Installation and Operation Handbook
Programmer Operation
5.6
Configuring The Programmer
Configuration defines:
•
the number of stored programs (
Multi programmer only
)
•
the holdback strategy
•
the power fail strategy
•
the servo type
•
if event outputs are available. (
Multi programmer only
)
When first installing a programmer, you should check that the configuration conforms to your requirement.
To check or change
the configuration, select Configuration level. See Chapter 6.
Programmer list header
After selecting Configuration mode, press
until the
PROG
ConF
header is
displayed.
Press
Number of programs
Use
or
to select:
•
nonE
:
Disable built-in 8-segment programmer
•
1
: Enable built-in 8-segment programmer
For 16-segment programmers:
•
nonE
: no programs
•
1
: One stored program
•
4
: Four stored programs
Press
Holdback Strategy
Use
or
to select:
•
SEG
:
Holdback type to be set in each segment
•
ProG
:
Holdback type to be set for the whole program
Press
Power fail strategy
Use
or
to select:
•
cont
: Continue from last setpoint
•
rmP.b
:
Ramp from PV to setpoint at last ramp rate
•
rSEt
: Reset the program
Continued on next page
PROG
Conf
HbAc
SEG
PtyP
4
Pwr.F
cont
HA025041 issue 12 Aug 14 5-7
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...