User Calibration Installation and Operation Handbook
7.3
Offset Calibration
Offset calibration is used to apply a single fixed offset over the full display range of the controller.
To calibrate, proceed as follows:
1. Connect the input of the controller to the source device to which you wish to calibrate.
2. Set the source to the desired calibration value.
3. The controller will display the current measurement of the value.
4. If the displayed value is correct, then the controller is correctly calibrated and no further action is necessary. If
it is incorrect, then follow the steps shown below.
Select ‘
FuLL
’ access level, as described in Chapter 3.
Input list header
Press
until you reach the input list header.
Press
until you reach the
‘
CAL
’
display.
Calibration type
•
FACt
:
Factory Calibration
•
USEr
:
User Calibration
Use
or
to select ‘
FACt
’.
Selecting ‘
FACt
’ reinstates the factory calibration and allows the application of
a single fixed offset.
Press
Set Offset 1
Use
or
to set the offset value of Process Value 1 (PV1).
The offset value is in display units.
Press
The following table shows the parameters which appear after ‘
OFS.1
’. These
are all read only values and are for information.
Displayed Value
Input
Factory Calibration
Fixed Offset
Continued on next page
IP
List
CAL
FACt
OFS.1
0
7-2 HA025041 issue 12 Aug 14
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...