Now you will need to decide on the steamhead placement in the shower so you can run the steam line from the generator to the 
steamhead. There are a couple of things you need to know about the placement of the steamhead and steam line itself.

24"

6"

B

7

 

Steam Line and Steamhead

A

C

Steam Line

Shown installed 

in attic  

DO NOT install any valve in the steam line. Flow of steam must 
be unobstructed.

DO NOT plumb any traps in the steam line.

The steam outlet on the generator requires a 1/2" brass   
union for easy installation (not included).

Use 1/2” brass pipe or copper tubing from unit to 
steamhead rough-in fitting as permitted by code.

A

B

The steam line can run up and then down, once; or horizontal; 
but never run down and then up. If it does, a steam trap will 
be produced at the low point blocking the flow of steam.

 Insulate the steam outlet piping if the piping run exceeds 10 feet or 
is exposed to cold areas. Use steam rated insulation.

 Pitch/angle steam lines back towards generator before any up or 
down turns; pitch/angle towards steam room after any up or down 
and avoid perfectly level plumbed lines.

THERMASOL.COM  

I

  800.776.0711

Total Wellness Package

9

Summary of Contents for 652592090008

Page 1: ...Total Wellness Package OVER 60 YEARS OF STEAM SHOWER INNOVATION Installation Manual For Tutorials and Troubleshooting visit www thermasol com solutions ...

Page 2: ...2 2 ThermaTouch Control 7 Inch Screen Installation Manual For Tutorials and Troubleshooting visit www thermasol com solutions TT7X XX OVER 60 YEARS OF STEAM SHOWER INNOVATION ...

Page 3: ...PPLICATION SLIPPING AND FALLING INTO THE STEAMHEAD ITSELF OR INTO THE STREAM OF STEAM EMITTING FROM THE STEAMHEAD WILL CAUSE SERIOUS BURNS OR PHYSICAL INJURY IF YOU ARE FEELING UNCOMFORTABLE DIZZY FAINT OR STARTING TO FALL ASLEEP IMMEDIATELY EXIT THE STEAM ROOM DO NOT USE STEAM ROOM IF YOU ARE UNDER THE AGE OF 16 UNLESS SUPERVISED BY AN ADULT THERMASOL STEAM BATH GENERATORS ARE NOT DESIGNED TO BE ...

Page 4: ...ing Power Supply Brick Item 03 7142 Materials needed o ThermaTouch control o M12 cable o Silicone o Power Distribution Module PDM o Mud Ring o Ethernet Cable with RJ 45 Connector not supplied o Other materials as required Back of Control REMINDER in order to receive software updates the unit must be plugged into the internet using an Ethernet Cable connected to a Router Router and Ethernet Cable n...

Page 5: ...er location DO NOT pinch nail staple wedge or bind the data cable DO NOT wrap the data cable around steam line or route it in a manner so that the hot steam line could melt the cable Any damage to the control cable will result in the control not working properly Carefully connect the data cable to the PDM and control BEFORE turning power on to the generator or PDM ON Turn Clockwise OFF Turn Counte...

Page 6: ...ALING THE CONTROL TO THE WALL Power on the control and see that it lights up Coat the entire groove on the control back with supplied waterproof silicone to fully seal the control to the wall Completely seal the control to the wall so moisture does not collect behind it Place the control on the wall pressing firmly You may need to tape the control into place until the silicone dries Be careful not...

Page 7: ...LS 110v 110v M12 Cable Audio Cable M12 Cable M8 Cable M12 Cable 6a Connecting ThermaTouch to Generator 6b Connecting ThermaTouch to Serenity Light Sound Rainhead THERMASOL COM I 800 776 0711 Total Wellness Package 7 ...

Page 8: ...rmaTouch to Digital Shower 6b Connecting Total Wellness Package THERMASOL COM I 800 776 0711 TTC SLS 110v M12 Cable M12 Cable Audio Cable TTC SLS 110v M12 Cable M12 Cable Audio Cable M8 Cable Total Wellness Package 8 8 ...

Page 9: ...es a 1 2 brass union for easy installation not included Use 1 2 brass pipe or copper tubing from unit to steamhead rough in fitting as permitted by code A B The steam line can run up and then down once or horizontal but never run down and then up If it does a steam trap will be produced at the low point blocking the flow of steam Insulate the steam outlet piping if the piping run exceeds 10 feet o...

Page 10: ...t be sealed to the wall to not allow vapor or water behind it plumbing must be done from backside of finshed space For new framing Mount and install rough in fitting to be flush with finished wall Connect a 1 2 NPT brass pipe or copper tubing to the steam outlet union not included on the generator running the pipe to the steam head location in the wall to connect with the steamhead rough in fittin...

Page 11: ...inal Pre Check Before Operation Upon final installation mount steamhead with facing up to allow aromatherapy well to dispense steam For detailed installation instructions of the steamhead please see Installation section in thermasol com customer support Apply a small amount of supplied lubricant directly on the o rings Once the shower wall is complete and the housing is sealed to the wall remove t...

Page 12: ...OVER 60 YEARS OF STEAM SHOWER INNOVATION Installation Manual For Tutorials and Troubleshooting visit www thermasol com solutions HVLSRSQ XX HydroVive ...

Page 13: ... BEFORE USE THESE PRODUCTS MAY BE HAZARDOUS TO YOUR HEALTH DO NOT USE STEAM ROOM WHILE UNDER THE INFLUENCE OF ALCOHOL OR DRUGS AS THIS CAN BE HAZARDOUS TO YOUR HEALTH YOUR SHOWER MAY BE A SLIP AND FALL HAZARD CHECK WITH YOUR CONTRACTOR OR FLOORING MANUFACTURER REGARDING THE SAFE USE OF YOUR FLOORING IN A STEAM APPLICATION SLIPPING AND FALLING INTO THE STEAMHEAD ITSELF OR INTO THE STREAM OF STEAM E...

Page 14: ...xible Water Line o Separate water volume control diverter with shut off valve Fig 1 Installation Profile View Compatible Controls ThermaTouch 7 and 10 HydroVive Light Sound Rain Head fixture and hardware Item HVLSRSQ XX Joist Mounting Bracket 4x 4 Flat Head Screw Plywood Waterproof Backing Mortar Finished Shower Surface RTV Silicone Sealant 10 Flat Head Screw O Ring 016 Screw Cover 25 Audio Cable ...

Page 15: ...37 lbs It must be mounted to a framed structure that can support its weight 16 7 16 7 14 5 14 25 14 25 Cutout Sizing PDM Sold and ships with ThermaTouch control ThermaTouch Control sold separately 25 Yellow M12 Cable Item 03 7149 25 ships with ThermaTouch control Digital Shower Valve By adding the Digital Shower Valve you replace multiple manual valves and can control all shower functions through ...

Page 16: ...otches at the top of the mounting guides with the mounting brackets and slip them over to firmly secure the HydroVive in place while the connections are made With HydroVive secured on the mounting brackets angle the unit to gain access and connect all cables Double check to ensure that all connections are correct before moving forward Connect both the M12 power data cable from the rainhead and the...

Page 17: ...e 3 5 included mounting screws and gradually insert them a little at a time to evenly lift the HydroVive into position to create a seal with the previously applied silicone DO NOT OVERTIGHTEN Once the HydroVive is in position and the silicone seal is created no further clamping force is necessary Sealing HydroVive 7 Apply silicone along the groove on the back of HydroVive Total Wellness Package TH...

Page 18: ...Digital Shower Valve OVER 60 YEARS OF STEAM SHOWER INNOVATION Installation Manual TDS 3000 18 18 ...

Page 19: ...USE THESE PRODUCTS MAY BE HAZARDOUS TO YOUR HEALTH DO NOT USE THIS PRODUCT WHILE UNDER THE INFLUENCE OF ALCOHOL OR DRUGS AS THIS CAN BE HAZARDOUS TO YOUR HEALTH All products must be installed in accordance with installation instructions provided Failure to do so may invalidate warranty at manufacturer s discretion 2018 ThermaSol Parts enclosed with the Digital Shower Digital Shower 10 9 x 6 93 x 2...

Page 20: ...hower Valve Digital Interface 110V Power 208 240VAC Steam Generator 110V Power Serenity Light and Sound TTC AUDIO OUT TTC INPUT SLS INPUT CONTROL 2 INPUT CONTROL 1 INPUT 24 VDC INPUT STEAM UNIT INPUT ThermaTouch Control Inside Shower To LAN ROUTER PDM Total Wellness Package THERMASOL COM I 800 776 0711 20 20 ...

Page 21: ...f Application IMPORTANT The Digital Shower Valve must be accessible and should not be sealed in the wall TDS 3000 Digital Shower Valve Digital Interface PDM Total Wellness Package THERMASOL COM I 800 776 0711 21 ...

Page 22: ...ve System Controller 1 5 V A C C U E X T R S 2 3 2 M O T O R T L I A U X 15V ACCU TLI Hot Fixing Holes Battery Compartment Power Supply Connector Block Cold Inlets Outlets Total Wellness Package THERMASOL COM I 800 776 0711 22 22 ...

Page 23: ...7 Mark and Drill Holes 235mm 9 25 235mm 9 25 8mm 0 31 Total Wellness Package THERMASOL COM I 800 776 0711 23 ...

Page 24: ...lve System Controller 9 Remove Inlet Retaining Bolt 1 5 V A C C U E X T R S 2 3 2 M O T O R T L I A U X 1 5 V A C C U E X T R S 2 3 2 M O T O R T L I A U X Total Wellness Package THERMASOL COM I 800 776 0711 24 24 ...

Page 25: ...R T L I A U X 1 5 V A C C U E X T R S 2 3 2 M O T O R T L I A U X 1 Connect hot and cold water supply 2 Insert inlet connectors 3 re insert retaining bolt 1 5 V A C C U E X T R S 2 3 2 M O T O R T L I A U X IMPORTANT Flush the pipework before connection Total Wellness Package THERMASOL COM I 800 776 0711 25 ...

Page 26: ...X 1 5 V A C C U E X T R S 2 3 2 M O T O R T L I A U X 12 Connect Outlet Pipeworks 1 Connect outlet pipeworks 2 Insert outlet connectors 3 re insert retaining bolt IMPORTANT Flush the waterlines prior to connecting to clear any debris 1 2 3 1 3 2 Total Wellness Package THERMASOL COM I 800 776 0711 26 26 ...

Page 27: ...M O T O R T L I A U X 1 5 V A C C U E X T R S 2 3 2 M O T O R T L I A U X 1 5 V A C C U E X T R S 2 3 2 M O T O R T L I A U X 1 5 V A C C U E X T R S 2 3 2 M O T O R T L I A U X RS232 Port Connect the digital interface to the RS232 port Total Wellness Package THERMASOL COM I 800 776 0711 27 ...

Page 28: ...15 Connect The PDM 1 5 V A C C U E X T R S 2 3 2 M O T O R T L I A U X 1 5 V A C C U E X T R S 2 3 2 M O T O R T L I A U X Total Wellness Package THERMASOL COM I 800 776 0711 28 28 ...

Page 29: ... fit Cover and Connect 1 5 V A C C U E X T R S 2 3 2 M O T O R T L I A U X IMPORTANT Electrical connection must be installed by a qualified electrician Total Wellness Package THERMASOL COM I 800 776 0711 29 ...

Page 30: ...port Department In addition we ll keep you informed about your product and time to time we ll update you about new products and other company announcements Thank you from all of us at ThermaSol and we wish you many relaxing and steamy days ahead We will not sell rent or share your personal information 1958 Steam Way Round Rock TX 78665 Total Wellness Package THERMASOL COM I 800 776 0711 30 30 ...

Page 31: ...THERMASOL COM I 800 776 0711 31 ...

Page 32: ...1958 STEAM WAY ROUND ROCK TX 78665 PHONE 800 776 0711 FAX 800 556 5257 WWW THERMASOL COM 81237_NC ...

Reviews: