Configuration Installation and Operation Handbook
Name
Description
Values
Meaning
iP
Input configuration
inPt
Input type
J.tc
J thermocouple
k.tc
K thermocouple
L.tc
L thermocouple
r.tc
R thermocouple (Pt/Pt13%Rh)
b.tc
B thermocouple (Pt30%Rh/Pt6%Rh)
n.tc
N thermocouple
t.tc
T thermocouple
S.tc
S thermocouple (Pt/Pt10%Rh)
PL
2
PL 2 thermocouple
C.tc
Custom downloaded t/c (default = type C)
rtd
100
Ω
platinum resistance thermometer
mV
Linear millivolt
voLt
Linear voltage
mA
Linear milliamps
Sr
V
Square root volts
Sr
A
Square root milliamps
* See ‘
CuSt
’ List.
mV.C
8-point millivolt custom linearisation
*
V.C
8-point Voltage custom linearisation
*
mA.C
8-point milliamp custom linearisation
*
CJC
Cold Junction
OFF
No cold junction compensation
Compensation
Auto
Automatic internal compensation
0
o
C
0
o
C external reference
45
o
C
45
o
C external reference
50
o
C
50
o
C external reference
imp
Sensor Break Impedance
Off
Disabled (applies to any input)
Caution:
If sensor break is disabled the controller will not detect open circuit
faults
Auto
Factory set
Hi
Impedance of input > 15K
Ω
Hi.Hi
Impedance of input > 30K
Ω
Linear Input Scaling
−
The next four parameters only appear if a linear input is chosen.
inP.L
Input value low
inP.H
Input value high
VAL.L
Display reading low
VAL.H
Display reading high
VAL.L
inP.H
inP.L
VAL.H
Displayed Value
Electrical
Input
6-8 HA025041 issue 12 Aug 14
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...