background image

All installations and services must be performed by qualified service personnel. 

When the call for cool is satisfied, the “CC” terminal is de-energized and the cooling off delay of 45 seconds is 
started.  Forty-five seconds later the blower speed ramps toward zero and the control reverts to Standby Mode. 

Dehumidification Operation 

If a call for dehumidification is received while the Cool Mode is active, blower speeds will be reduced.  
The speed value will be selected from the DEHUM column of the CFM Tables.  This input may only be 
used on systems using a thermostatic expansion valve (TXV) on the evaporator. 

Anti-Short Cycle Operation 

To prevent compressor short cycling, a call for cooling will be ignored for four minutes after the 
termination of any cooling call.  The anti-short cycle delay is also in effect at power-up.  

Heat Mode 

When a call for heat ("W") is received from the thermostat, if the “Cool” mode is not already active, the “T-T” 
terminal is energized and the blower on delay is started.  The on-off pattern of DIP switch SW2 (positions 1 
and 2) select one of four blowers on delay values (see Table 1).  When the delay time has elapsed, a speed 
value is read from DIP switch SW1 positions 1 through 3 (see the CFM Tables) and the blower is ramped up 
to that speed.  The 2-Stage control will be operated by t-stat through W1 and W2.  For 2-stage control with a 
single stage t-stat, call for heat will go through W2.  When W2 is energized, low fire is activated for 15 
minutes.  If a call for heat still exists, high fire will be activated and will continue until the demand for heat 
has been satisfied. 

Counterflow units, in addition, will run at a low blower speed shortly after the burner is brought on.  They will 
continue at that speed until the delay time has elapsed. 

The control remains in steady heat mode until the thermostat is satisfied.  When the call for heat signal is 
removed, the “T-T” terminal is de-energized and the blower off delay is started.  The on-off pattern of DIP 
switch SW2 (positions 3 and 4) select one of four blower off delay values (see Table 1).  When the delay time 
has elapsed, the blower is ramped toward zero.

 

Table 1:

 ON and OFF Blower Delay Time Switch Settings  

DIP SWITCH 2 SECTION 
STATE 

BLOWER DELAY 

TIMES 

 

1

 

ON - SEC

 

OFF - MIN

 

 

OFF 

OFF 

 

 

30 

 

 

OFF 

ON 

 

 

60 

 

Factory Set 

ON 

OFF 

 

 

120 

 

 

ON 

ON 

 

 

240 

 

 

 

 

OFF 

OFF 

 

 

 

 

OFF 

ON 

 

Factory Set 

 

 

ON 

OFF 

 

 

 

 

ON 

ON 

 

 

 
Motor Blower Speed  

Three blower speed outputs are provided.  A “G” call for fan will provide the Low speed only.  A “W” 
heat call will provide the Heat speed only.  A “Y” cooling call will provide the Cool speed only. 
 
In the case of thermostat calls for “Y” and “W” together, blower speed selection will be determined by the 
input that was first initiated.   In the case where the control is in a cooling mode with both “Y” and “W” 
inputs energized and then the “Y” input is removed, the cooling blower off time will be executed prior to 
the control switching into a heating mode.  In the case where the control is in a heating mode with both 
“Y” and “W” inputs energized and then the “W” input is removed, the heating blower off time will be 

Summary of Contents for OL11-105FDBE

Page 1: ...DS IN THE VICINITY OF THIS OR ANY OTHER APPLIANCE INSTALLATION AND SERVICE MUST BE PERFORMED BY A QUALIFIED INSTALLER SERVICE AGENCY OR THE GAS SUPPLIER REFERRED TO IN THESE INSTRUCTIONS AS A QUALIFIE...

Page 2: ......

Page 3: ...I BLOWER CONTROL INFORMATION 1 A TERMINAL DEFINITIONS FIELD WIRING 1 B WIRING SWITCHES 2 C INPUTS 4 D OUTPUTS 4 E OPERATING MODES 5 F CFM TABLES 7 G ECM SPECIFIC REPLACEMENT PARTS 8 III ECM TROUBLESH...

Page 4: ...mostat call for heat R 24 VAC to thermostat G Thermostat call for fan Y Thermostat call for cool DEHUM Humidistat call for dehumidification TXV systems ONLY Thermostat Humidistat connections for 2 Sta...

Page 5: ...All installations and services must be performed by qualified service personnel 2 B WIRING SWITCHES OL11 OL16 LOWBOY Figure 1 BLOWER WIRING...

Page 6: ...lations and services must be performed by qualified service personnel 3 TURN OFF THE ELECTRICAL POWER to the furnace before attempting to disconnect blower wiring Figure 2 BOARD LAYOUT WITH SWITCHES B...

Page 7: ...oling is recognized when the thermostat connects Y to R This input has an indicator LED that will light when the control receives a call for cooling Refer to the Cool Mode section for the control oper...

Page 8: ...their respective thermostat connections W Y G and DEHUM and operate whenever a call is present See Diagnostic Features for a function description of operation Motor CFM LED This green LED will flash...

Page 9: ...d low fire is activated for 15 minutes If a call for heat still exists high fire will be activated and will continue until the demand for heat has been satisfied Counterflow units in addition will run...

Page 10: ...es their tabular values are enacted when their function is called Three additional dip switches select 8 heating speeds which are enacted when heat is called This allows independent selection of heati...

Page 11: ...rness 350271 350271 Transformer 350464 350464 Power Choke 350855 COOLING SPEEDS HEATING SPEEDS TEMPERATURE RISE F Rise CFM COOL LOW DEHUM 3 ON 6 OFF 2 OFF 5 OFF 1 OFF 4 OFF 3 ON 6 OFF 2 OFF 5 OFF 1 ON...

Page 12: ...servicing motor Wait at least 5 minutes after disconnecting power before opening motor SYMPTOM CAUSE PROCEDURE Motor rocks slightly when starting This is normal start up for ECM Motor won t start No...

Page 13: ...moving panel or filter reduce puffing Reduce restriction Reduce max airflow Evidence of Moisture Motor failure or malfunction has occurred and moisture is present Replace motor and perform Moisture Ch...

Page 14: ...rain plugged Check for low airflow too much latent capacity Check for undercharged condition Check and plug leaks in return ducts cabinet Comfort Check Check proper airflow settings Low static pressur...

Page 15: ...TO MOTOR IF CONNECTIONS ARE GOOD AND MOTOR STILL DOES NOT RUN REPLACE MOTOR THIS GUIDE SHOULD BE USED IN THE CASE OF A STOPPED OR MANFUNCTIONED ECM BLOWER MOTOR THE FOLLOWING SHOULD HELP ESTABLISH THE...

Page 16: ...Status LED Off 1 HEAT mode On 2 BLOWER HEAT 3 Status LED Flashes 1 COOL mode On 2 Blower On Delay Started 3 Condenser On 4 Status LED On continuous 1 FAN mode On 2 BLOWER LOW 3 Status LED On continuo...

Page 17: ...Fire Connect 2 Stage T stat to both W1 and W2 Single Stage T stat W2 Connect single stage T stat to W2 only BLOWER Speeds HEAT The Heating Blower speed selected by positions 1 2 3 of SW1 CFM tables o...

Reviews: