background image

Installer’s Information Manual 

 

Page 15

 

NON-DIRECT VENT TERMINATION 

You may terminate vent pipe either vertically (through the 
roof) or horizontally (through a sidewall).  Vertical (through 
the roof) venting is preferred because it offers protection 
from pipe damage and is less likely to cause condensate 
damage. 

For vertical non-direct venting, extend PVC vent pipe at 
least 12 inches above roof or average snow accumulation.  
In Canada, vent pipe must extend at least 18 inches above 
roof.  See Figure 15. 

 

Figure 15.  Vertical Termination for Non-Direct Venting. 

Note:  When properly installed, vent system is designed to 
drain condensate and will not be affected by rainwater. 

For horizontal non-direct venting, extend PVC pipe at least 
6 inches from structure and 12 inches above grade or 
above average snow accumulation.  See Figure 16. 

 

Figure 16.  Horizontal Termination for Non-Direct Venting. 

COMBUSTION AND VENTILATION AIR (non-direct 
vent) 

The total amount of combustion and ventilation air provided 
within the building must equal the requirements of all gas 
appliances in the building.  You must also allow for 
reduction of air available for combustion and ventilation 
caused by exhaust fans, range hoods and fireplaces.  
Sufficient air must be provided to ensure there will not be a 
negative pressure in fu rnace room or space.  In addition, 

there must be a positive seal between fu rnace and return-
air duct to avoid pulling air from furnace room. 

Provide for adequate combustion and ventilation air in 
accordance with Section 5.3, Air for Combustion and 
Ventilation, of the National Fuel Gas Code, ANSI 
Z223.1/NFPA 54, or Sections 7.2, 7.3 or 7.4 of CAN/CGA 
B149 Installation Codes, or applicable provisions of local 
building codes. 

 

 

WARNING

: Furnaces and any other fuel burning 

appliances must have enough fresh air for proper 
combustion.  Lack of adequate combustion air could cause 
the furnace to produce carbon monoxide and may result in 
nausea or asphyxiation. 

Excessive exposure to air contaminated with chlorine, 
fluorine, bromine and iodine may result in safety and 
performance related problems.  The following types of 
installation may require outdoor air for combustion (or direct 
venting) due to chemical exposures: 

??

Commercial buildings, repair garages, beauty parlors, 
and so on 

??

Buildings with indoor pools  

??

Furnaces installed in laundry rooms 

??

Furnaces installed in hobby or craft rooms 

??

Furnaces installed near chemical storage rooms 

??

Furnaces installed near exhaust fans which vent the 
above areas  

Exposure to the following substances in the combustion air 
supply may also require outdoor air for combustion: 

??

Aerosols  

??

Permanent wave solutions  

??

Chlorinated waxes, bleaches a nd cleaners  

??

Cat litter 

??

Chlorine-based swimming pool chemicals  

??

Cleaning solvents  

??

Paint removers and varnishes  

??

Adhesives 

??

Anti-static fabric softeners  

??

Most refrigerants 

 

 

WARNING

:  Combustion air that contains chlorine, 

fluorine, bromine or  iodine could cause corrosion in heat 
exchanger and may result in nausea or death by 
asphyxiation. 

UNCONFINED SPACE INSTALLATION (non-direct 
vent) 

The National Fuel Gas Code, ANSI Z223.1/NFPA 54 and 
CAN/CGA B149 Installation Codes do not require that you 
m ake special provisions for combustion and ventilation air 
when furnace is in an "unconfined space" and building is 
not of "unusually tight construction". 

??

"Unconfined spaces" have a volume of at least 50 
cubic feet per 1000 Btu per hour combined input rating 

Summary of Contents for Thermo Pace Downflow/Horizontal Furnace

Page 1: ...tion may arise For more information solutions to particular problems or clarification contact your local distributor or the manufacturer ATTENTION USER Your furnace installer should give you the docum...

Page 2: ...o situations that could cause or result in minor or moderate injury or property damage For a safe and reliable installation be sure to read and follow all warnings and cautions We also use the words m...

Page 3: ...e Figure 1 Figure 1 Furnace Installation Positions CAUTION Do not install furnace in an area subject to freezing temperatures Doing so could cause condensate to freeze This furnace operates best when...

Page 4: ...rnace room When a cooling unit is installed with this furnace the furnace must be installed parallel with or on the upstream side of the cooling unit to avoid condensation in furnace heat exchanger Wi...

Page 5: ...5 15 16 15 3 4 0 1 0 1 18 0 2 OR 3 72 000 3 4 20 1 2 18 15 16 18 3 4 0 1 0 1 18 0 2 OR 3 90 000 1 2 17 1 2 15 15 16 15 3 4 0 1 0 1 18 0 2 OR 3 90 000 3 4 20 1 2 18 15 16 18 3 4 0 1 0 1 18 0 2 OR 3 108...

Page 6: ...right and maintain clearances as described previously Figure 7 Suspending Using Threaded Rod SECTION 4 PROVIDING VENTING AND COMBUSTION AIR This furnace must be connected to a plastic venting system...

Page 7: ...thin 10 feet of an adjacent building Do not locate termination underneath a veranda porch or deck IN THE UNITED STATES Allow a minimum clearance of 4 feet from electric meters gas meters regulators an...

Page 8: ...ON DIRECT VENTING instructions A non direct vented furnace takes all air for combustion from the room in which furnace is installed Non direct venting requires only one pipe for venting the flue gases...

Page 9: ...Left Vent Top Vent Right Vent Downflow Position Top Vent Right Vent Horizontal Air Left Position Top Vent Left Vent Horizontal Air Right Position Figure 9 Venting Options Dashed lines show optional co...

Page 10: ...reducer bushing in flue outlet See Table 1 or Table 2 for correct vent diameter for your application 11 Complete installation of venting system with field supplied parts 12 Support vent pipe at furna...

Page 11: ...pending on altitude elevation of the installation gas input rating of furnace diameter of the air and vent pipes number of elbows Note that some of the larger furnace models may require a high altitud...

Page 12: ...5 20 15 108 000 3 40 40 40 40 40 40 40 40 See Note 2 below 126 000 3 40 40 40 40 35 30 25 20 54 000 2 40 40 40 40 40 40 40 40 72 000 2 21 18 14 11 72 000 3 40 40 40 40 40 40 40 40 5001 6000 90 000 3 4...

Page 13: ...burner enclosure Seal air pipe to collar with RTV silicone caulk See Figure 14 Note When venting with 3 inch pipe a 3 X 2 reducer must be used Locate reducer as close as possible to combustion air in...

Page 14: ...60 55 50 108 000 3 85 80 75 70 65 60 55 50 See Note 2 126 000 3 55 50 45 40 35 30 25 20 54 000 2 43 40 37 33 30 27 24 20 72 000 2 21 18 14 11 72 000 3 150 150 150 150 150 150 150 150 5001 6000 90 000...

Page 15: ...54 or Sections 7 2 7 3 or 7 4 of CAN CGA B149 Installation Codes or applicable provisions of local building codes WARNING Furnaces and any other fuel burning appliances must have enough fresh air for...

Page 16: ...of the spaces meet the criteria above for an unconfined space not of unusually tight construction The total input of all gas appliances within the combined space must be considered in making this dete...

Page 17: ...7 76 000 90 000 45 8 100 000 108 000 54 9 127 000 126 000 63 9 127 000 144 000 72 10 157 000 Example Furnace is 90 000 Btu per hour input and is to be installed in a confined space that contains no o...

Page 18: ...TAL AIR LEFT POSITION 1 See Figure 22 for drain trap location for your installation In horizontal positions condensate drain trap must be mounted through bottom side of furnace 2 From parts package fi...

Page 19: ...n furnace gas supply piping so it will not interfere with removal of burner assembly front door or blower door for servicing Make sure gas piping is large enough for all appliances connected to it to...

Page 20: ...rounding by attaching grounding source to green wire in furnace junction box Follow local codes or in the absence of local codes the current National Electrical Code ANSI NFPA 70 or Canadian Electrica...

Page 21: ...G terminals connected Fan Timer energizes main blower on heating speed A call for cooling while in constant fan mode causes main blower to change from heating to cooling speed Sixty seconds after the...

Page 22: ...Page 22 Installer s Information Manual Figure 26 Furnace Wiring Diagram...

Page 23: ...it passes through End ductwork outside furnace space See Figure 27 for floor cutout dimensions for combustible floor base Figure 27 Floor Cutout Dimensions Note A combustible floor base available from...

Page 24: ...cooling system operation FILTER MOUNTING Use a downflow filter kit field fabricated filter cabinet or a return air filter grille Field fabricated filter cabinets should allow spacing between filter a...

Page 25: ...as explained above NOTE Pilot flame adjustment was checked at the factory and should not require adjustment However pilot adjustment is possible if necessary 1 Remove three screws holding burner acces...

Page 26: ...heck obtain gas heating value at your location from local supplier You will need a stopwatch to measure actual gas input 1 Gas supply pressure must be between 5 and 7 inches W C for natural gas See Se...

Page 27: ...ve 2 000 feet the furnace must be derated 4 for each 1 000 foot above sea level It is the installer s responsibility to see that the furnace input rate is adjusted properly Derating must be achieved b...

Page 28: ...urner carry overs Replace screws 9 Replace burner access panel using three screws removed in step 3 10 Open equipment shut off valve in gas supply line just ahead of furnace 11 Set room thermostat to...

Page 29: ...e poor cooling performance or air conditioning coil freeze up High duct system static pressure is an indication of an overly restrictive duct system Static pressure in excess of 0 5 inches W C indicat...

Page 30: ...instructions in Section 14 Checking Gas Input Rate If air temperature rise is still below temperature rise range specified less heating airflow is needed Change blower heating speed to a lower setting...

Page 31: ...ee Return air duct must be physically sound sealed to furnace casing and ending outside the space containing furnace Supply air ducts and return air ducts must be clear and free and without air leaks...

Page 32: ...ATURAL GAS CONVERSION KIT ABOVE 6000 FEET Includes natural gas regulator spring kit natural gas pilot orifice main burner orifices and high altitude pressure switch COMBUSTIBLE FLOOR BASE Required for...

Reviews: