User Manual
3200 Series
24 Part No HA028651 Issue 11.0 July-12
Mnemonic
Scrolling Display and description
Range
WKG.SP
WORKING SETPOINT
is the active setpoint value and appears when the
controller is in Manual mode. It may be derived from SP1 or SP2, or, if the
controller is ramping (see SP.RAT), it is the current ramp value.
SP.HI to SP.LO
WRK.OP
WORKING OUTPUT
is the output from the controller expressed as a percentage
of full output. It appears when the controller is in Auto mode.
In a motorised valve controller (option VC or VP) this is the ‘inferred’ position of
the valve
For a time proportioning output, 50% = relay or logic output on or off for equal
lengths of time.
For On/Off control: OFF = <1%. ON = >1%
Read only value
0 to 100% for heating
0 to –100% for cooling
-100 (max cooling) to 100%
(max heating
T.STAT
TIMER STATUS
is the current state of the timer: Run, Hold, Reset or End
It is only appears when a timer is configured.
rES
Reset
run
Running
hoLd
Hold
End
Timed out
UNITS
DISPLAY UNITS
Temperature display units. ‘Percentage’ is provided for
linear inputs
O
C
Degrees C
O
F
Degrees F
O
k
Degrees K
nonE
None
PErc
Percentage
SP.HI
SETPOINT HIGH
High setpoint limit applied to SP1 and SP2.
Alterable between range limits
SP.LO
SETPOINT LOW
Low setpoint limit applied to SP1 and SP2
By default the remote setpoint is scaled between SP.HI and SP.LO. Two further parameters (REM.HI and REM.LO) are
available in access level 3 to limit the Remote SP range if required. See section 10.1.
SP1
SETPOINT 1
allows control setpoint 1 value to be adjusted
Alterable: SP.HI to SP.LO
SP2
SETPOINT 2
allows control setpoint 2 value to be adjusted
Alterable: SP.HI to SP.LO
SP.RAT
SETPOINT RATE LIMIT
Rate of change of setpoint value.
OFF to 3000 display units per
minute
The next section applies to the Timer only
– see also section 5.4.
TM.CFG
TIMER CONFIGURATION
Configures the timer type:- Dwell, Delay, Soft Start or
none. The timer type can only be changed when the timer is reset.
The Programmer option only appears if the programmer has been ordered.
none
None
Dwel
Dwell
DeLy
Delayed switch on
sfst
Soft start
Prog
Programmer
TM.RES
TIMER RESOLUTION
Selects the resolution of the timer. This can only be
changed when the timer is reset.
Hour
min
Hours
Minutes
THRES
TIMER START THRESHOLD
The timer starts timing when the temperature is
within this threshold of the setpoint. This provides a guaranteed soak
temperature. The threshold can be set to OFF in which case it is ignored and
the timing starts immediately.
If a setpoint ramping is set, then the ramp completes before the timer starts.
OFF or 1 to 3000
END.T
TIMER END TYPE
This determines the behaviour of the timer when it has timed
out. This value can be changed while the timer is running.
OFF
Control OP goes to
zero
Dwel
Control continues at
SP1
SP2
Go to SP2
res
Reset programmer
SS.PWR
SOFT START POWER LIMIT
This parameter only appears if the timer
configuration is set to
sfst
(Softstart). It sets a power limit which is applied
until the measured temperature reaches a threshold value
(SS.SP)
or the set
time
(DWELL)
has elapsed. The timer starts automatically on power up.
-100 to 100%
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...