Installation and Operation Handbook Load Current Monitoring and Diagnostics
8.8
To Configure Low and High Current Trip Alarms
Alarm 1 will be configured as Load Current Low (
Lcr
)
Alarm 2 will be configured as Load Current High (
Hcr
)
Do This
This Is The Display You Should See
Additional Notes
Press
button until the
AL Conf
is displayed
This opens the configuration list which
contains the Alarms
Press
to show
AL1
(alarm 1)
Press
or
to show
LCr
To select alarm 1
To make alarm 1 = Low Current
Press
until
AL2
(alarm 2)
appears
Press
or
to show
HCr
After 0.5 sec the
display will blink to
show the alarm type
has been accepted
To select alarm 2.
To make alarm 2 = High Current
8.9
TO ATTACH SOFT ALARMS TO A RELAY OUTPUT
Any one alarm indicated above may be attached to an output (normally a relay). Alternatively any combination of
alarms may be attached to operate a relay using the procedure below:-
Do This
This Is The Display You Should See
Additional Notes
Press “PAGE” key
as many
times as necessary to
3A ConF
Any output module can be configured for
an alarm output provided it is not used
for any other purpose, eg as a control
output.
In place of
3A
you should select the
module required, i.e.
1A
or
2A
Press
until
1---
is displayed
Press
or
to select
YES
or
Repeat the above step for every alarm
to be attached to the output
1----
denotes alarm
1
followed by three
letters which denote
the alarm type e.g.
LCr
yes
means that the selected output will
activate when an alarm occurs in normal
operation
no
means the output will not activate
i
Note:
The above alarms are known as SOFT ALARMS because they are indication only.
3A
Conf
AL
Conf
AL1
LCr
1---
yes
AL2
HCr
Alarms Connected to a
Relay Output
dIG
SEnS
nor
inv
Output
Module
Soft
Alarms
OR
3A
3B
HA025041 issue 12 Aug 14 8-7
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...