background image

 

DTH Electric Boilers USE & CARE MANUAL 

(Revision June 2014)

,  Page 

8.

 

3.4.7 Circulator zoning recommendations

 

The preferred location of the circulator pump for 
each zone is on the boiler supply side, with the 
expansion tank between the boiler and the 
pump. 
 
A flow check valve must be installed in each 
zone, preferably on the outlet side of each 
circulator pump, to prevent water flow to other 
zones where no heat is required. 
 

3.4.8 Zone valve zoning 
recommendations 

The preferred location of the circulator pump is 
on the boiler supply side, with the expansion 
tank between the boiler and the circulator.  Use 
zone valves with low pressure drop.  

 
3.4.9 Pump & pipe sizing 

 
3.4.9.1 Boiler water temperature drop (BWTD) 
through the heating loop 
A simplified design method based on a 20°F 
temperature drop (BWTD) between boiler outlet 
and inlet is commonly used.  Although such a 
method is widely used and generates 
satisfactory system performance when applied 
properly, it does not determine the system 
operating point.  The pipe size is often 
uneconomically large, and the actual system 
flow rate is likely to be much higher than 
intended.  Such design methods seldom 
consider temperature drops higher than 20°F, 
which results in overdesign. 
 
Another method by which the boiler water 
temperature drop  (BWTD) could be calculated 
is to assume a constant supply boiler water 
temperature minus the return boiler water 
temperature.   For example a boiler might have 
a return temperature of 140 °F.  Assuming a 
constant supply boiler temperature of 180 °F, 
the BWTD would be 40 °F ( = 180 °F – 140 °F).  
Second example: If the boiler water has a return 
temperature of 120 °F and the boiler supply is at 
140 °F, then the temperature drop is 20 °F 
(=140 °F – 120 °F). 
 
The following table suggests temperature drops 
(BWTD) to be used in calculating the pump flow 
rate. 
 
 
 
 

 
Table 5: Temperature rise through the boiler 

 

PROPOSED BOILER WATER 

TEMPERATURE RISE THROUGH THE 

BOILER  (BWTD) 

 

 

System 

type 

Boiler  

water  

Supply 

tempera-

ture 

Boiler 

water  

Return 

tempera-

ture 

BWTD 

Baseboards 

190°F to 

140°F 

170°F to 

120°F 

20°F to 

40°F 

Cast Iron 

Radiators 

160°F to 

130°F 

140°F to 

110°F 

20°F to 

40°F 

Radiant  
In-Floor 

130°F to 

90°F 

110°F to 

70°F 

10°F to 

20°F 

 
3.4.9.2 Pump flow rate calculation 
The boiler output rating must correspond to the 
calculated heating load.  Use the equation below 
to calculate the pump flow rate. 
 
  

Pump flow rate = Boiler output 

÷÷÷÷

 

BWTD 

÷÷÷÷

 500 

 

 

Pump flow rate is expressed in US gallons 
per minute or GPM. 

 

The Boiler output ( in net BTU per hour) is 
the maximum amount of heat to be 
transferred through the heating loop to meet 
the heating load. 

 

BWTD is the boiler water temperature drop  

 

 
For example, an electric boiler rated at 144KW 
has a power output of 491,328 BTU per hour.  
The system is designed for a temperature drop 
(BWTD) of 20°F. 
 
Required pump flow rate = 491,328 

÷

 20 

÷

 500 = 

49.1 GPM 
 
The following table lists the required pump flow 
rate as a function of  boiler power and BWTD. 
 
 
 
 
 

Summary of Contents for DTH 102

Page 1: ...proper installation operation and maintenance of this product It is imperative that all persons who are expected to install operate or adjust this electric boiler should read these instructions carefully to fully understand how to do so Any questions regarding the operation maintenance service or warranty of this electric boiler should be directed to the supplier When all installation steps have b...

Page 2: ...6KW 14 14 14 4 3 DTH 90 90 375 15 X 6KW 15 15 15 4 3 DTH 96 96 400 16 X 6KW 16 16 16 4 3 Table 2 Electric Ratings for 480 VAC 3 phases Electric Boilers Model P Kw Current Amp Élements 277V Stages Aquastats Lights Power contactors Secondary contactors Sequencers DTH 45 45 54 9 X 5KW 3 3 3 2 3 1 DTH 54 54 65 9 X 6KW 3 3 3 2 3 1 DTH 60 60 72 12 X 5KW 4 4 4 2 4 1 DTH 72 72 87 12 X 6KW 4 4 4 2 4 1 DTH ...

Page 3: ... 5Kw 6 6 6 3 6 2 DTH 108 108 104 18 x 6 KW 6 6 6 3 6 2 DTH 120 120 115 24 X 5KW 8 8 8 4 8 3 DTH 132 132 127 12 X 5KW 12 X 6KW 8 8 8 4 8 3 DTH 144 144 139 24 X 6KW 8 8 8 4 8 3 Table 4 Connections sizes Boiler overall dimensions Connections sizes Boiler overall dimensions Boiler inlet 2 NPT M Height 33 po Boiler outlet 2 NPT M Depth 46 po Waterworks 1 2 NPT M Width 22 po Safety valve 3 4 NPT F Shipp...

Page 4: ...DTH Electric Boilers USE CARE MANUAL Revision June 2014 Page 4 Figure 1 Component identification ...

Page 5: ...on In any case where instructions in this manual differ from local or national codes the local or national codes take precedence 2 2 CORROSIVE ATMOSPHERE The electric boiler should not be located near an air vent containing a corrosive atmosphere or high humidity The limited warranty is void when the failure of the electric boiler is due to a corrosive atmosphere 2 3 SHIPMENT INSPECTION Inspect th...

Page 6: ... to physical damage for example by moving vehicles area flooding etc All models can be installed on combustible floors and in alcoves Ambient temperature must not exceed 80 F or 27 C 3 3 CLEARANCE Minimum clearances for adequate inspection and servicing are listed in the following table Table 4 Boiler clearance Left side 14 inches Right side 14 in 78to144kW 480 600v 54to96kWx 240v 0in Other models...

Page 7: ...um allowable pressures and maintain minimum pressure for all normal operating temperatures They also allow air bleeding prevent cavitation at the pump inlet and prevent water from boiling within the system all this is accomplished with minimal addition of new water The increase in boiler water volume resulting from higher temperature is stored in the expansion tank during periods of high operating...

Page 8: ...perature minus the return boiler water temperature For example a boiler might have a return temperature of 140 F Assuming a constant supply boiler temperature of 180 F the BWTD would be 40 F 180 F 140 F Second example If the boiler water has a return temperature of 120 F and the boiler supply is at 140 F then the temperature drop is 20 F 140 F 120 F The following table suggests temperature drops B...

Page 9: ...it of 4 feet per second for 2 inch pipe and smaller and a pressure drop limit of 4 feet of water per hundred feet for piping over 2 inches These limitations are imposed either to control the levels of pipe and valve noise erosion and water hammer pressure or for economic reasons Please note that in the smaller pipe sizes this velocity limit permits the use of friction loss rates higher than 4 feet...

Page 10: ...e valve will power the boiler pump upon opening fully See figure 7 for more details If the heating system is set up to use only a single pump then to minimize flow by gravity heat loss during non draw periods a flow check must be installed 3 7 CONNECTING THE THERMOSTAT The thermostat shall not be connected directly on the boiler Its function is to activate the circulating pump s to bring cold retu...

Page 11: ... DTH boiler is equipped with an external terminal block facilitating the connection between the two units In Oil Mode The CBE EM dual energy control will start up the oil burner upon receiving a demand signal It will shut off when the temperature in the boiler reaches its target on the Limit Control or when the heat demand has been satisfied In Electric Mode the electric boiler is activated and wi...

Page 12: ...DTH Electric Boilers USE CARE MANUAL Revision June 2014 Page 12 Figure 2 Wiring diagram DTH 96KW 240V ...

Page 13: ...DTH Electric Boilers USE CARE MANUAL Revision June 2014 Page 13 Figure 3 Wiring diagram DTH 144KW 480V ...

Page 14: ...DTH Electric Boilers USE CARE MANUAL Revision June 2014 Page 14 Figure 4 Wiring diagram DTH 144KW 600V ...

Page 15: ...W CHECK VALVE REQUIRED ON SYSTEMS WITHOUT MOTORIZED ZONE VALVES CLAPET ANTI GRAVITÉ REQUIS SUR SYSTÈME N AYANT PAS DE ROBINETS MOTORISÉS 14 HOT WATER BASEBOARD PLINTHES CHAUFFAGES 13 MOTORIZED ZONE VALVE ROBINETS MOTORISÉS 10 TEMPERATURE AND PRESSURE GAUGE THERMOMANOMÈTRE 1 MAIN WATER SUPPLY ALIMENTATION D EAU 2 MAINTENANCE VALVE VALVE D ENTRETIEN 3 CHECK VALVE CLAPET ANTI RETOUR 4 PRESSURE REDUCE...

