User Manual
3200 Series
122 Part No HA028651 Issue 11.0 July-12
17.7.4
Example 4: Display the message ‘OUT OF CONTROL’ if both Alarm 1 and Alarm 2 are active.
Operation
Action
Indication
Add a
parameter
1.
Right click where the
parameter is required
2.
Select ‘Insert Item’
3.
Choose the parameter from
the pop up box eg
‘STATUS
InstStatus’
Set the
Operator
4.
From the Operator drop
down box select
‘Mask’
See also note 1 below
Alternatively a message may be
configured to appear if the
enumeration of the parameter:-
= equals the ‘Value’
!= is not equal to the ‘Value’
> is greater than the ‘Value’
< is less than the ‘Value’
Set the value
The bitmap list
is given here
and in the
Digital Comms
chapter
5.
Click in the ‘Value’ box and
press enter
6.
From the pop up box either
tick the bit field values or
type in the decimal
equivalent in ‘New Value’.
In this example 3.
Instrument Status - Bitmap
B0 – Alarm 1 Status
B1 – Alarm 2 Status
B2 – Alarm 3 Status
B3 – Alarm 4 Status
B4 – Auto/Manual Status
B5 – Sensor Break Status
B6 – Loop Break Status
B7 – CT Low load current alarm status
B8 – CT High leakage current alarm status
B9 – Program End
B10 – PV Over-range (by > 5% of span)
B11 – CT Overcurrent alarm status
B12 – New Alarm Status
B13 – Timer/Ramp Running
B14 – Remote Fail, New Alarm
B15 – Auto-tune Status
In each case, a setting of 1 signifies ‘Active’, 0 signifies ‘Inactive’.
Set the priority 7.
From the drop down select
Low Medium or High
Enter the
message
8.
In the message section enter
OUT OF CONTROL
Download to
the controller
9.
Press <Back, Next> or Close
to download the settings
Note 1:
Mask allows any combination of parameters in the above bitmap field to activate the custom message. The
table below shows how this operates for the four alarm fields.
Value
Bitmap
Parameter (Alarm) active
1 0001
Alarm
1
2 0010
Alarm
2
3
0011
Alarm 1 + Alarm 2
4 0100
Alarm
3
5
0101
Alarm 3 + Alarm 1
6
0110
Alarm 2 + Alarm 3
7
0111
Alarm 1 + Alarm 2 + Alarm 3
8 1000
Alarm
4
Other parameters can be added by extending this table.
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...