3200 Series
User Manual
Part No HA028651 Issue 11.0 July-12 33
6.1.3
To Select Access Level 3 or Configuration Level
Do This
The Display You Should See
Additional Notes
1.
From any display press and hold
for more than 5 seconds
To Select Level 3
Lev 3
go to
0
CODE
The display will pass from the current operating level, for
example,
Lev 1
to
Lev 3
as the button is held down.
(If no button is then pressed for about 50 seconds the display
returns to the HOME display)
2.
Press
▲
or
▼
to enter the
passcode for Level 3
3
code
The default code is 3:
If an incorrect code is entered the display reverts to ‘
g o t o
’
.
The controller is now in the level 3 will then revert to the
HOME display
3.
When the
LEV3
GO TO
view is
shown, as in paragraph 1 above,
press
▲
to select ‘
Conf
’
To Select Configuration level
Conf
go to
0
CODE
Note:
▲
must be pressed quickly before the controller
requests the code for level 3
4.
Press
▲
or
▼
to enter the
passcode for Configuration level
4
code
Conf
The default code is 4:
If an incorrect code is entered the display reverts to
‘
g o t o
’
.
The controller is now in Configuration level will now show
Conf
5.
Press and hold
for more than 3
seconds
6.
Press
▲
to select the required
level eg
LEV 1
To Return to a Lower Level
Conf
go to
Lev1
go to
The choices are:
LEV 1
Level 1
LEV 2
Level 2
LEV 3
Level 3
C o n F
Configuration
It is not necessary to enter a code when going from a higher
level to a lower level.
Alternatively, press
and scroll to the
A c c e s
list
header, then press
to select the required level.
The display will then flash ‘
ConF
’ for a few seconds and the
controller will then go through its start up sequence, starting
in the level selected.
Do not power down while
Conf
is flashing. If a power down
does occur an error message will appear – see section
12.4
‘Diagnostic Alarms’
☺
A special case exists if a security code has been
configured as ‘0’. If this has been done it is not
necessary to enter a code and the controller will enter
the chosen level immediately.
☺
When the controller is in configuration level the
ACCESS list header can be selected from any view by
holding down the
button for more than 3 seconds.
Then press
again to select ‘ACCES’
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...