All installations and services must be performed by qualified service personnel.
18
OL6F/RA072DV5
Cooling Speed Set-ups
NOTE: Electrical data provided for Ultratech motor
Furnace Motor Current
Draw (Amps / Watts) vs.
External Static Pressure (in W.C)
Fan
Contr ol
SW 1
Sw itch
Se tting
Clg.
Tonnage
Cool
Continuous
0.2
0.5
6-OFF
5-OFF
4-OFF
2
799
500
1.2/100
1.9/162
6-OFF
5-OFF
4-ON
2.5
1017
508
1.8/155
2.5/223
6-OFF
5-ON
4-OFF
3
1210
605
2.5/223
3.2/298
6-OFF
5-ON
4-ON
3.5
1404
702
3.4/310
4.2/394
Factory SW1
Sw itch
Se ttings
6-ON
5-OFF
4-OFF
4
1622
799
4.7/444
5.5/535
6-ON
5-OFF
4-ON
-
1817
897
6.1/590
7.1/693
6-ON
5-ON
4-OFF
5
2010
993
7.9/789
8.8/883
Air Flow