Installation and Operation Handbook Ordering Code
-
Hardware coding
Part 2: Configuration
►
Continued
Sensor input
Range min
Range max
Units
Options
K
0
1000
C
CF
i
Note:
PDSIO is a proprietary technique developed by Eurotherm for bi-directional transmission
of analogue and digital data between instruments.
Mode 1: provides logic heating to a Eurotherm TE10S solid state relay with feedback of
a general load fault alarm.
Mode 2: provides logic heating to a Eurotherm TE10S solid state relay with feedback of
load current and two alarms: solid state relay failure and heater circuit failure.
Sensor input
Range min &max
Standard sensor inputs
°
C
°
F
J
J thermocouple
-210 to 1200
-340 to 2192
K
K thermocouple
-200 to 1372
-325 to 2500
T
T thermocouple
-200 to 400
-325 to 750
L
L thermocouple
-200 to 900
-325 to 650
N
N thermocouple
-250 to 1300
-418 to 2370
R
Type R - Pt13%Ph/Pt
-50 to 1768
-58 to 3200
S
Type S - Pt10%Rh/Pt
-50 to 1768
-58 to 3200
B
Type B - Pt30%Rh/Pt6%Rh
0 to 1820
32 to 3308
P
Platinel II
0 to 1369
32 to 2496
C
*Type C W5%Re/W26%Re
(Hoskins)*
0 to 2319
32 to 4200
Z
RTD/PT100
-200 to 850
-325 to 1562
Process inputs
F
-9.99 to + 80mV
0 to 9999
Y
0-20 mA Linear
0 to 9999
A
4-20 mA Linear
0 to 9999
W 0-5V DC Linear
0 to 9999
G
1-5V DC Linear
0 to 9999
V
0-10V DC Linear
0 to 9999
Custom Sensor inputs (* replaces type C thermocouple)
D
Type D - W3%Re/W25%Re
0 to 2399
32 to 4350
E
E thermocouple
-270 to 1000
-450 to 1830
1
Ni/Ni18%Mo
0 to 1399
32 to 2550
2
Pt20%Rh/Pt40%Rh
0 to 1870
32 to 3398
3
W/W26%Re (Englehard)
0 to 2000
32 to 3632
4
W/W26%Re
(Hoskins)
0 to 2010
32 to 3650
5
W5%Re/W26%Re
(Englehard)
10 to 2300
50 to 4172
6
W5%Re/W26%Re
(Bucose)
0 to 2000
32 to 3632
7
Pt10%Rh/Pt40%Rh
200 to 1800
392 to 3272
Range min and Range max:
Thermocouple and RTD sensor inputs will
always display over the full operating range shown in Sensor input table.
For these inputs, the values entered here are the low and high setpoint
limits. For process inputs, the values are the display scaling
corresponding to the minimum and maximum input values.
Options
Add as many options as required
Control options
NF
On/Off control
DP
Direct acting PID control
PD
Power feedback disabled
Cooling options
CF
Fan cooling
CW
Water cooling
CL
Oil cooling
Front panel buttons
MD
Auto/man button disabled
RD
Run/hold button disabled
Programmer options
HD
Dwell time in hours
HR
Ramp rate in units/hour
(minutes is standard)
Units
C
Centigrade
F
Fahrenheit
K
Kelvin
X
Blank
HA025041 issue 12 Aug 14 A-3
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...