User Manual
3200 Series
46 Part No HA028651 Issue 11.0 July-12
9.1.2
Remote Digital Setpoint Select and
Remote Fail
These parameters were added in software version 1.11,
and subsequent versions, and are associated with the
retransmission of remote setpoint through master
comms (see section 15.2.1). ‘
rmt
’ allows the remote
setpoint to be selected via a digital input and ‘
rmt.F
’ is a
flag which is set if no comms activity is detected for 5
seconds or more when writing to the remote setpoint.
The flag is reset when writing to the remote setpoint
resumes.
9.1.3
Sense
If the module is an output, ‘normal’ means a relay output
is energised for 100% PID demand. For a heating or
cooling output, set this parameter to ‘
nor
’.
‘Inverted’ means a relay output is energised for 0% PID
demand
For an alarm output set this parameter to ‘
Inv
’ so that
it de-energises to the alarm state.
If the module is an input, ‘normal’ means the function is
activated when the input contact is closed, and ‘inverted’
means the function is activated when the input contact is
open.
9.1.4
Source
The four parameters SOURCE A, SOURCE B, SOURCE C,
and SOURCE D appear when the output is configured as
a digital output i.e. ‘-
.FUNC
’ = ‘
d.Out
and provide the
facility to connect up to four alarms or events to operate
a single output (normally configured as a relay). If any
one of the events becomes true then the output relay
will operate.
9.1.5
Power Fail
An output, configured as a digital output, can be made
to operate following a power fail. It can be
acknowledged in the same manner as an alarm but no
alarm message is given.
9.1.6
Example: To Configure IO-1 Relay to
Operate on Alarms 1 and 2:-
Do This
Display
Additional Notes
1.
From any
display, press
as
many times as
necessary to select
‘I O -1’
Scrolling display
‘
i o -1 l is t
’
2.
Press
to
scroll to ‘1.I D ’
This is the
identification of the
hardware fitted and
cannot be adjusted.
3.
Press
to
scroll to
‘1. F U N C ’
4.
Press
▲
or
▼
to select
‘
d.out
The output is
configured as a digital
output function.
Scrolling display ‘
i o
1 fu n c t i o n
’
5.
Press
to
scroll to ‘1.S RC .A ’
6.
Press
▲
or
▼
to select the
event which you want
to operate the
output, eg ‘
AL.1
The output will
activate if either
alarm 1 or alarm 2
occur .
Scrolling display ‘
i o
1 s o u rc e a
’
7.
If a second
event is required to
operate the same
output, press
to
select ‘1.S RC .B ’
8.
Press
▲
or
▼
to select the
second event which
you want to operate
the output, eg
‘
AL.2
Scrolling display ‘
i o
1 s o u rc e b
’
Continue to select up
to four events if
required using
1.S R C . C
and
1. S R C . D
9.
Press
to
scroll to ‘1
.S E NS ’
10.
Press
▲
or
▼
to select ‘
Inv
’
‘Inverted’ means a
relay output is
energised for 0% PID
demand
‘Normal’ means a
relay output is
energised for 100%
PID demand
Scrolling display ‘
io
1 s e n s e
’
OR
SEnS
Output
(relay)
Nor
Inv
SRC.A
SRC.B
SRC.C
SRC.D
reLy
1. id
d.out
1. fu n c
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...