INSTALLATION INSTRUCTIONS
9
1
Feet with locking nut
f
f
Position the device in the installation location.
f
f
Remove packing straps and polystyrene mouldings.
f
f
Level the device by adjusting the equipment feet.
f
f
After leveling the device fix the nut of the rubber feet to provide a maximum of structural safety.
external InStallatIon
!
materIal loSSeS
The heat pump must not be installed in areas where ambient temperatures frequently exceed 42 °C or areas
where temperatures frequently drop below 0 °C.
!
materIal loSSeS
Installation locations with aggressive air (e.g.
air loaded with ammonia, chlorine, metals, oil, ...) are inadmis-
sible because they can cause damage to the device.
Where possible select an installation location that has limited exposure to extreme rain or snow.
Mount the unit so that it is not exposed to direct strong wind, but is well ventilated.
The air inlet and outlet
must be free.
Protect your device with possibly a canopy, a base and baffles to weather.
The locaTion where The device is To be insTalled musT meeT The following condiTions:
-
Load-bearing floor (wet weight of the device approx.
430 kg).
-
Never operate the device in rooms at a risk from explosion due to dust, gases or vapours.
-
It is preferred that the location of the unit is not near a bedroom or a neighbour's bedroom.
Ideally a unit may
be mounted near a kitchen or laundry.
Opposite a neighbours garage is always prefferred.
-
The water heater should be located as close as possible to the most frequently used hot water tap connection.
-
Ensure that the data plate is clearly visible.
-
Ensure that the ambient temperature lies within the application limits for heat pump operation.
Internal InStallatIon
!
materIal loSSeS
The heat pump must not be installed in areas where ambient temperatures frequently exceed 42 °C or areas
where temperatures frequently drop below 0 °C.
!
materIal loSSeS
When installing the heat pump in a boiler room, ensure that the boiler operation will not be impaired.
!
materIal loSSeS
Do not place the device near high frequency machines.
The room where The device is To be insTalled musT meeT The following condiTions:
-
Load-bearing floor (wet weight of the device approx.
430 kg).
-
Never operate the device in rooms at a risk from explosion due to dust, gases or vapours.
-
Include in your considerations the utilisation of waste heat, for example from a boiler, tumble drier or
refrigerator/freezer.
-
The available floor area in the installation room must be at least 6 m².
Never install this equipment in rooms
with a volume of less than 13 m³.
-
Never restrict the clearances of the device through walls and ceilings further than illustrated in the figure
below.
-
In case of indoor installation and min. installation room volume, the room temperature might be reduced by
approx.
1-3 °C through the heat pump operation.
The initial temperature is reached again approx.
½ h after the
heat pump has been switched OFF.
Summary of Contents for TIHP 300
Page 1: ...INSTALLATION INSTRUCTIONS INTEGRATEDHEATPUMP300L FOR MODEL TIHP 300 OPERATION AND ...
Page 2: ...2 INSTALLATION INSTRUCTIONS ...
Page 25: ...INSTALLATION INSTRUCTIONS 25 Notes ...
Page 26: ...26 INSTALLATION INSTRUCTIONS Notes ...
Page 27: ...INSTALLATION INSTRUCTIONS 27 Notes ...
Page 28: ...Works for you www reece com au Thermann 313698 37792 8934 ...