88
C. SECURITY MENU
1. Press and hold the MENU button to enter menu mode.
2. Access parameters and set password.
a. In MENU mode page through to the SECURITY menu and press ENTER.
b. Page down to the "Enter Password" parameter and press ENTER.
c. Use the arrow buttons to change the password value to the desired password and
hold
ENTER until the screen flashes.
3. The access level will reset to Basic after one hour if no key is pressed, or if power is removed.
PASSWORD
Access Level
Enter Password Description
Basic
0 (NONE)
This is the default access level. The user can view many parameters, but is only
allowed to edit a small sub-set of the parameters that are visible.
Supervisor
15
This password is set at the factory but can be changed in the field. The user can
view and edit most parameters that are visible. Note: Not all parameters will be vis-
ible at the Supervisor Access Level.
Factory
All relevant internal parameters in the system will be visible and programmable.
Please consult Thermal Solutions for the factory access level password.
Consult Thermal Solutions Boiler Control (TSBC) Instruction manual for operation guidance and a detailed list of parameters
and their associated access levels.
Summary of Contents for EVCA SERIES
Page 14: ...14 Figure 4 Typical Vertical Pressurized Venting ...
Page 16: ...16 Figure 6 Vertical Air Intake Piping Figure 5 Horizontal Air Intake Piping ...
Page 19: ...19 Figure 8 Schematic Boiler Piping ...
Page 25: ...25 Figure 9a 208 230 480V 1PH 3PH 60HZ Supply Power Wiring Schematic ...
Page 26: ...26 Figure 9b 120V 1PH 60HZ Supply Power Wiring Schematic ...
Page 27: ...27 Figure 9c Control Wiring Schematic EVCA 750 2000 ...
Page 29: ...29 Figure 9e Control Wiring Schematic EVCA 3000 ...
Page 32: ...32 Figure 10 Modular System Horizontal Air Intake Piping ...
Page 33: ...33 Figure 11 Modular System Vertical Air Intake Piping ...
Page 34: ...34 Figure 12 Modular System Typical One Pipe Water Piping ...
Page 35: ...35 Figure 13 Modular System Typical Primary Secondary Water Piping ...
Page 36: ...36 Figure 14 Modular System Typical Primary Secondary without System Pump ...
Page 37: ...37 Figure 15 Modular System Typical Reverse Return Water Piping ...
Page 38: ...38 Figure 16 Modular System Reverse Return with System Pump Only ...
Page 39: ...39 Figure 17 Modular System Typical Primary Secondary with Reverse Return ...
Page 55: ...55 Figure 18 Cleaning Secondary Heat Exchanger 1 2 ...
Page 56: ...56 This page intentionally left blank ...
Page 58: ...58 Figure 19 Boiler Combustion Chamber ...
Page 60: ...60 Figure 20 Burner Assembly FRONT VIEW TOP VIEW ...
Page 62: ...62 Figure 21a UL FM CSD 1 Main Gas Train Assembly EVCA 750 2000 ...
Page 64: ...64 Figure 21b UL FM CSD 1 Main Gas Train Assembly EVCA 3000 ...
Page 66: ...66 Figure 22a DB B Gas Train 750 Figure 22b DB B Gas Train 1000 2000 ...
Page 68: ...68 Figure 22c DB B w POC Gas Train 750 Figure 22d DB B w POC Gas Train 1000 2000 ...
Page 70: ...70 Figure 22e DB B Gas Train EVCA 3000 Figure 22f DB B w POC Gas Train EVCA 3000 ...
Page 72: ...72 Figure 23 Jacket ...
Page 74: ...74 Figure 24 EVCA 750 1000 and 1500 Secondary Heat Exchanger and Housing ...
Page 78: ...78 Figure 25b EVCA 3000 Secondary Heat Exchanger and Housing ...
Page 80: ...80 Figure 26 Control Panel Assembly ...
Page 82: ...82 Figure 27 Bishop Pilot Assembly ...
Page 97: ...97 NOTES ...
Page 98: ...98 NOTES ...
Page 99: ...99 NOTES ...