3200 Series
User Manual
Part No HA028651 Issue 11.0 July-12 47
9.1.7
Output List 2 (OP-2)
This is an optional normally open relay or logic output and is available on terminals 2A and 2B. The way in which this
output operates is determined by parameters in the OP- 2 List. OP2 beacon is operated from this output channel.
OUTPUT LIST 2 ‘
op -2
’
Name
Scrolling
Display
Parameter Description
Value
Default
Access
Level
2. i d
OUTPUT 2
TYPE
Output channel 2 hardware
type
nonE
Output not fitted
As
ordered
Read only
reLy
Relay output
L.OP
Logic output (3200 only)
dC.Op
0-20mA output - non-isolated. See
note 1
dc.rT
0-20mA output - isolated.
This parameter appears in 3216
controllers only when an
isolated output is fitted (order
code C)
SSR
Triac output
2.FUNC
FUNCTION
Output channel 2 function
If the instrument is ordered
as valve positioner (codes VC
or VP), only options available
are ,
none
,
d.out
,
UP
, or
dwn
Note: If output 2 is set to
Up
ensure the other valve
position output is set to
dwn
and vice versa
none
Disabled. If disabled no further
parameters are shown
d.out
Conf
d.out
Digital output
UP
Valve open codes VC and VP only
dwn
Valve close codes VC and VP only
Heat
Heat output
CooL
Cool output
w.SP
Working setpoint re-transmission
Shown if I/O 2 TYPE =
dc.OP
Retransmission
PV
Process variable re-transmission
OP
Output power demand re-transmission
2.SRC.A
I/O 2 SOURCE
A
These parameters only
appear when the channel
function is a Digital OP,
i.e. 2.FUNC =
d.Out
Selects an event status to be
connected to the output
channel.
The output status is the
result of an OR of Src A, Src
B, Src C, and Src D
Up to four events can,
therefore, operate the
output
See section 9.1.4.
none
No event connected to the output
none
Conf
AL1
Alarm 1 *
2.SRC.B
I/O 2 SOURCE
B
AL2
Alarm 2 *
AL3
Alarm 3 *
2.SRC.C
I/O 2 SOURCE
C
AL4
Alarm4 *
ALL.A
All alarms
2.SRC.D
I/O 2 SOURCE
D
nw.AL
Any new alarm
Ct.AL
CT alarm, load, leak & overcurrent
Lbr
Loop break alarm
Sbr
Sensor break alarm
t.End
Timer end status
t.run
Timer run status
mAn
Manual status
rmt.F
Remote fail - see section 9.1.2
Pwr.f
Power fail
prg.e
Programmer event. See also section
13.2.3.
2.PLS
OUTPUT
MINIMUM
PULSE TIME
Minimum output on/off
time.
Only applies to time
proportioning outputs and
prevents relays from
switching too rapidly
0.0
to
150.0
Auto or 1.0 to 150.0 seconds
Auto = 110mS
5.0 sec
for relay
Auto for
logic
Conf
2.SENS
SENSE
To configure the polarity of
output channel 2
See also section 9.1.3
nor
Normal
nor
Conf
Inv
Inverted
2 . rn g
DC OUTPUT
RANGE
To configure 0-20mA or 4-
20mA output
Only appears if the output
module is DC output
0.20
0-20mA output
L3
4.20
4-20mA output
* The mnemonic for the alarm will change depending upon the alarm configuration.
Note 1:- A DC output may require calibration. This is described in section 16.3.4
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...