User Manual
3200 Series
100 Part No HA028651 Issue 11.0 July-12
Parameter
Mnemonic
Parameter Name
Modbus Address
Decimal
40 – None
41 – Acknowledge all alarms
42 – Select SP1/2
43 – Lock All Keys
44 – Timer Reset
45 – Timer Run
46 – Timer Run/Reset
47 – Timer Hold
48 – Auto/Manual Select
49 – Standby Select
50 – Remote setpoint
51 – Recipe select through IO1
52 – Remote key UP
53 – Remote key DOWN
L.SENS
Configures the polarity of the logic input channel A (0 = Normal, 1 = Inverted)
12361
L.TYPE (LB) Logic Input B channel hardware type (3208/3204 only)
0 – None
1 – Logic Inputs
12368
L.D.IN (LB) Logic input B function (3208/3204 only)
40 – None
41 – Acknowledge all alarms
42 – Select SP1/2
43 – Lock All Keys
44 – Timer Reset
45 – Timer Run
46 – Timer Run/Reset
47 – Timer Hold
48 – Auto/Manual Select
49 – Standby Select
50 – Remote setpoint
51 – Recipe select through IO1
52 – Remote key UP
53 – Remote key DOWN
12369
L.SENS (LB) Configures the polarity of the logic input channel B (0 = Normal, 1 = Inverted) (3208/4 only)
12377
ID
Comms Module Type
0 – None
1 – EIA232
2 – EIA232
3 – EIA232
4 – Remote setpoint input
12544
BAUD Baud
Rate
0 – 9600
1 – 19200
2 – 4800
3 – 2400
4 – 1200
12548
PRTY Parity
setting
0 – None
1 – Even
2 – Odd
12549
DELAY
RX/TX Delay – (0 = no delay, 1 = delay) Select if a delay is required between received and transmitted comms
messages. Sometimes required when intelligent EIA232 adaptors are used.
12550
RETRN
Comms Retransmission Variable selection:
0 – Off
1 – Working Setpoint
2 – PV
3 – Output Power
4 – Error
12551
REG.AD
Modbus register address to broadcast retransmission to. For example if you wish to retransmit the working setpoint
from one 3200 to a group of slaves, and receive the master working setpoint into the slaves’ remote setpoint, set this
variable to 26 (the address of the remote setpoint in the slave units).
12552
Ct.Id Current
Transformer
12608
CT.SRC CT
Source
0 – None
12609
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...