All installations and services must be performed by qualified service personnel.
27
OME-72D36
ALTERATIONS REQ’D FOR A/C @ DESIGN EXTERNAL STATIC PRESSURE
COOLING
UNIT
HTG Speed by Input
Recommended CLG
Speed
Low Fire
High Fire
24,000
Low
ML
Med Low
30,000
Low
ML
Med High
36,000
Low
ML
High
Speed Tap\ Static
Pressure
Furnace Airflow (CFM) vs. External Static pressure (in. WC.)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
Low
849
809
768
724
677
627
512
ML
1011
971
923
887
849
776
724
MH
1227
1200
1156
1145
1092
1004
923
High
1492
1443
1397
1354
1295
1195
1092
Blower Motor Current Draw / Power (Amps / Watts) vs. External Static pressure (in. WC.)
Low
3.2 / 309
3.2 / 310
3.0 / 297
2.9 / 292
2.8 / 285
2.7 / 280
2.6 / 271
ML
4.0 / 400
4.0 / 394
3.9 / 386
3.7 / 374
3.5 / 364
3.4 / 352
3.3 / 343
MH
4.9 / 508
4.8 / 497
4.6 / 481
4.5 / 472
4.3 / 455
4.0 429
3.8 / 415
High
5.8 / 618
5.7 / 607
5.5 / 586
5.3 / 570
5.2 / 554
4.9 / 532
4.7 / 515
Speed Tap\ Static
Pressure
High Fire Temperature Rise vs. External Static pressure (in. WC.)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
Low
80
84
88
94
100
108
132
ML
67
70
73
76
80
87
94
MH
55
56
59
59
62
67
73
High
45
47
48
50
52
57
62
Speed Tap\ Static
Pressure
Low Fire Temperature Rise vs. External Static pressure (in. WC.)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
Low
66
69
73
77
82
89
109
ML
55
57
60
63
66
72
77
MH
45
46
48
49
51
56
60
High
37
39
40
41
43
47
51
=
Recommended operation range
Summary of Contents for OME-72D36
Page 2: ......
Page 7: ...All installations and services must be performed by qualified service personnel 4a...
Page 21: ...All installations and services must be performed by qualified service personnel 18 Figure 6...
Page 34: ...All installations and services must be performed by qualified service personnel 31...
Page 53: ...All installations and services must be performed by qualified service personnel 50...
Page 54: ...All installations and services must be performed by qualified service personnel 51...
Page 55: ......