Loading and Enroute Inspections
139
Enroute Inspections
Complete the following enroute inspection every four hours.
This will help minimize temperature related problems.
Inspection Procedure
1.
Verify setpoint is correct.
2.
Check the return air temperature reading. It should be
within the desired temperature range.
3.
Initiate a manual defrost cycle after each enroute
inspection.
Inspection Troubleshooting
1.
If a temperature reading is not within the desired
temperature range, refer to the troubleshooting table on the
following pages. Correct problem as required.
2.
Repeat the Enroute Inspection every 30 minutes until the
compartment temperature is within the desired
temperature range. Stop the unit if the compartment
temperature is not within the desired temperature range on
two consecutive 30 minute inspections, especially if the
compartment temperature appears to be moving away
from the setpoint.
3.
Immediately contact the nearest Thermo King Service
Center or your company office.
4.
Take all necessary steps to protect and maintain proper
load temperature.
CAUTION: Stop the unit if the compartment
temperature remains higher than the desired
temperature range from the setpoint on two
consecutive 30 minute inspections. Contact the
nearest Thermo King Service Center or your
company office immediately. Take all necessary steps
to protect and maintain proper load temperature.