VOLTMAX ELECTRIC BOILER Installation and Operation Manual
(
Revised June 2017)
, Page
47.
4.4.1 WEBSITE
In order to access the boiler remotely via the
internet, the boiler controller must be correctly
connected.
The web portal has 3 main menus, the
User
,
Installer
and
Manufacturer
menu. The structure
of the web portal is the same as the controller;
please refer to the previous sections, if you have
any questions.
Ex: The user can obtain information concerning
the boiler status, in the menu Operations /
N.B. The password to acces the installater
section of the website is
1111
. He is
independent of the boiler password.
4.4.2 EMAIL
In order to configure the alarm by e-mail, you
must:
1. You must first ensure that you enter the
correct
information
in
the
controller
(depending on your network) under the
following options:
a. IP address
b. Default Gateway
c. Subnet mask
d. Primary DNS
e. Secondary DNS
You must restart the device for the changes
to take place.
2. Access the Boiler Web Portal.
3. Click on the Installer / Communication
menu.
4.
Enter your e-mail under Recipient. You can
also use your own mail server by entering
the necessary data.
5. Then select the types of alarms you want to
receive by e-mail.
If you want to send alarms to different e-mail
addresses, simply enter a list of e-mails.
Personal Email Server (Type: Gmail)
The M171 controller does not support SSL
encryption. Thus, your SMTP Email server must
accept an unencrypted connection.
Internet service providers usually have a specific
server
that
accepts
connections
without
encryptions. On-line messaging services, such
as Hotmail, G-mail, do not accept unencrypted
communications. In order to work around the
problem, there are relay services such as
SMTP2GO: https://www.smtp2go.com, to relay
between controller communication and your
messaging system. This service is free for up to
1000 emails per month.