Thermo Dynamic water heater & central heating booster
www.elitetdch.com
ELITE TDCH Aug 2014v3 Page
20
of
26
Trouble shooting cont.
Water escaping from the
tank
Codensation
Check that there is no blockage in the condensate tray or
condensate drip hose
Water leak
Check that none of the piping / connexions are leaking
Check the pressure and temperature relief valve
discharge is not causing the water leak
Compressor working
intermitantly
Power source
Check eletrical plug is in the socket correctly
Cable is not in tension
Drip tray and hose inspection clearing procedure
1. Switch off electrical power supply to the unit
2. Remove the four retaining screws in the top of the unit
3. Remove lid
4. Inspect the drip tray to see if there is excess water flowing over the tray
5. If so remove the drip pipe connexion from the rear of the unit ( use a container to catch
any water) Fig A
6. If the drip tray drains then there is a blockage in the drip pipe, call your installer
7. If the tray does not drain there is a blockage in the drip tray or internal drip pipe Fig B
8. This can be cleared by inserting a wire rod e.g.a wire coat hanger ,into the internal drip
pipe and out through the tray outlet Fig C
9. Remove any debris.
10. Re install drip pipe connector
11. Re install lid and attach with the four screws
12. Switch unit back on.
External drip pipe connextion Fig A