT of cable with DIN connectors standard op...

Page 8: ...tting Figure 8 Press TEST button until LATCH ON appears on the LCD Display LATCH ON mode requires manual RESET of all alarms 2 Analog Output optional is factory set at 0 5 VDC or 4 20mA as ordered Use...

Page 9: ...troller Terminal Provided Wire Color Extension Wire Color Function SCAN Red Red Scanner SIG White White Signal GND Blk Blk Black Ground Note SCAN Terminal is used with scanner Only Figure 6 Sensor Cab...

Page 10: ...allowing sufficient warm up time c Poor sensor location To check Zero Calibration fill a clean plastic trash bag with clean outside air tie off with twist tie let sample stabilize inside for 15 20 min...

Page 11: ...on condensing Controller 0o F to 120o F Non condensing Fault Diagnostics Indicator Light or LCD Readout for fault diagnostics See Figure 5 Materials IR Module NEMA 4 12 13 IP 65 Design Controller NEMA...

Page 12: ...OFFSCALE ALARM 2 Notes 1 Power Cord Provided w wall plug connector and 8 Ft 3 conductor wire 2 Audible and Visual Alarm Optional factory wired Remote Audible and Visual Alarms must be 120VAC and conne...

Reviews: