6.4 First Time Installation
The indoor units and the pipes between indoor and outdoor units must be leak tested and evacuated in
order to remove gas and moisture from the system. If not, the air and moisture in the refrigerant system
can cause undesirable effects such as the ones shown below.
•
Pressure in the system rises.
•
Operating current rises.
•
Cooling or heating efficiency drops.
•
Moisture in the refrigerant circuit may freeze and block capillary tubing.
•
Water may lead to corrosion of parts in the refrigerant system.
6.4.1 Gas Leak Check (Soap Water Method)
Apply soap water or a neutral liquid detergent to the indoor unit, line set connections, and
service ports with a soft brush. If bubbles start forming, there is a leak at the connection where
the bubbles form.
6.4.2 Air Purging with a Vacuum Pump
Procedure:
1.
Tighten the flare nuts of the indoor and outdoor units. Confirm that both the 2-way and 3-way
valves are set to the closed position.
2.
Connect the charge hose with the push pin of Handle Lo (low pressure side) to the 3-way valve
’
s
gas side service port.
3.
Connect the charge hose of Handle Hi (high pressure side) connection to the vacuum pump.
4.
Fully open the Handle Lo of the manifold valve.
5.
Operate the vacuum pump to evacuate.