The DATA Extra HIU, Installation Instructions DE2, 12th August 2021
Stage 6 - Venting the Heating System
It is important that the central heating system within the property is completely bled of air. The HIU is equipped with a manual air vent,
connected to the central heating circuit of the HIU.
Quick venting:
1. Vent the central heating system at the radiators. Start at the lowest point of the central heating system and finish at the highest. For
fast bleeding of the HIU, turn the manual air vent cap counter clockwise, but do not remove this cap.
2. If necessary, the venting function of the pump can also be used to aid bleeding (see chapter "Setting the pump").
3. Continue venting the entire central heating system and the HIU until the entire system has been completely bled.
4. Make sure that all the vents on the radiators are closed tight and turn the cap of the manual air vent on the HIU, clockwise until
finger tight.
Do not remove the manual air vent cap while the HIU is in operation. Ensure dirt is prevented from entering the air vent nipple, as it may
cause a blockage. Ensure that it does not come into contact with chlorine products ( 250 ppm) and that steps are taken to eliminate
water hammer in the central heating system.
.
Page 31
Summary of Contents for DATA Extra HIU
Page 7: ...The DATA Extra HIU Installation Instructions DE2 12th August 2021 Dimensions Page 7...
Page 15: ...The DATA Extra HIU Installation Instructions DE2 12th August 2021 HIU Schematic Page 15...
Page 17: ...The DATA Extra HIU Installation Instructions DE2 12th August 2021 Wiring Schematic Page 17...
Page 33: ...The DATA Extra HIU Installation Instructions DE2 12th August 2021 Page 33...
Page 37: ...The DATA Extra HIU Installation Instructions DE2 12th August 2021 Page 37...
Page 38: ...The DATA Extra HIU Installation Instructions DE2 12th August 2021 Page 38...