background image

All installations and services must be performed by qualified service personnel. 

II.  GENERAL INSTRUCTIONS - READ BEFORE START OF INSTALLATION 

 
1.  The  heating  output  capacity  of  the  furnace  proposed  for  installation  should  be  based  on  a  heat  loss  calculation 
made according to the manuals provided by the Air Conditioning Contractors of America (ACCA) or the American 
Society of Heating, Refrigeration and Air Conditioning Engineers, Inc. (ASHRAE). 
 
2.  All  local  codes  and/or  regulations  take  precedence  over  the  instructions  in  this  manual  and  should  be  followed 
accordingly. In the absence of local codes, installation must conform with these instructions and regulations of the 
National Fire Protection Association, and to the provisions of the National Electrical Code (ANSI/NFPA 70-1999 or 
latest edition).  
 
3. The installed furnace must be level and positioned in a central location with respect to outlet registers. It should be 
located near the chimney to minimize any horizontal run of flue pipe, which may be required. 
 
4. A furnace installed in a residential garage must be installed so the burner and ignition source are located higher 
than 18 inches above the floor, unless the required combustion air is taken from the exterior of the garage. Also, the 
furnace must be located or protected to avoid physical damage by vehicles. 
 

c

WARNING: This furnace is not to be used as a construction heater.  

 
5. Listed below are definitions of "COMBUSTIBLE MATERIAL" and "NON-COMBUSTIBLE MATERIAL." 
 
COMBUSTIBLE MATERIAL: 
Material made of or surfaced with wood, compressed paper, plant fibers, plastics, or other material that will ignite 
and burn, whether flame resistant or not. 
 
NON-COMBUSTIBLE MATERIAL: 
Material  that  is  not  capable  of  being  ignited  and  burned.    Such  materials  consist  entirely  of,  or  a  combination  of, 
steel, iron, brick, tile, concrete, slate, or glass.   
 

MINIMUM CLEARANCES TO COMBUSTIBLE MATERIALS 

 

TYPE OF UNIT 

MODEL NO.

1

 

FROM 

SIDES OF 

FURNACE 

FRONT 

TOP & 

SIDES OF 

PLENUM 

FROM THE 

FLUE/VENT 

REAR 

HIGHBOY 

VHF-A** 

0” 

Note 

1

 

1” 

7” 

0” 

 

 

 

Notes: 

1

 VHF-A** front clearance  6” for Closet, 24” for Alcove. 

 
 
The minimum clearances listed in the preceding table are for fire protection.  Clearance for servicing the front of the 
furnace should be at least 24 inches.  A clearance of 24 inches is recommended for passage to all points on the 
furnace requiring service access.   
 
NOTE: The VHF-A** furnaces may be installed on combustible flooring.  
 
NOTE: The VHF-A** furnace is approved for closet installation. If the VHF-A** is installed in a closet, it requires 
two openings in the closet door for combustion air, each having a minimum area of 162 sq. inches.  This free area for 
the VHF-A** intentionally exceeds the recommended minimum free area of 2 square inches per 1000 BTUH of 
input rate. 

Summary of Contents for Spirit VHF-ABE

Page 1: ...nce Improper installation adjustment alteration service or maintenance can cause a fire or explosion resulting in property damage personal injury or loss of life For assistance or additional informati...

Page 2: ...ry substantial property damage or death See Page 5 cWARNING THE HEAT EXCHANGER MUST BE CLEANED BY A QUALIFIED SERVICE PERSON See Page 8 cCAUTION DO NOT ATTEMPT TO MAKE REPAIRS YOURSELF See Page 9 cWAR...

Page 3: ...RETURN AIRFLOW AND AIR TEMPERATURE 3 D FILTERS MOUNTED EXTERNAL TO FURNACE 4 E LIMIT POSITION AND LOCATION 5 F BURNER INSTALLATION 6 G BURNER SPECIFICATIONS AND APPLICATIONS 7 H HEAT EXCHANGER CLEANI...

Page 4: ...located or protected to avoid physical damage by vehicles cWARNING This furnace is not to be used as a construction heater 5 Listed below are definitions of COMBUSTIBLE MATERIAL and NON COMBUSTIBLE MA...

Page 5: ...power venter manufacturer to design and assemble a satisfactory power vent system A VENTING NOTE On the VHF A it is possible to rotate the flue elbow which is factory installed for vertical discharge...

Page 6: ...tioning cooling the furnace should be installed parallel with or on the upstream side of the evaporator coil to avoid condensation in the furnace heat exchanger If the cooling unit is installed with a...

Page 7: ...essary to cut the return air opening in the side or rear casing depending upon the needs of the specific installation The filter rack provided with the furnace refer to Fig 2 will serve as a template...

Page 8: ...ange of the filter rack Connect the return air plenum to the filter rack and slide the filter into place Dimensions for adapting the return air plenum to the filter rack are provided See Fig 2 E LIMIT...

Page 9: ...ig 4 This retainer secures the chamber during shipping and helps to maintain insertion depth DO NOT remove this retainer when installing burner Fig 4 Typical location of the overfire air tap and compo...

Page 10: ...CONE FOR EXAMPLE A NOZZLE RATED AT 0 65 GPH 100 PSIG THAT PROVIDES AN 80 SPRAY ANGLE AND A HOLLOW SPRAY PATTERN WOULD BE ABBREVIATED IN THE TABLE AS 0 65 X 80 A For more specific burner information c...

Page 11: ...With access to the inside of the heat exchanger through the burner area clean out openings and vent pipe connection it is possible to use a long flexible wire brush and an industrial type vacuum clean...

Page 12: ...discoloration of materials and damage from rust or corrosion FLUE PIPE VENT PIPE OR CONNECTOR The furnace vent pipe should be inspected for signs of rust corrosion pitting or holes in pipe and leakage...

Page 13: ...ystem and home cWARNING To avoid injury from moving parts hot surfaces or electrical shock shut off the power to the furnace before removing any furnace access doors to service the air filters The fil...

Page 14: ...MASONRY CHIMNEY W METAL LINER FUEL LINE FILTER DRAFT CONTROL COMBUSTION TESTS Operate burner at least 10 minutes before CO2 in stack pipe INITIAL SERVICE SERVICE SERVICE INSTALLATION Draft Over fire D...

Page 15: ...All installations and services must be performed by qualified service personnel 12 APPENDIX A Replacement Parts List...

Page 16: ...All installations and services must be performed by qualified service personnel 13...

Page 17: ...All installations and services must be performed by qualified service personnel 14...

Page 18: ...All installations and services must be performed by qualified service personnel 15...

Page 19: ...All installations and services must be performed by qualified service personnel 16 APPENDIX B Wiring Diagrams BLOWER SPEED TAPS COOL A C Tap HEAT Heating Tap LOW Constant air or Dehumifier...

Page 20: ...All installations and services must be performed by qualified service personnel 17...

Reviews: