background image

  

Installing and Operating Instructions 

1592020062

 

 

1592020062 XR60CX GB ES m&M r1.1 05.03.2007.doc 

XR60C 

3/5 

AFH Differential for temperature alarm/ fan recovery: 

(0,1÷25,5°C; 1÷45°F) Intervention 

differential for recovery of temperature alarm. It’s also used for the restart of the fan when the 
FSt temperature is reached  

ALd  Temperature alarm delay

: (0÷255 min) time interval between the detection of an alarm 

condition and alarm signalling. 

dAO Exclusion of temperature alarm at startup

: (from 0.0 min to 23.5h) time interval between the 

detection of the temperature alarm condition after instrument power on and alarm signalling. 

CONDENSER TEMPERATURE ALARM 

AP2  Probe selection for temperature alarm of condenser: nP

 = no probe; 

P1

 =thermostat probe; 

P2 = 

evaporator probe; 

P3

 =configurable probe; 

P4

 = Probe on Hot Key plug. 

AL2 Low temperature alarm of condenser

:

 

(-55÷150°C) when this temperature is reached the 

LA2 alarm is signalled, possibly after the Ad2 delay. 

Au2 High temperature alarm of condenser

:

 

(-55÷150°C) when this temperature is reached the 

HA2 alarm is signalled, possibly after the Ad2 delay. 

AH2 Differential for temperature condenser alarm recovery

:

 

(0,1÷25,5°C; 1÷45°F) 

Ad2 Condenser temperature alarm delay

: (0÷255 min) time interval between the detection of the 

condenser alarm condition and alarm signalling. 

dA2  Condenser temperature alarm exclusion at start up

: (from 0.0 min to 23.5h, res. 10min) 

bLL  Compressor off with low temperature alarm of condenser

:

 n = no: 

compressor keeps on 

working

; Y = yes, 

compressor is switched off till the alarm is present, in any case regulation 

restarts after AC time at minimum.

 

AC2 Compressor off with high temperature alarm of condenser

:

 n = no: 

compressor keeps on 

working

; Y = yes, 

compressor is switched off till the alarm is present, in any case regulation 

restarts after AC time at minimum.

 

DIGITAL INPUT  
i1P  Digital input polarity: oP: 

the digital input is activated by opening the contact; 

CL: 

the digital 

input is activated by closing the contact.

 

i1F Digital input configuration: EAL 

= external alarm: “EA” message is displayed; 

bAL 

= serious 

alarm “CA” message is displayed. 

PAL 

= pressure switch alarm, “CA” message is displayed; 

dor

 = door switch function; 

dEF

 = activation of a defrost cycle; 

AUS 

=not enabled; 

Htr 

= kind of 

action inversion (cooling – heating); 

FAn = not set it; ES = 

Energy saving. 

did

:

 

(0

÷

255 min) 

with

 

i1F= EAL or i1F = bAL digital input alarm delay:

 delay between the 

detection of the external alarm condition and its signalling. 

with

 

i1F= dor: door open signalling delay 

with i1F = PAL: time for pressure switch function: 

time interval to calculate the number of 

the pressure switch activation. 

nPS Pressure switch number:

 (0 

÷

15) Number of activation of the pressure switch, during the “

did

” 

interval, before signalling the alarm event (I2F= PAL).  

If the nPS activation in the did time is reached, switch off and on the instrument to 

restart normal regulation. 

odc  Compressor and fan status when open door:

   

no

 = normal; 

Fan

 = Fan OFF; 

CPr 

Compressor OFF; 

F_C

 = Compressor and fan OFF.  

rrd  Outputs restart after doA alarm: no = 

outputs not affected by the doA alarm;  

yES = 

outputs 

restart with the doA alarm;  

HES Temperature increase during the Energy Saving cycle :

 (-30,0°C

÷

30,0°C/-22÷86°F) it sets 

the increasing value of the set point during the Energy Saving cycle.  

OTHER 
Adr   Serial  address

 (1÷244): Identifies the instrument address when connected to a ModBUS 

compatible monitoring system. 

PbC Type of probe:

 it allows to set the kind of probe used by the instrument: 

PbC

 = PBC probe, 

ntc 

NTC probe. 

onF  Enrgy saving key enabling: nu = 

disabled; 

oFF = not set it

ES = 

enabled. 

dP1 Thermostat probe display 

dP2 Evaporator probe display 
dP3 Third probe display

optional

dP4 Fourth probe display

rSE  Real set point: 

(readable only), it shows the set point used during the energy saving cycle or 

during the continuous cycle. 

rEL Software release 

for internal use

Ptb Parameter table code: 

readable only

8.

 

DIGITAL INPUT 

(ENABLED WITH P3P = N)

 

The free voltage digital input is programmable in different configurations by the “

i1F

” parameter. 

8.1

 

DOOR SWITCH INPUT  (i1F = dor) 

It signals the door status and the corresponding relay output status through the “

odc

” parameter: 

no

 

= normal (any change); 

Fan

 = Fan OFF; 

CPr

 = Compressor OFF; 

F_C

 = Compressor and fan OFF. 

Since the door is opened, after the delay time set through parameter “

did

”, the door alarm is 

enabled, the display shows the message “

dA

” and 

the regulation restarts is rtr = yES.

 The alarm 

stops as soon as the external digital input is disabled again. With the door open, the high and low 
temperature alarms are disabled. 

8.2

 

GENERIC ALARM (i1F = EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before signalling the 

EAL

” alarm message. The outputs status don’t change. The alarm stops just after the digital input is 

de-activated. 

8.3

 

SERIOUS ALARM MODE (i1F = bAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the “

CA

” alarm 

message. The relay outputs are switched OFF. The alarm will stop as soon as the digital input is de-
activated. 

8.4

 

PRESSURE SWITCH (i1F = PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached the number of 

activation of  the “

nPS

” parameter, the “

CA

” pressure alarm message will be displayed. The 

compressor and the regulation are stopped. When the digital input is ON the compressor is always 
OFF. 

If the nPS activation in the did time is reached, switch off and on the instrument to restart 

normal regulation. 

8.5

 

START DEFROST (i1F = dFr) 

It starts a defrost if there are the right conditions. After the defrost is finished, the normal regulation 
will restart only if the digital input is disabled otherwise the instrument will wait until the “MdF” safety 
time is expired. 

8.6

 

INVERSION OF  THE KIND OF ACTION: HEATING-COOLING (i1F = Htr) 

This function allows to invert the regulation of the controller: from cooling to heating and viceversa. 

8.7

 

ENERGY SAVING (i1F = ES) 

The Energy Saving function allows to change the set point value as the result of the SET+ HES 
(parameter) sum. This function is enabled until the digital input is activated. 

8.8

 

DIGITAL INPUTS POLARITY  

The digital input polarity depends on the “

i1P

” parameter. 

i1P=CL

: the input is activated by closing the contact.

 

i1P=OP

: the input is activated by opening the contact 

9.

 

TTL SERIAL LINE – FOR MONITORING SYSTEMS 

The TTL serial line, available through the HOT KEY connector, allows by means of the external 
TTL/RS485 converter, 

XJ485-CX

, to connect the instrument to a monitoring system 

ModBUS-RTU

 

compatible  such as the  X-WEB500/3000/300. 

10.

 

X-REP OUTPUT – OPTIONAL 

As optional, an X-REP can be connected to the instrument, trough the HOY KEY 
connector. The X-REP output 

EXCLUDES 

 the serial connection.

 

 

To connect the X-REP to the 
instrument the following connectors 
must be used CAB-51F(1m), CAB-
52F(2m), CAB-55F(5m), 

11.

 

INSTALLATION AND MOUNTING 

 

Instrument 

XR60CX

 shall be mounted on vertical panel, in a 

29x71 mm hole, and fixed using the special bracket supplied.  
The temperature range allowed for correct operation is 0

÷

60 °C. 

Avoid places subject to strong vibrations, corrosive gases, 
excessive dirt or humidity. The same recommendations apply to 
probes. Let air circulate by the cooling holes. 
 

12.

 

ELECTRICAL CONNECTIONS 

The instrument is provided with screw terminal block to connect cables with a cross section up to 2,5 
mm

2

. Before connecting cables make sure the power supply complies with the instrument’s 

requirements. Separate the probe cables from the power supply cables, from the outputs and the 
power connections. Do not exceed the maximum current allowed on each relay, in case of heavier 
loads use a suitable external relay. 

12.1

 

PROBE CONNECTION 

The probes shall be mounted with the bulb upwards to prevent damages due to casual liquid 
infiltration. It is recommended to place the thermostat probe away from air streams to correctly 
measure the average room temperature. Place the defrost termination probe among the evaporator 
fins in the coldest place, where most ice is formed, far from heaters or from the warmest place during 
defrost, to prevent premature defrost termination. 

13.

 

HOW TO USE THE HOT KEY  

13.1

 

HOW TO PROGRAM A HOT KEY FROM THE INSTRUMENT (UPLOAD) 

1.

 

Program one controller with the front keypad. 

2.

 

When the controller is ON, insert the “

Hot key

” and push 

9

 key; the  

"uPL" 

message 

appears followed a by flashing 

“End”

 

3.

 

Push “

SET”

 key and the 

End

 will stop flashing. 

4.

 

Turn OFF the instrument remove the 

“Hot Key”, 

then turn it ON again. 

 

NOTE

: the “

Err

” message is displayed for failed programming. In this case push again 

9

 key if you 

want to restart the upload again or remove the “

Hot key

” to abort the operation. 

13.2

 

HOW TO PROGRAM AN INSTRUMENT USING A HOT KEY 

(DOWNLOAD) 

1.

 

Turn OFF the instrument. 

2.

 

Insert  a 

programmed “Hot Key” into the 5 PIN receptacle 

and then turn the Controller ON. 

3.

 

Automatically the parameter list of the 

“Hot Key”

 is downloaded into the Controller memory, 

the “

doL

” message is blinking followed a by flashing 

“End”.

 

4.

 

After 10 seconds the instrument will restart working with the new parameters.  

5.

 

Remove the 

“Hot Key”.

NOTE 

the message “

Err

” is displayed for failed programming. In this case turn the unit off and then 

on if you want to restart the download again or remove the “

Hot key

” to abort the operation. 

14.

 

ALARM SIGNALS 

Message  

Cause 

Outputs 

“P1” 

Room probe  failure 

Compressor output acc. to par. “Con” and 
“COF” 

“P2” 

Evaporator probe  failure 

Defrost end is timed 

“P3” 

Third probe  failure 

Outputs unchanged 

“P4” 

Fourth probe  failure 

Outputs unchanged 

“HA” 

Maximum temperature alarm 

Outputs unchanged. 

“LA”  

Minimum temperature alarm 

Outputs unchanged. 

"HA2" 

Condenser high temperature 

It depends on the “Ac2” parameter 

Summary of Contents for Jewett CTF306

Page 1: ...Installation and Operation Manual Thermo Scientific Jewett CTF306 Blood Plasma Freezers...

Page 2: ...2009 Thermo Fisher Scientific All rights reserved Suva is a registered trademark of DuPont All other trademarks are the property of Thermo Fisher Scientific Inc and its subsidiaries...

Page 3: ...peration Do not adjust the refrigerant valves or the temperature control 7 Use of electrical characteristics other than those specified on the serial plate will cause permanent damage to the mechanism...

Page 4: ...2...

Page 5: ...3...

Page 6: ...ormed according to the temperature measured by the thermostat probe with a positive differential from the set point if the temperature increases and reaches set point plus differential the compressor...

Page 7: ...2 100 P2 CCt Compressor ON time during continuous cycle 0 0 24 0h res 10min Allows to set the length of the continuous cycle compressor stays on without interruption for the CCt time Can be used for i...

Page 8: ...The alarm stops just after the digital input is de activated 8 3 SERIOUS ALARM MODE i1F bAL When the digital input is activated the unit will wait for did delay before signalling the CA alarm message...

Page 9: ...P Third probe presence n not present Y pres n Pr2 O3 Third probe calibration 12 12 C 120 120 F 0 0 0 Pr2 P4P Fourth probe presence n not present Y pres n Pr2 O4 Fourth probe calibration 12 12 C 120 12...

Page 10: ...ce to removal of the dollar bill test strip should be felt Check the perimeter of the door If the latch is loose see latch adjusting information 5 Replace cover plate A Note To accomplish different of...

Page 11: ...line solenoid will not open 10 Repair or replace coil 1 Low voltage to unit 1 Determine reason and correct 2 Start capacitor failure or wrong 2 Replace start capacitor 3 Run capacitor failure or wrong...

Page 12: ...nt 1 Leak check and repair 2 Control contacts stuck or frozen 2 Clean contacts or replace control 3 Refrigerated air space has an excessive load 3 Determine reason and correct 4 Dirty Condenser 4 Clea...

Page 13: ...lve 1 Defrost duration too long 1 Adjust defrost termination 2 Fan delay not delaying fans after defrost period 2 Defective fan delay thermostat Replace 3 Defective timer 3 Replace N Ice accumulating...

Page 14: ...unter diese RoHS Anweisungfallen finden Sie unter www thermo com Conformit WEEE Questo prodotto deve rispondere alla direttiva dell Unione Europea 2002 96EC in merito ai Rifiuti degli Apparecchi Elet...

Page 15: ...e information can be found on the dataplate attached to the equipment If available please provide the date purchased the source of purchase manufacturer or specific agent rep organization and purchase...

Page 16: ...Thermo Fisher Scientific Inc 275 Aiken Road Asheville NC 28804 United States www thermofisher com 306650H01 Rev D...

Reviews: