TSBC Instruction Manual
Page 19 of 48
Front Panel
Setpoint Menu
Time
De
g F
175
185
180
Water
Temperature
On Point
Operational SP
Off Point
Call For Heat
Relay (CH)
Call For Heat Settings
No.
Range / Choices
Parameter and Description
70
60 F to 230 F
Operational Setpoint
Setpoint used in Local Setpoint Mode when not servicing a Domestic Hot Water
Priority (DHWP) request.
71
0 F to –99 F
On Point
The boiler starts when the water temperature drops ‘On Point’ degrees below the
setpoint.
72
0 F to 99 F
Off Point
The boiler stops when the water temperature rises ‘Off Point’ degrees above the
setpoint.
73
60 F to 230 F
High Temp Stop
The boiler stops when the boiler outlet water temperature is above the High
Temperature Stop setpoint. This setpoint is active in every control mode. If the
lead boiler’s boiler outlet temperature is above the high temperature stop all
boilers are stopped.
74
140 F to 230 F
*DHWP Setpoint
The Domestic Hot Water Priority (DHWP) Setpoint is active when DHWP Input
(DP) closes and “DHWP” parameter is set to “yes” and Local SP Mode is
selected. When the contact is closed, the boiler outlet is maintained at, or above,
the DHW Setpoint.
75
40 to 90 F
*WWSD Setpoint
The Warm Weather Shutdown (WWSD) Setpoint used to disable boiler and or
system pump operation when enabled by setting the “WWSD” parameter to
“WWSD of Boiler”, “WWSD of Sys Pump” or “Both”.
76
140 F to 230 F
Max SP
The Maximum Operational Setpoint for all possible Local and Remote modes.
77
60 F to 230 F
Min SP
The Minimum Operational Setpoint is the lower limit for all Local and Remote
modes.
78
110 F to 235 F
Min BIT
Low Boiler Inlet Temperature alarm and event setpoint.
79
110 F to 180 F
*Min In H2O Temp.
Minimum Inlet Water Temperature setpoint used as the Mixing Valve inlet
temperature setpoint.
80
20 F to 50 F
*Max H2O Delta T
Maximum Water Differential (Boiler Outlet minus Boiler Inlet) Temperature
setpoint used as the Mixing Valve differential temperature setpoint.
81
20 F to 50 F
Max Delta T Hold
Maximum Water Differential (Boiler Outlet minus Boiler Inlet) Temperature used
to hold modulation rate at low fire.
* Only visible when parameter enabled on the configuration and setup menus