Page 16: ...MAINTENANCE VALVE VALVE D ENTRTIEN 3 CHECK VALVE CLAPET ANTI RETOUR 4 PRESSURE REDUCER RÉDUCTEUR DE PRESSION 5 EXPANSION TANK RÉSERVOIR DE DILATATION 6 CIRCULATING PUMP POMPE RECIRCULATION 7 PURGE VALVE ROBINET D ÉLIMINATION D AIR 8 DRAIN VALVE VALVE DE DRAINAGE 11 AUTOMATIC AIR VENT PURGEUR D AIR 9 SAFETY VALVE SOUPAPE DE SÛRETÉ 12 SUPPLY HEADER COLLECTEUR D ALIMENTATION 14 RADIANT IN FLOOR PIPIN...

Page 17: ...ALIMENTATION D EAU 2 MAINTENANCE VALVE VALVE D ENTRETIEN 3 CHECK VALVE CLAPET ANTI GRAVITÉ 4 PRESSURE REDUCER RÉDUCTEUR DE PRESSION 5 EXPANSION TANK RÉSERVOIR DE DILATATION 6 CIRCULATING PUMP POMPE RECIRCULATION 8 DRAIN VALVE VALVE DE DRAINAGE 9 SAFETY VALVE SOUPAPE DE SÛRETÉ 7 PURGE VALVE ROBINET D ÉLIMINATION D AIR 10 TEMPERATURE AND PRESSURE GAUGE THERMOMANOMÈTRE LEGEND 15 INJECTION VALVE SLOW ...

Page 18: ...diagram pump thermostat Diagramme électrique Wiring diagram Raccordement de pompe DTH Wiring pump for DTH Relais de pompe pump relay T T 1 2 3 4 L2 L1 Pompe Pump jumper Thermostat Relais Relay RA89A 120Vac Fig 8 1 Heating systems with pumps Fig 8 2 Heating systems with zone valves ...

Page 19: ...ur Wiring by others H H V1 V2 V3 E1 E2 Valve 3 voies optionnelle Optional 3 way valve Contact externe External contact Lumière haut tarif High tarif light Transfo 120 Vac 24 Vac Interrupteur DPDT Switch ON OFF ON Bi energie Dual energy Electrique Electric Mazout Oil DPST Relais Relay Chaudière mazout Oil boiler T T relais de combustion oil boiler burner DPST Relais Relay T6 T5 Relais Pompe Externe...

Page 20: ... been done Safety and energy conservation are factors to be considered when setting the boiler water temperature using the aquastats The most energy efficient operation will result when the temperature setting of each aquastat is the lowest that satisfies the heating needs Please refer to table 5 for more details Each aquastat controls one stage in the 240V model each electric element has it own a...

Page 21: ...lish an heating demand from the distribution system 8 The circulator should start 9 The elements should turn on in sequence as the boiler water temperature drops below the aquastat set points This could take many minutes 10 The circulator stays on for as long as there is a demand for heating 11 When the circulator turns off temperature inside the boiler should increase Elements and pilot lights sh...

Page 22: ...e the cause of the high pressure and have it corrected rapidly Do not plug the outlet of this valve if a dripping condition occurs 5 3 AIR PURGE Twice a yeat Check for proper operation of the automatic air purgers and activate manual air vents to eliminate air present 5 4 ELECTRIC INSPECTION Annually It is recommended to perform a visual inspection of the boiler electric compartment annually durin...

Page 23: ...Temperature pressure indicator 3 Indicating lamp 4 Hi limit temperature control 5 Operating temperature control aquastat 6 heating element see table 1 7 Power contactor 8 Main supply terminal block 9 Fuse holder controls 10 Main power fuse holder 11 Transformer 12 Sequencer 13 Secondary power relay 3 5 6 7 9 10 11 12 8 2 4 13 9 3 3 ...

Page 24: ...ons resulting from installation repair maintenance and or usage that are not done in conformity with the manufacturer s installation manual or 2 Defects or malfunctions resulting from installation maintenance or repair that are not done in accordance with regulations in force or 3 Defects or malfunctions resulting from improper installation maintenance or repair done carelessly or resulting from c...

Reviews: