3200 Series
User Manual
Part No HA028651 Issue 11.0 July-12 65
11.3.6
Autotune From Below SP – Heat Only
The sequence of operation for a heat only loop is the same as that previously described for a heat/cool loop except that
the sequence ends at ‘F’ since there is no need to calculate ‘R2G’.
At ‘F’ autotune is turned off and the process is allowed to control using the new control terms.
Relative cool gain, ‘
R2G’
, is set to 1.0 for heat only processes.
For a tune from below setpoint
‘CBLO’
is calculated on the basis of the size of the overshoot (assuming it was not set to
Auto in the initial conditions). CBHI is then set to the same value as CBLO.
Note:- As with the heat/cool case, Autotune can also occur when the initial PV is above SP. The sequence is the same as
tuning from below setpoint except that the sequence starts with natural cooling applied at ‘B’ after the first one minute
settling time.
In this case CBHI is calculated – CBLO is then set to the same value as CBHI.
E
A – B = 1 min.
C
D
F
First
overshoot
Target Setpoint
PV
Tune Control Point
High Output
Zero Output
Peak to
Peak
Hysteresis
F - End of
Autotune
D to F -
calculate
PID
C to D -
calculate CBL
A - Start of
Autotune
B
Summary of Contents for XST-2-0-12-1V1-E28
Page 16: ...12 FURNACE TROUBLE SHOOTING ...
Page 27: ...ɸ ...
Page 28: ...ɸ ...
Page 29: ......
Page 30: ......
Page 31: ...3216 3208 3204 User Manual 3200 Range Process Controller HA028651 11 Aug 2012 ...
Page 170: ...User Manual 3200 Series 138 Part No HA028651 Issue 11 0 July 12 21 Certificate of Conformity ...
Page 171: ......
Page 173: ...Model 2416 Process Controller User Manual Part No HA025041_12 Date August 2014 ...
Page 174: ...This page is intentionally blank ...
Page 259: ...This page is intentionally blank ...